PREPARED 12/05/16, 10:52:48 INSPECTION TICKET PAGE
CITY OF PORT ANGELES INSPECTOR: JAMES LIERLY DATE 12/05/16
------------------------------------------------------------------------------------------------
ADDRESS . : 2503 S LINCOLN ST SUBDIV:
CONTRACTOR ACE MICHAELS INC PHONE (360) 460-6172
OWNER KATHY S CARSEY/JANET J COLES PHONE (303) 416-0286
PARCEL 06-30-10-5-0-0940-0000-
APPL NUMBER: 16-00001325 RES ADDITION
------------------------------------------------------------------------------------------------
PERMIT: BPR 00 BUILDING PERMIT - RESIDENTIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
BLFO 01 10/13/16 JLL BLDG FOUNDATION
10/13/16 AP October 13, 2016 10:37:01 Am jlierly.
Mike 460-6172
October 13, 2016 4:54:05 PM jlierly.
BL2 01 10/18/16 JLL BLDG FOUNDATION STEM WALL
10/19/16 AP October 18, 2016 8:52:15 AM jlierly.
Mike 460-6172
October 19, 2016 12:09:24 PM jlierly.
BEXS 01 10/28/16 JLL BLDG EXTERIOR SHEETING
10/28/16 AP October 28, 2016 12:29:33 PM jlierly.
Mike Caudlill
Oc tober 28, 2016 4:08:20 PM jlierly.
BAIR 01 12/ 16 BLDG AIR SEAL
December 5, 2016 10:23:04 AM jlierly.
Mike 460-1325
BL3 01 12/05/16 BLDG FRAMING
December 5, 2016 10:23:28 AM jlierly.
----------- ------- ------------- COMMENTS AND NOTES --------------------------------------
CITY OF PORT ANGELES
DEPARTMENT OF COMMUNITY & ECONOMIC DEVELOPMENT- BUILDING DIVISION
321 EAST 5TH STREET, PORT ANGELES, WA 98362
Application Number . . . . . 16-00001325 Date 10/03/16
Application pin number . . . 916225
Property Address . . . . . . 2503 S LINCOLN ST
ASSESSOR PARCEL NUMBER: 06-30-10-5-0-0940-0000- REPORT SALES TAX
Application type description RES ADDITION on your state excise tax fofm
Subdivision Name
Property Use . . . . . . . . to the City of Port Angeles
Property Zoning . . . . . . . RS7 RESDNTL SINGLE FAMILY
Application valuation . . . . 14875 (Location Code 0502)
Application desc
new bedroom and 3/4 bath
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
KATHY S CARSEY/JANET J COLES ACE MICHAELS INC
2503 S LINCOLN ST 1329 W. 10TH ST.
PORT ANGELES WA 983626303 PORT ANGELES WA 98363
(303) 416-028G (360) 460-6172
Other struct info . . . . . HARD SURFACE AREA
------ - - - - - - -------- ------ ------------
Permit BUILDING PERMIT -RESIDENTIAL
Additional desc NEW BEDROOM AND 3/4 BATH
Permit Fee . . . . 277.75 Plan Check Fee 180.54
Issue Date . . . . 10/03/16 Valuation . . . . 14875
Expiration Date 4/01/17
Qty Unit Charge Per Extension
BASE FEE 95.75
13.00 14.0000 THOU BL-2001-25K (14 PER K) 182.00
----- ---------------------------------------------------------
Permit . . . . . . MECHANICAL PERMIT
Additional desc . . REMODEL MECH 2ND STORY
Permit Fee . . . . 86.85 Plan Check Fee .00
Issue Date . . . . 10/03/16 Valuation . . . . 0
Expiration Date 4/01/17
Qty Unit Charge Per Extension
BASE FEE 50.00
1.00 7.2500 EA ME-VENT FAN (SINGLE DUCT) 7.25
2.00 14.8000 EA ME-HEATER(SUSP/WALL/FLOOR-MTD) 29.60
----------------------------------------------------------------------------
Permit . . . . . . PLUMBING PERMIT
Additional desc
Permit Fee . . . . -85.00 Plan Check Fee .00
Issue Date . . . . 10/03/16 Valuation . . . . 0
Expiration Date 4/01/17
Qty Unit Charge Per Extension
BASE FEE 50.00
3.00 7.0000 EA PL-PLUMBING TRAP 21.00
1.00 7.0000 EA PL-WATER LINE 7.00
1.00 7.0000 EA PL-DRAIN VENT PIPING 7.00
----------------------------------------------------------------------------
Special Notes and Comments
September 20, 2016 2:46:07 PM tamiot.
Separate Permits are required for electrical work,SEPA,Shoreline,ESA,utilities,private and public improvements. This permit becomes
null and void if work or construction authorized is not commenced within 180 days,if construction or work is suspended or abandoned
for a period of 180 days after the work has commenced, or if required inspections have not been requested within 180 days from the
last inspection. I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions
of laws and ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does
not presume to give authority to violate or cancel the provisions of any state or local law regulating construction or the performance of
constru�fior.
V_ V_
Date Print Name Signature of Contractor or Authorized Agent Signature of Owner(if owner is builder)
T:Forms/Building Division/Building Permit
BUILDING PERMIT INSPECTION RECORD
PLEASE PROVIDE A MINIMUM 24-HOUR NOTICE FOR INSPECTIONS-
Building Inspections 417-4815 Electrical Inspections 417-4735
Public Works Utilities 417-4831 Backflow Prevention Inspections 417-4886
IT IS UNLAWFUL TO COVER, INSULATE OR CONCEAL ANY WORK BEFORE INSPECTED AND ACCEPTED.
POST PERMIT INCONSPICUOUS LOCATION. KEEP PERMIT AND APPROVED PLANS AT JOB SITE.
Inspec tion Type Date Accepted By Comments
FOUNDATION:
�-ootings
Stemwall
Foundation Drainage/Downspouts
Piers
Post Holes(Pole Bldgs.)
PLUMBING:
Under Floor/Slab
Rough-In
Water Line(Meter to Bldg)
Gas Line
Back Flow I Water
AIR SEAL:
Walls
Ceiling
FRAMING:
Joists/Girders/Under Floor
Shear Wall/Hold Downs
Walls/Roof/Ceiling
Drywall(interior Braced Panel Only)
T-Bar
INSULATION:
Slab
Wall/Floor/Ceiling
MECHANICAL:
Heat Pump/Furnace/FAU/Ducts
Rough-In
Gas Line
Wood Stove/Pellet/Chimney
Commercial Hood/Ducts
MANUFACTURED HOMES:
Footing/Slab
Blocking&Hold Downs
ISkirting
PLANNING DEPT. Separate Permit#s SEPA:
Parking/Lighting ESA:
Landscaping ISHORELINE:
FINAL INSPECTIONS REQUIRED PRIOR TO OCCUPANCY1 USE
Inspection Type Date Accepted By
Electrical 417-4735
Construction - R.W. PW /Engineering 417-4831
Fire 417-4653
Planning 417-4750
Building 417-4815
CITY OF PORT ANGELES
DEPARTMENT OF COMMUNITY & ECONOMIC DEVELOPMENT- BUILDING DIVISION
321 EAST 5TH STREET, PORT ANGELES, WA 98362
Page 2
Application Number . . . . . 16-00001325 Date 10/03/lG
Application pin number . . . 916225
--------------------------------------------------------------------------- REPORT SALES TAX
Special Notes and Comments on your state excise tax form
ELECTRICAL PERMIT REQUIRED FOR ANY AND ALL ELECTRICAL WORK.
September 22, 2016 2:38:19 PM pbarthol. to the City of Port Angeles
Work will result in the addition of a second story
bedroom/bathroom over existing structure. no land use (Location Code 0502)
problems anticipated.
Public Works Utility Engineering has no requirements for
this plan review.
----------------------------------------------------------------------------
Other Fees . . . . . . . . . STATE SURCHARGE 4.50
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 449.60 449.60 .00 .00
Plan Check Total 180.54 180.54 .00 .00
Other Fee Total 4.50 4.50 .00 .00
Grand Total 634.64 634.64 .00 .00
Separate Permits are required for electrical work,SEPA,Shoreline,ESA,utilities,private and public improvements. This permit becomes
null and void if work or construction authorized is not commenced within 180 days,if construction or work is suspended or abandoned
for a period of 180 days after the work has commenced, or if required inspections have not been requested within 180 days from the
last inspection. I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions
of laws and ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does
not presume to give authority to violate or cancel the provisions of any state or local law regulating construction or the performance of
construction.
Date Print Name Signature of Contractor or Authorized Agent Signature of Owner(if owner is builder)
T:Forms/Building Division/Building Permit
BUILDING PERMIT INSPECTION RECORD
— PLEASE PROVIDE A MINIMUM 24-HOUR NOTICE FOR INSPECTIONS—
Building Inspections 417-4815 Electrical Inspections 417-4735
Public Works Utilities 417-4831 Backflow Prevention Inspections 417-4886
IT IS UNLAWFUL TO COVER, INSULATE OR CONCEAL ANY WORK BEFORE INSPECTED AND ACCEPTED.
POST PERMIT INCONSPICUOUS LOCATION. KEEP PERMIT AND APPROVED PLANS AT JOB SITE.
Inspection Type Date Accepted By Comments
FOUNDATION:
Footings
Stemwall
Foundation Drainage/Downspouts
Piers
Post Holes(Pole Bldgs.)
PLUMBING:
Under Floor/Slab
Rough-in
Water Line(Meter to Bldg)
Gas Line
Back Flow/Water
AIR SEAL:
Walls
Ceiling
FRAMING:
Joists/Girders/Under Floor
Shear Wall/Hold Downs
Walls/Roof/Ceiling
Drywall(interior Braced Panel Only)
T-Bar
INSULATION:
Slab
Wall/Floor/Ceiling
MECHANICAL:
Heat Pump/Furnace/FAU/Ducts
Rough-In
Gas Line
Wood Stove/Pellet/Chimney
Commercial Hood/Ducts
MANUFACTURED HOMES:
Footing/Slab
Blocking&Hold Downs
ISkirting
PLANNING DEPT. Separate Permit#s SEPA:
Parking I Lighting ESA:
Landscaping ISHORELINE:
FINAL INSPECTIONS REQUIRED PRIOR TO OCCUPANCY1 USE
Inspection Type Date Accepted By
Electrical 417-4735
Construction - R.W. PW /Engineering 417-4831
Fire 417-4653
Planning 417-4750
Building 417-4815
WH
A R C H I kJ' C T S
319 s.peabody, suite bi port angeles,wa 98362
3 60.452.6116 fax 3 60.452.7o64
Ptoiecta Prpject No.
S.tjbfect, B
-y:
D�te: Sheet of
ea--p vr,
LINDBER(&NIrm
ARCH 1 -UCT - S.
319 S.Peabody,Suite B.,Port Angeles,
WA 98362
360.452.6116/fax 360.452,7064
Gonta0@,hndarqfr.co /www.Endarch.Gom
Project: 4'- 49.6 Proiect No.
Subject: ��By_: 4txv-
Date- 10 0/00 -Sheet of
SHEAR WALL SLMOAARY
L —V --T/L— Sw V-F DOST HOLD-DOWN
JA
14- --s43 5 M-or-004-0
Z'd w 6
4.15- -7 35-1v
3-7.3 4 -154 1
I/ALLOFrr/FHZNffNFONORMS/SBF.ARWAL
SWEAR WALL$
S. MA~&FAIt M PIP.
USE we SVATM-pe SIPE OF U&L NAIL ALL MXW WITH ad NAILS
AT 6'or'
MCILTS AT 3MIMMADSWAt MTrM2;&AVM ANCHM
4k,
WALL S' FOR TO Do"At EACH 00 OF M IMLL,60 RWN2"Alt PLAN&
b. MAX"11 G"-SID PLJI.
SW9AIt WALL USE V2*SMATNS-M SM CP"L NAIL ALL MMS WITW Old NAILS
Jh 6 At 4'Or- FOR FIRMINS USE DP NOJ, mol"m 4 TER ANCHM
d% 9MT9 AT 24'or-RARRA spAcm AT TWE MMITIPMI"
FM TIE DO"AT RAW M OF ne d",01 MtftN&OSM PLAN&
6. MAXM 0NEAR-M PLA
USE VP SGATINM-M INIM OP"A- NAIL ALL COS VM Sd NAILS
AT 31 Or- IM Ft��
T 9XFV ca
To OLT;LA
1102111w, FM —
DW DIASM ANCWM BOLTS AT 32'OZ MUMM WACM AT M
Opp
POWATION. MR TO W"AT EAW M 01"'M U" MDU
2 SEE FIRMINSAmem PLANS, 0
raw
1. MAXM*8AIt s MO MI.F.
USE Y2'"ATM-ONE GIDE OF WALL NAIL ALL COO WIT4 10d NAILS
AT 31 or_ NffogM&XIT� MVAME
TE MMWLA p
RMFWI 87MMMALFA M J=
Wbe DWSMIt AHC�M MMTS AT 240 Or-MAXM WACM AT M
POMATION. FM TO WM AT EAW MV OF M U41.1, all
0
S.
WALL IN USE 1/2,SWEAMS-06 GIPE C
AT2VZ'0aGTAGMM. FORFRAM04LUUMN02. D=UWTT0M
G"WALL MAXM 61"9 680 W, F WALL. NAIL ALL MCIEG WITW 10d NAILS
PLATES AFF9 WAUMM,MCLT TWIRCUC44 BMW PLATES UT14 ANCWCR DMTS.
mrmb PROVIDE WV VIAMETIM MCNOR DOLTS AT 20'0C.M&VM SPACM
N At M MWATION, FM TIE W"AT BAC14 DO OF TME WALL,
80 FRAMMOMAR PLANS. 7
GENE"REGAIDIMMERTS
ALL SWEATING;EDONG WALL IME SACI=WITW PRMM SUED ACOMM
0RZrKj 11%XMICTIONG
T=M
AXW&-
"ATMINS AM LCIM WALL"ANING;WALL IN 0"T14AT M"60
EDGE NALM PER GCAMILE 18 CCNTNU0A TINCUM4 KOCKM AND
WALL PLATES. SPACE Od NAILS AT 21=A1.04 NMWWIATE FRAMM
TW TIE 00"ARE FREMMED ON UPPER RjOOR WALLS,
E D C"M44LL IBE MMTM TO TM UPPM AND LOWEIR WALL 8TUD6
Ale C4NNEGM BY TWREADED ROP AS PM I"IMPACTLIMS
FRECOMMMATIONS,
UFFER LEVEL 5�4r=AR WALL FLAN 9
ROOF FRAMING FLAN
SCALls V4' I'-V
0
Jo
WALL'A'
IIJALL
Won a
il Y1, 111 ,.r Xw
Q-
f OF
J1 -1
3�"r r
k/7,
tti -11�11
LOWER LEVEL SIIIIIIIIEAR WALL PLAN MAN
SCALE,1/41-P-Q' 5�4r=AR WALL DETAIL POOLE STUDS
A-4. 1
32
Ll
kk
A�o A5
Project: %qj".
Charles D Smith
Location: FLOOR 1
Multi-Loaded Multi-Span Beam
[20-12 International Building Code(2012 NDS)]
(4) 1.5 IN x 7.25 IN x 10.0 FT
#2-Doug las-Fir-La rch-Dry Use StruCalc Version 9.0.2,5 8/23/2016 6:30:39 AM
Section Adequate By:4.1%
Controlling Factor: Moment
CAUTIONS
*Laminations are to be fully connected to provide uniform transfer of loads to all members
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.15 INL/817
Dead Load 0.10 in
Total Load 0.24 IN L/491
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A B
Live Load 453 lb 1610 lb
Dead Load 326 lb 1032 lb
Total Load 779 lb 2642 lb
Bearing Length 0.21 in 0.70 in
BEAM DATA Center
Span Length 10 ft
Unbraced Length-Top 0 ft
Unbraced Length-Bottom 10 ft 10ft-
Live Load Duration Factor 1.00
Notch Depth 0.00 UNIFORM LOADS Center
MATERIAL PROPERTIES Uniform Live Load 0 plf
#2-Doug las-Fi r-Larch Base Values Ad6usted Uniform Dead Load 0 plf
Beam Self Weight 9 plf
Bending Stress: Fb 900 psi Fb'= 1242 psi Total Uniform Load 9 plf
Cd=1.00 CF=1.20 Cr--1.15
Shear Stress: Fv= 180 psi Fv'= 180 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Live Load 956 lb
Comp.-L to Grain: Fc- 625 psi Fc--L'= 625 psi Dead Load 598 lb
Location 7 ft
-Controlling Moment: 5224 ft-lb TRAPEZOIDAL LOADS-CENTER SPAN
7.0 Ft from left support of span 2(Center Span) Load Number One
Created by combining all dead loads and live loads on span(s)2 Left Live Load 369 plf
Controlling Shear: -2642 lb Left Dead Load 222 plf
At right support of span 2(Center Span) Right Live Load 369 plf
Created by combining all dead loads and live loads on span(s)2 Right Dead Load 222 plf
Load Start 7 ft
Comparisons with required sections: Regl'd Provided Load End 10 ft
Section Modulus: 50.47 in3 52.56 in3 Load Length 3 ft
Area(Shear): 22.02 in2 43.5 in2
Moment of Inertia(deflection): 93.05 in4 190,54 in4
Moment: 5224 ft-lb 5440 ft-lb
Shear: -2642 lb 52201b
NOTES
Pro�ect:
Charles D Smith
Location: FLOOR 2
Multi-Loaded Multi-Span Beam
[2042 International Building Code(2012 NDS)]
5.5 IN x 9.5 IN x 9.0 FT
#2-Doug las-Fir-La rch-Dry Use StruCalc Version 9.0.2.5 8/23/2016 6:47:50 AM
Section Adequate By: 18.2%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.07 IN L/1454
Dead Load 0.07 in
Total Load 0.14 IN L/747
Live Load Deflection Criteria: L/360 Total Load Deflection Criteria: L/240
REACTIONS A Q
Live Load 1151 lb 1025 lb
Dead Load 1092 lb 1010 lb
Total Load 2243 lb 2035 lb
Bearing Length 0.65 in 0.59 in
BEAM DATA Center
Span Length 9 ft
Unbraced Length-Top 1.33 ft
Unbraced Length-Bottom 9 ft
Live Load Duration Factor 1.00
Notch Depth 0.00
MATERIAL PROPERTIES UNIFORM LOADS Center
#2-Doug las-Fir-Larch Uniform Live Load 200 plf
Base Values Adiusted Uniform Dead Load 195 plf
Bending Stress: Fb= 875 psi Fb'= 874 psi Beam Self Weight 11 plf
Cd=1.00 C/=1.00 CF=1.00 Total Uniform Load 406 plf
Shear Stress: Fv= 170 psi Fv'= 170 psi POINT LOADS-CENTER SPAN
Cd=1.00 Load Number One
Modulus of Elasticity: E= 1300 ksi E'= 1300 ksi Live Load 376 lb
Qomp.-L to Grain: Fe- 625 psi Fc-J- = 625 psi Dead Load 246 lb
Location 3 ft
Controlling Moment: 5100 ft-lb
3.96 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
-Controlling Shear: 2243 lb
At left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: Req�d Provided
Section Modulus: 70 in3 82.73 in3
Area(Shear): 19.79 in2 52.25 in2
Moment of Inertia(deflection): 126.33 in4 392.96 in4
Moment: 5100 ft-lb 6027 ft-lb
Shear: 2243 lb 5922 lb
NOTES
Charles D Smith
Project:
Location: FOOTING 1
Footing
[2012 International Building Codel:2012 NDS)]
Footing Size:2.0 FT x 2.0 FT x 12.00 IN
Reinforcement:#4 Bars @ 8.00 IN. O.C. EM (3)min. StruCalc ersion 9.0.2.5 8/23/2016 6:50:15 AM
Section Footing Design Adequate
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure. Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 40000 psi
Concrete Reinforcement Cover: C 3 in
FOOTING SIZE
Width: W= 2 ft
Length: L= 2 ft
Depth: Depth= 12 in
Effective Depth to Top Layer of Steel: d 8.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 6 in
Column Depth: n= 6 in 6 in
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1170 psf
Effective Allowable Soil Bearing Pressure: Qe= 1350 psf
Required Footing Area: Areq= 3.47 sf
Area Provided: A 4.00 sf 12 in
Bqseplate Bearing:
Bearing Required: Bear= 6664 lb
Allowable Bearing: Bear-A 99450 lb
Beam Shear Calculations(One Way Shear):
3 in
Beam Shear: Vul = 1041 lb
Allowable Beam Shear: VC1 = 14850 lb
Punching Shear Calculations(Two Way Shear): ---2 ft
Critical Perimeter: Bo 57 in
Punching Shear: Vu2= 4314 lb
Allowable Punching Shear(ACI 11-35): vc2-a= 105806 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-36): vc2-b= 137363 lb Live Load: PL= 2622 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 70538 lb Dead Load: PD= 2057 lb
Controlling Allowable Punching Shear: vc2 70538 lb Total Load: PT= 4679 lb
Bending Calculations: Ultimate Factored Load: Pu= 6664 lb
Factored Moment: Mu 19991 in-lb Weight to resist uplift w/1.5 F.S.: U.R. 387 lb
Nominal Moment Strength: Mn 169965 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a 0.46 in
Steel Required Based on Moment: As(l)= 0.07 in2
Min.Code Req'd Reinf.Shrink..fTemp. (ACI-10.5.4): As(2)= 0.58 in2
Controlling Reinforcing Steel: As-reqd 0.58 in2
Selected Reinforcement: #4's @ 8.0 in.o.c. e/w(3)Min.
Reinforcement Area Provided: As= 0,59 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup 9 in
Note: Plain concrete adequate for bending,
therefore adequate development length not required.
NOTES
CO
VERFY ROOF
,I'OVER14AM TO
MATC44 EXISTNG
T7CANTILEVER NEW
TRISSES 4'-0'
4 CALE:1/4' P-O'
E SA-E:1/4"- 1'-0'
ul
KAILika
LLI 2X4 VEFZr.
OUTLOOKERS
Z AT 24'OiC.
VERFY ROOF
F MCR14AW-To
�W EXIS�TNG
Project:
4,� Charles D Smith
Location: ROOF I
Roof Beam
[2012 International Building Code(2012 NDS)]
3.5 IN x 7.25 IN x 6.0 FT
#2-Douglas-Fir-Larch-Dry Use StruCalc Version 9.0,2.5 8/9/2016 10:52:12 AM
Section Adequate By:47.0%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.05 IN L/11378
Dead Load 0.03 in
Total Load 0.08 IN L/848
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 956 lb 956 lb
Dead Load 598 lb 598 lb
Total Load 1554 lb 1554 lb
Bearing Length 0.71 in 0.71 in
BEAM DATA
Span Length 6 ft
Unbraced Length-Top 2 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 2 :12
Roof Duration Factor 1.15
MATERIAL PROPERTIES ROOF LOADIII G
#2-Doug las-Fir-Larch Side One:
Base Values Adiusted Roof Live Load: LL 25 psf
Bending Stress: Fb= 900 psi Fb' 1341 psi Roof Dead Load: DL 15 psf
Cd=1.15 C/=1.00 CF=1�30 Tributary Width: TW 4 ft
Shear Stress: Fv= 180 psi Fv' 207 psi Side Two:
Cd=1.15 Roof Live Load: LL 25 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Roof Dead Load: DL 15 psf
Qomp.-L to Grain: Fe- 625 psi Fc- 625 psi Tributary Width: TW 8.8 ft
Controlling Moment: 2332 ft-lb Wall Load: WALL 0 plf
3.0 ft from left support
Created by combining all dead and live loads. SLOPE/PITCH ADJUSTED LENGTH$AND LOADS
-Controlling Shear: -1554 lb Adjusted Beam Length: Ladj= 6 ft
At support. Beam Self Weight: BSW 6 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 319 plf
Beam Uniform Dead Load: wD_adj 199 plf
Comparisons with required sections: Req`d Provided Total Uniform Load: WT 518 plf
Section Modulus: 20.86 in3 30.66 in3
Area(Shear): 11.26 in2 25.38 in2
Moment of Inertia(deflection): 23.6 in4 111.15 in4
Moment: 2332 ft-lb 3428 ft-lb
Shear: -1554 lb 3502 lb
NOTES
Project:
Charles D Smith
Location: ROOF 2
Roof Beam
(2012 International Building Code(2012 NDS)]
(2) 1.5 IN x 5.5 IN x 5.0 FT
#2- Doug las-Fir-Larch-Dry Use StruCalc Version 9.0.2.5 8/9/2016 10:52:41 AM
Section Adequate By: 335.6%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.02 IN L/3787
Dead Load 0.01 in
Total Load O�03 IN L/2287
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 188 lb 188 lb
Dead Load 123 lb 123 lb
Total Load 311 lb 311 lb
Bearing Length 0.17 in 0.17 in
BEAM DATA
Span Length 5 ft
Unbraced Length-Top 2 ft
Unbraced Length-Bottom 0 ft 5 ft 77-1
Roof Pitch 2 :12
Roof Duration Factor 1.15
MATERIAL PROPERTIES ROOF LOADING
#2-Doug las-Fir-La rch Side One:
Base Values Ad6usted Roof Live Load: ILL 25 psf
Bending Stress: Fb= 900 psi Fb' 1341 psi Roof Dead Load: DIL 15 psf
Cd=1.15 C/=1.00 CF=1.30 Tributary Width: TW 1 ft
Shear Stress: Fv= 180 psi Fv'= 207 psi Side Two:
Cd=1.15 Roof Live Load: LL 25 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Roof Dead Load: DL 15 psf
Comp.-L to Grain: Fc- 625 psi Fc--L'= 625 psi Tributary Width: TW 2 ft
Controlling Moment: 388 ft-lb Wall Load: WALL= 0 plf
2.5 ft from left support
Created by combining all dead and live loads. SLOPEIPITCH ADJUSTED LENGTHS AND LOADS
'Controlling Shear: 310 lb Adjusted Beam Length: Ladj= 5 ft
At support. Beam Self Weight: BSW 4 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 75 plf
Beam Uniform Dead Load: wD_adj 49 plf
Comparisons with required sections: ReQ'd Provided Total Uniform Load: WT 124 plf
Section Modulus: 3.47 in3 15.13 in3
Area(Shear): 2.25 02 16.5 in2
Moment of Inertia(deflection): 3.27 in4 41.59 in4
Moment: 388 ft-lb 1691 ft-lb
Shear: 310 lb 2277 lb
NOTES
Protect:
_..--._-,"0Cha,Ies D Smith
Location: ROOF 3
Ro6f Beam
[2012 International Building Code(2012 NDS)]
3.5 IN x 5.5 IN x 6.0 FT
#2- Doug las-Fi r-Larch-Dry Use StruCalc Version 9.0.2.5 8/9/2016 10:53:18 AM
Section Adequate By:0.5%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.10 IN L/713
Dead Load 0.06 in
Total Load 0.16 INL/439
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 806 lb 806 lb
Dead Load 503 lb 503 lb
Total Load 1309 lb 1309 lb
Bearing Length 0.60 in 0.60 in
BEAM DATA
Span Length 6 ft ..........
Unbraced Length-Top 2 ft -6ft
Unbraced Length-Bottom 0 ft
Roof Pitch 2 :12
Roof Duration Factor 1,11 ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Douglas-Fir-Larch Base Values Admusted Roof Live Load: LL= 25 psf
Bending Stress: Fb= 900 psi Fb' 1342 psi Roof Dead Load: DL= 15 psf
Cd=1.15 C1=1.00 CF=1.30 Tributary Width: TW 2 ft
SAear Stress: Fv= 180 psi Fv' 207 psi Side Two:
Cd=1.15 Roof Live Load: ILL 25 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Roof Dead Load: DL 15 psf
Gomp.-L to Grain: Fc- 625 psi Fc- 625 psi Tributary Width: TW 8.8 ft
Controlling Moment: 1964 ft-lb Wall Load: WALL 0 plf
3.0 ft from left support
Created by combining all dead and live loads. SLOPE/PITCHADJUSTED LENGTHS AND LOADS
'Controlling Shear: -1309 lb Adjusted Beam Length: Ladj= 6 ft
At support. Beam Self Weight: BSW 4 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 269 plf
Beam Uniform Dead Load: wD_adj 168 plf
Comparisons with required sections: ReaJ Provided Total Uniform Load: WT 436 plf
Section Modulus: 17.55 in3 17.65 in3
Area(Shear): 9.49 in2 19.25 02
Moment of Inertia(deflection): 19.88 in4 48.53 04
Moment: 1964 ft-lb 1974 ft-lb
Shear: -1309 lb 2657 lb
NOTES
Project:
1,Ch,rles D Smith
Location: ROOF 4
Roof Beam
[202 International Building Code(2012 NDS)]
(2 ) 1.5 IN x 3.5 IN x 5.0 FT
#2-Doug las-Fir-La rch-Dry Use StruCalc Version 9.0.2.5 8/9/2016 10:53:52 AM
Section Adequate By: 105.9%
Controlling Factor: Moment
DEFLECTIONS Center LOADING DIAGRAM
Live Load 0.06 IN L/976
Dead Load 0.04 in
Total Load 0.10 INL/595
Live Load Deflection Criteria: L/240 Total Load Deflection Criteria: L/180
REACTIONS A B
Live Load 188 lb 188 ib
Dead Load 120 lb 120 lb
Total Load 308 lb 308 lb
Bearing Length 0.16 in 0.16 in
BEAM DATA
Span Length 5 ft
Unbraced Length-Top 2 ft -5 ft
Unbraced Length-Bottom 0 ft
Roof Pitch 2 :12
Roof Duration Factor 1.15 ROOF LOADING
MATERIAL PROPERTIES Side One:
#2-Doug las-Fi r-La rch Base Values Admusted Roof Live Load: LL 25 psf
Bending Stress: Fb= 900 psi Fb' 1549 psi Roof Dead Load: DL 15 psf
Cd=1.15 C1=1.00 CF=la 50 Tributary Width: TW 1 ft
Slie-ar Stress: Fv= 180 psi Fv'= 207 psi Side Two:
Cd=1.15 Roof Live Load: LL 25 psf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Roof Dead Load: DL 15 psf
C,omp.-L to Grain: Fc- 625 psi Fc- 625 psi Tributary Width: TW 2 ft
Controlling Moment: 384 ft-lb Wall Load: WALL 0
2.5 ft from left support plf
Created by combining all dead and live loads. SLOPE/PITCH ADJUSTED LENGTHS AND LOADS
Controlling Shear: 307 lb Adjusted Beam Length: Ladj 5 ft
At support. Beam Self Weight: BSW 2 plf
Created by combining all dead and live loads. Beam Uniform Live Load: wL= 75 plf
Beam Uniform Dead Load: wD_adj 48 plf
Comparisons with required sections: Re(:Cd Provided Total Uniform Load: wT 123 plf
Section Modulus: 2.98 in3 6.13 in3
Area(Shear): 2.23 in2 10.5 in2
Moment of Inertia(deflection): 3.24 in4 10.72 in4
Moment: 384 ft-lb 791 ft-lb
Shear: 307 lb 1449 lb
NOTES