HomeMy WebLinkAbout2327•
ORDINANCE NO. 9,'2.),a7
AN ORDINANCE
regulating
Section 14
and of the
of the City of Port Angeles
electrical wiring, amending
.12.100 of Ordinance 2325
Port Angeles Municipal Code.
BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF PORT
ANGELES as follows:
Section 1. Section 14.12.100 of Ordinance 2325 and of
the Port Angeles Municipal Code are each hereby amended to read
as follows:
14.12.100 Regulatory Provisions.
A. 1. Woodworking Plants. The production areas of saw
mills and commercial and industrial woodworking plants shall be
wired in rigid metal conduit, intermediate metal conduit, M.I.
cable, MC cable, or, if not subject to mechanical injury or
vibration, E.M.T. with compression ring fittings.
2. The following premises shall be wired with rigid
metal conduit, intermediate metal conduit, rigid nonmetallic
conduit, liquid -tight flexible metal conduit, or MI cable:
(a) Portions of dairies, laundries, car washes
and other locations which are subject to continuous moisture.
See Section 300 -6 of the NEC.
(b) Portions of docks, piers and wharfs which are
subject to continuous moisture.
(c) Premises designated elsewhere in this
Chapter.
3. The following premises shall be wired with metal
raceways, busways, MC, MI cable, or rigid nonmetallic conduit
encased in not less than two (2) inches of concrete:
(a) All institutional, educational and health
care occupancies as defined in Article 100 of the NEC.
Exception No. 1: For signal and control
circuits, open cable wiring approved for the purpose shall be
permitted for Class 2 signal and control,circuits as defined in
-1-
Article 725 of the National Electrical Code for other than the
following circuits and /or systems: nurse call systems, fire
alarm systems actuated at manual stations, electric water flow
alarm devices in connection with sprinkler systems, automatic
fire or smoke or products of combustion devices, alarms required
for systems used in the piping of nonflammable medical gases, and
communications systems used for issuing instructions during
emergency conditions.
Exception No. 2: Open cable wiring approved
for the purpose of NFPA Bulletin No. 71 shall be permitted for
Central Station Protective Systems installed and operator- manned
and supervised in accordance with the latest adopted edition of
the National Fire Protection Association Bulletin No. 71 in other
than hospitals and nursing homes.
Exception No. 3: Single -story boarding homes
having direct grade entrance and egress, and alcohol treatment
facilities (other than detoxification facilities) licensed for
less than 10 residents by the Department of Social and Health
Services.
Exception No. 4: Unlicensed health care
facilities except in patient care areas.
(b) All premises in Fire Zone #1 as defined in
Section 14.24.010(A) PAMC.
4. The following premises shall be wired with metal
raceways, busways, cable trays, SNM, TC, MC, MI cable, or rigid
nonmetallic conduit encased in not less than two (2) inches of
concrete:
(a) Industrial plants. Industrial plants, except
that open conductors of No. 4/0 or larger size may be installed
on insulators not less than 20 feet above floor or working
surface level in accordance with Article 320 of the National
Electrical Code.
Exception No. 1: For signal and control
circuits, other than those defined as Class 1 circuits per
National Electrical Code, Sections 725 -3(a) and 725 -4, open cable
wiring approved for the purpose shall be permitted for Class 2
signal and control circuits installed in accordance with Article
725 of the National Electrical Code.
Exception No. 2: Open cable wiring approved
for the purpose (NFPA Bulletin No. 71) shall be permitted for
Central Station Protective Systems installed and operator - manned
and supervised in accordance with the latest adopted edition of
the National Fire Protection Association Bulletin No. 71.
Exception No. 3: Rigid nonmetallic conduit
may be installed in areas outlined in National Electrical Code
Section 300 -6.
(b) Multifamily Occupancy Buildings. Feeder and
Sub- feeders in such buildings (i.e., apartment buildings, hotels,
motels and dormitories) of two or more stories, not including
basement, shall be wired in a raceway(s).
(c) High Rise Buildings.
5. Within buildings, all mains, sub - feeders, circuits
exceeding 300 volts between conductors, and circuits exceeding
150
for
volts
to
6.
services
7.
ground shall be installed in approved raceways.
Rigid Non - Metallic conduit installed underground
shall have rigid conduit steel ell's.
All wiring in unused spaces underneath buildings
shall be installed in rigid metal conduit, electrical metallic
tubing, flexible metal conduit or other approved raceways, except
where provided in Articles 336 and 339 of the NEC for dwelling
occupancies.
8. On an addition or rewire of an existing commercial
facility, all wiring that is newly installed, rerouted, or in any
other way modified, as determined by the Electrical Inspector,
will meet the requirements of this Chapter.
-3-
9. When 65% of the existing electrical facilities
have been or are expected to be modified, as determined by the
Electrical Inspector, the entire electrical wiring facilities of
the commercial establishment's service shall meet the
requirements of this Chapter.
10. An exception shall be granted by the Electrical
Inspector to this section but not to the NEC or WAC, in the event
that the commercial facility is determined to be an historic site
or qualified for historic preservation, as determined by the
State Historical Preservation Officer.
11. On rewires or additions to non - commercial
facilities for which all permissions and permits have been
obtained for conversion to a commercial use, the same criteria
will apply as if the facility were originally of commercial use.
B. The connections for electric meters shall be so located
that meters will be readily accessible at all times. Meters
shall not be permitted inside buildings or within carports or
porches without special approval of the Office of the Electrical
Inspector.
D. For all motors, other than portable motors, located in
industrial or manufacturing establishments, such as mills, ware-
houses, foundries, mercantile and similar establishments, such as
grocery stores and butcher shops, factories and machine shops,
the wiring method employed shall be only rigid conduit. Elec-
trical metal tubing or flexible metal conduit may be used, pro-
vided that it is not exposed to mechanical injury, or as per-
mitted in Section 400.4 of the National Electrical Code.
D. All kitchens, bathrooms, toilet rooms, laundry rooms
and similar locations containing plumbing fixtures, shall have a
separate wall switch for lighting fixtures. No pull chains shall
be permitted.
Section 2 Severability. If any provision of this
section or its application to any person or circumstance is held
-4-
invalid, the remainder of the section or the application of the
provision to other persons or circumstances is not affected.
Section 3 Effective Date. This Ordinance shall take
effect as provided by law.
PASSED by the City Council of the City of Port Angeles
at a regular meeting of said Council held on the 53d,_, day of
, 1985.
jM ae4i
dri-4/0Y,
' TEM
ATTEST:
Me ri A. Lannoye, Citj Clerk
APPRO AS TO FO
Craig D.-Knutson, City Attorney
PUBLISHED: (p)