PREPARED 9/12/13, 12:15:35 INSPECTION TICKET PAGE I
CITY OF PORT ANGELES INSPECTOR: JAMES LIERLY DATE 9/12/13
------------------------------------------------------------------------------------------------
ADDRESS . : 520 S PEABODY ST SUBDIV:
CONTRACTOR STEVE JOHNSON CONSTRUCTION PHONE (360) 457-8196
OWNER HOHAM RUTH S PHONE
PARCEL 06-30-00-0-1-9980-0000-
APPI, NUMBER: 13-00000414 RES FOUNDATION ONLY
------------------------------------------------------------------------------------------------
PERMIT: BPR 00 BUILDING PERMIT - RESIDENTIAL
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
------------------------------------------------------------------------------------------------
BL6 01 8/02/13 JLL BLDG POST/COLUMN FTG
8/02/13 AP August 2, 2013 8:20:41 AM pbarthol.
Steve 670-1317
AM
August 2, 2013 4:10:34 PM jlierly.
BLFO 01 8/28/13 PB BLDG FOUNDATION
8/29/13 AP August 28, 2013 9:31:42 AM pbarthol.
Steve 670-1317
August 29, 2013 1:46:45 PM pbarthol.
UFR ground in place
BL99 01 9/12/13 BLDG FINAL
September 12, 2013 9:55:59 AM pbarthol.
Steve 670-1317
he would like you to call so he can be there.
------------------------------------------------------------------------------------------------
PERMIT. PL 00 PLUMBING PERMIT
REQUESTED INSP DESCRIPTION
TYP/SQ COMPLETED RESULT RESULTS/COMMENTS
--------------------- ------------------------------------------------------------------
PL99 01 9/12/13 PLUMBING FINAL
September 12, 2013 9:56:45 AM pbarthol.
Steve 670-1317
he would like you to call so he can be there.
-------------------------------------- COMMENTS AND NOTES --------------------------------------
CITY OF PORT ANGELES
DEPARTMENT OF COMMUNITY& ECONOMIC DEVELOPMENT- BUILDING DIVISION
321 EAST 5TH STREET, PORT ANGELES,VA 98362
Application Number . . . . . 13-00000414 Date 5/03/13
Application pin number . . . 607774
Property Address . . . . . . 520 S PEABODY ST
ASSESSOR PARCEL NUMBER: 06-30-00-0-1-9980-0000-
Application type description RES FOUNDATION ONLY REPORT SALES TAX
Subdivision Name . . . . . . on your state excise tax form
Property Use . . . . . . . .
Property Zoning . . . . . . . COMMERCIAL OFFICE to the City of Port Angeles
Application valuation . . . . 11000 (Location Code 0502)
----------------------------------------------------------------------------
Application desc
INSTALL STEEL FOUNDATION SYSTEM/NEW WATER SERVICE
----------------------------------------------------------------------------
Owner Contractor
------------------------ ------------------------
HOHAM RUTH S STEVE JOHNSON CONSTRUCTION
520 S PEABODY ST 1512 W. 5TH ST
PORT ANGELES WA 983626230 PORT ANGELES WA 98362
(360) 457-8196
-----------------------------------------------------------------------------
Permit . . . . . . BUILDING PERMIT -RESIDENTIAL
Additional desc STEEL FOUNDATION SYSTEM
Permit Fee . . . . 221.75 Plan Check Fee 144.14
Issue Date . . . . 5/03/13 Valuation . . . . 11000
Expiration Date 10/30/13
Qty Unit Charge Per Extension
BASE FEE 95.75
9.00 14.0000 THOU BL-2001-25K (14 PER K) 126.00
----------------------------------------------------------------------------
Permit . . . . . . PLUMBING PERMIT
Additional desc . . NEW WATER SERVICE
Permit Fee . . . . 57.00 Plan Check Fee .00
Issue Date . . . . 5/03/13 Valuation . . . . 0
Expiration Date . . 10/30/13
Qty Unit Charge Per Extension
BASE FEE 50.00
1.00 7.0000 EA PL-WATER LINE 7.00
----------------------------------------------------------------------------
Other Fees . . . . . I . . . STATE SURCHARGE 4.50
----------------------------------------------------------------------------
Fee summary Charged Paid Credited Due
----------------- ---------- ---------- ---------- ----------
Permit Fee Total 278.75 278.75 .00 .00
Plan Check Total 144.14 144.14 .00 .00
Other Fee Total 4.50 4.50 .00 .00
Grand Total 427.39 427.39 .00 .00
V�
Separate Permits are required for electrical work,SEPA,Shoreline,ESA,utilities,private and public improvements. This permit becomes
null and void if work or construction authorized is not commenced within 180 days,if construction or work is suspended or abandoned
for a period of 180 days after the work has commenced, or if required inspections have not been requested within 180 days from the
last inspection. I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions
of laws and ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does
not presume to give authority to violate or cancel the provisions of any state or local law regulating construction or the performance of
construction.
tee Print Name Signature of Contractor or Authorized Agent Signature of Owner(if owner is builder)
T:Forms/Building Division/Building Permit
BUILDING PERMIT INSPECTION RECORD
PLEASE PROVIDE A MINIMUM 24-HOUR NOTICE FOR INSPECTIONS—
Building Inspections. 417-4815 Electrical Inspections 417-4735
Public Works Utilities 417-4831 Backflow Prevention Inspections 417-4886
IT IS UNLAWFUL TO COVER, INSULATE OR CONCEAL ANY WORK BEFORE INSPECTED AND ACCEPTED.
POST PERMIT INCONSPICUOUS LOCATION. KEEP PERMIT AND APPROVED PLANS AT JOB SITE.
Inspection Type Date Accepted By Comments
FOUNDATION:
Footings
Sternwall
Foundation Drainage/Downspouts
Piers
Post Holes(Pole Bldgs.)
PLUMBING:
Under Floor/Slab
Rough-in
Water Line(Meter to Bldg)
Gas Line
Back Flow/Water FINAL Date Accepted by
AIR SEAL:
Walls
Ceiling
FRAMING:
Joists I Girders/Under Floor
Shear Wall/Hold Downs
Walls/Roof/Ceiling
Drywall(interior Braced Panel Only)
T-Bar
INSULATION:
Slab
Wall/Floor/Ceiling
MECHANICAL:
Heat Pump/Furnace/FAU/Ducts
Rough-In
Gas Line
Wood Stove/Pellet/Chimney
Commercial Hood/Ducts FINAL Date Accepted by
MANUFACTURED HOMES:
Footing/Slab
Blocking&Hold Downs
Skirting
PLANNING DEPT. Separate Permit#s SEPA:
Parking/Lighting ESA:
Landscaping ISHORELINE:
FINAL INSPECTIONS REQUIRED PRIOR TO OCCUPANCY1 USE
Inspection Type Date Accepted By
Electrical 417-4735
Construction-R.W. PW Engineering 417-4831
Fire 417-4653
Planning 417-4750
Building 417-4815
T:Forms/Building Division/Building Permit
TmE For City Use
CITY OF ORT ANGELES
P Permit# /3-
V� A S H I N G T 0 N , U . S. Date Received:
321 E 51h Street Date Approved
Port Angeles,WA 9836 1A
P:360-417-4817 F:360-417-4711 r\
Email:permits0cityofpa.us BUILDING PERMIT APPLICATION
Project Address: 5-Z 0 P
d Phone: 6 70
Primary Contact: Email:
i
Name Phomr
Property Mailing Address Email
Owner '5-
City State Zip
Name Phone
Contractor Address Email
Information City ;P
State Zip
LCcontractors License4r i—fdr g-C-fe 7 7 7c-- Exp.Date:
Legal Description: Zoning: Tax Parcel# Project Value: (materials and labor)
$ //ro E5016 fx—�
Residential 1:1 Commercial El Industrial El Public 11
Permit Demolition 1:1 Fire El Repair 1:1 Reroof(tear off/lay over)
Classification For the following,fill out both pages of permit api2lication:
(check New Construction 1:1 Exterior Remodel 1:1 Addition 0 Tenant Improv(mynt
appropriate) I Mechanical 11 Plumbing El Other 11
Fire Sprinkler System? Irrigation System? Proposed Bathrooms Proposed Bedrooms
Yes 13 No 0 � Yes 13 No 13 1
Project Description rep /a ZE-.;a Lt- /XAd-k-f--
Project Valuation $ ��6)ooe-A=>
f
Is project ina Flood Zone: Yes 13 NoC3--Flood Zone Type: —
If in a Flood Zone, what is the value of the structure before proposed improvement? $
I have read and completed the application and know it to be true and correct. I am authorized to apply for
this permit and understand that it is my responsibility to determine what permits are required and to
obtain permits prior to work. I understand that plan review fees are not refundable after review has
occurred. I understand that I will forfeit review fees if I withdraw the application before the permit is
issued. I understand that if the permit is not picked up/issued within 18o days of submittal,the application
will be considered abandoned and the fees will be forfeited.
Date Print Name 5;1s-aC— 9b'HA1So0V Signature
Residential Structures
For Office Use
Area Description(SQ FT) Existing Proposed ss value
Basement
First Floor
Second Floor
Covered Deck/Porch/Entry
Deck(over 30"or 2 nd floor)
Garage
Carport
Other(describe)
Area Totals
Commercial Structures
For Office Use
Area Descriptions(SQ FT) Existing Proposed ss Value
Existing Structure (s)
Proposed Addition
Tenant Improvement?
Other work(describe)
Site Area Totals
Lot/Site Coverage Calculations
Lot Size(sq ft) Lot Coverage(sq ft) %Lot Coverage (Total lot coverage lot size)
Site Coverage (�q Ft of all impervious) %of Site Coverage (total site coverage-- lot size)
Mechanical Fixtures
Indicate how many of each-type of fixture to be installed or relocated as part of this project.
Air Handler Size: # Haz/Non-Haz Piping Outlets:
Appliance Exhaust Fan # Heater(Suspended,Floor,Recessed wall) #
Boiler/Compressor Size: # Heating/Cooling appliance #
repair/alte ation
Evaporative Cooler(attached,not # Pellet Stove/Wood-burning/Gas #
portable) as Stove/Gas Cook Stove/Misc.
Fuel Gas Piping #of Outlets: Ventilation Fan,single duct #
# Ventilation System #
Forced Air Unit
Furnace/Heat Pump
Plumbing Fixtures
Indicate how many of each type of fixtu e to be installed or relocated
Plumbing Traps # Fuel gas piping #of Outlets:
Water Heater # Medical gas piping #of Outlets:
Water Line # Plumbing Vent piping #
Sewer Line # Industrial waste pretreatment
interceptor(Grease Trap) Size
Other(describe):
T:\BUILDING\APPLICATION FORMS\Current BP Application\Building Permit 4-17-13.docx
325
516
�43
520
6e'l
519
.01
11-611 X 11-611 X 1011 12" WIDE X 12" DEEP
CONCRETE FOOTING WITH CONCRETE FOOTING WITH
(2) NOA 5ARS EACH WAY (2) NO.4 5ARS CONTINUOUS r 4
VARIFY LOCATION WITH ONE TOP AND ONE 50TTOM Q)
EXSITIW.z POSTS I I
TYPICAL FOR (2) -5.
-------------------------------------------------------------------------- ------------------
--—1
r------------------------------------------------------------------------------------------------
0
10" DIA. CONCRETE PLINTH
WITH (3) NOA 5ARS VERT. 4j
c*4 0
AND V, O.C. HORIZ. 4 4 -(
PROIVDE SIMPSON EP5 44 4 4 4 (P
POST 5ASE ol
TYPICAL FOR (2) 0 0
EXISTING
4X6 DF
cz cd
NO2
Q)
O� -
0
11-131*1 X 11-131, X 101, DEEP -p
CONCRETE PAL) WITH
(3) NOA 5ARS EACH WAY
0
TYPICAL FOR (22) LOCATIONS Y)
2 Q)
L j k A
EXISTING CQ
r4 4X8 DF Lo
�4-6,
NO2
E� - — - --l'-13--4 A -E3-4 -
L- --J
L�j
2X4 c_:"
E -�j LD
OF BEAM AND POST
TYPICAL FOR (22) LOCATIONS
(p
L C4
L----------------------------------------------------------------------------------------------------
4 11
Z
.5
CQ
co
m .1 co
co 5
"-4 1
0 CQ CQ
4
FOUNDATION f=LAN m
10 .,q a) co co
SCALE: 114" cm V-011 0 co co
co
0
cd
0 44
EXISTING EXISTING EXISTING 0 4
F FLOOR STURCTURE FLOOR STURCTURE FLOOR STURCTURE co 134
F7� EXISTING
PORCH
STRUCTURE
EXISTING
4X(o FLOOR
GRIDER 114" DIA. X 2"
LAG SCREWS P.T. 4X4 100ST ......
AT 12" O.C. EXISTING WIT14 SIMPSON
4X& FLOOR P.T. 4X(o POST 5C4 POST CAR SIMPSON EP`544
1/4 11 D I A. X 2 'ANCHORPANEL' GRIDER Al WITH SIMPSON A24 VERIFY POST 5A5E nrl
LAG SCREWS CHANNEL AND ATIBASE QN00,
AT 12" O.C. FOUNDATION
PANELS 10" DiA. CONCRETE
2X4 IBLOCK
PLINTH WITH (3) NOA
EACH -SIDE OF
'ANCHORPANEL' 5EAM AND POST X 1, 5ARS VERT. AND
-c3a X 101, C—A/
CHANNEL AND cj" O.C. HORIZ.
ONRETE FOOTING
FOUNDATION 1/2" DIA. AM. WITH (3) NOA 5ARS fAr.,
cl,
PANELS W1 3" EM5EDMENT EACH WAY
lit
IL
L--------------- -------i I Cr L
clfy OF PORT A% ose
permlt j1pon
--------------------------- the buildm.
V,�jp an,,''All pair,
121, WIDE X 121, DEEP 12" WIDE X 12" DEEP 1-611 X 11 ai dats,�+,,-!'rio; -
0 1 —611 X 1011 ij,-m elrov'S in qIl
CONRETE FOOTING CONRETE FOOTING tnn
CONRETE FOOTING ;,,i in
WITH (2) NOA BARS WITH (2) NOA 5AR-5 "'o 14 -
lt,UiCL
WITH (2) NO.4 5ARS eu� I
3! �I ( "es IV - /w
EACH WAY
CHUC:K
SJOHN50N
FOUNE::) ATION WALL FOUNDATION WALL INTEF--, 10F� f=AID FOOTING; AT f=OFRC�4
F &,1 014
2 .4
SCALE: 11/2 V-011 SCALE: 11/2 V-011 SCALE: 11/2 V—011
SCALE: 11/211 V-011
FA S�.19
Aim;;
T"
LINDBE4,-AW4'
A R C H I kJ' C T' IS
319 s.peabody,suite bi port angeles,wa 98362
360.452.6116 fax 360.452.7064
Ptoject. PE411A P.-P 1%W-)
Project No.
Sublect; W40S By: eg--
,D*�te: L �]a Sheet of
LOADS Pr-dF- 7-,Wwvkn BYIJ
1:5 G12. P!-J- -
)6�TD
4z?
NAIL 11 e-I
PAP
r-------------------- -------------------------- ---------w C
-----------
------------- --------------------------------------- T-
-— —- -—-—- -—-
X),
+
*&A WAI
/DO-- /Va.-2-
L--------------------------------------------------------------------I --2PAV
- -----------------------------------------------------------------------------------------------
Sac[
t/VAL"
Z-961WI) ,
64 I-W;;,
1 M-6-333
L4*1-1�J.
Project:
Location: Uniformly Loaded Floor Beam 1
Uniformly Loaded Floor Beam
[200�International Building Code(2005 NDS)]
3.5 IN x 7.25 IN x 6.75 FT
#1 -Hem-Fir(North)-Dry Use
Section Adequate By: 19.7% StruCalc Version 8.0.100.0 4/18/2013 11:22:09 AM
Controlling Factor:Moment LOADING DIAGRAM
DEFLECTIONS Cente
Live Load 0.09 IN U881
Dead Load 0.04 in
Total Load 0.13 INU634
Live Load Deflection Criteria: U360 Total Load Deflection Criteria: U240
REACTIONS A B
Live Load 1181 lb 1181 lb
Dead Load 460 lb 460 lb
Total Load 1641 lb 1641 lb
Bearing Length 1.16 in 1.16 in
BEAM DATA Center �1.711
Span Length 6.75 ft A
Unbraced Length-Top 1.33 ft
Floor Duration Factor 1.00
Notch Depth 0.00 FLOOR LOADING
MATERIAL PROPERTIES Side 1 Side 2
#1 -Hem-Fir(North) Floor Live Load FLL 40 psf 40 psf
Base Values Ad6usted Floor Dead Load FDL 15 psf 15 psf
Bending Stress: Fb= 1000 psi Fb' 1298 psi Floor Tributary Width FTW 4.4 ft 4.3 ft
Cd=1.00 C1=1.00 CF=1.30 Wall Load WALL 0 plf
Shear Stress: Fv= 145 psi Fv' 145 psi BEAM LOADING
Cd=1.00 Beam Total Live Load: wL= 350 plf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Beam Total Dead Load: wD= 131 plf
Min.Mod.of Elasticity: E—min= 580 ksi E—min'= 580 ksi Beam Self Weight: BSW 5 plf
Comp.-L to Grain: Fc--L= 405 psi Fc--L = 405 psi Total Maximum Load: wT 486 plf
Controlling Moment: 2770 ft-lb
3.375 ft from left support
Created by combining all dead and live loads.
Controlling Shear: 1379 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections: RecCd Provided
Section Modulus: 25.61 in3 30.66 in3
Area(Shear): 14.26 in2 25.38 in2
Moment of Inertia(deflection): 45.4 in4 111.15 in4
Moment: 2770 ft-lb 3315 ft-lb
Shear: 1379 lb 2453 lb
NOTES
Project:
Location: Footing 1
Footing
[20M International Building Code(2005 NDS)]
Footing Size:0.833 FT x 0.833 FT x 10.00 IN
Reinforcement:#4 Bars @ 3.50 IN.O.C.EAA1 (2)min.
Section Footing Design Adequate StruCalc Version 8.0.100.0 4118/2013 11:25:40 AM
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi 5.5 in
Reinforcing Steel Yield Strength: Fy= 40000 psi
Concrete Reinforcement Cover: C 3 in
FOOTING SIZE
Width: W= 0.83 ft
Length: L 0.83 ft
Depth: Depth= 10 in
Effective Depth to Top Layer of Steel: d 6.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m 5.5 in
Column Depth: n 5.5 in
FOOTING CALCULATIONS
10 in
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1183 psf
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf
Required Footing Area: Areq= 0.6 sf
Area Provided: A 0.69 sf
Baseplate Bearing:
Bearing Required: Bear= 1222 lb
Allowable Bearing: Bear-A 83566 lb 3 in
Beam Shear Calculations(One Way Shear):
Beam Shear: Vul = 0 lb
Allowable Beam Shear: Vc1 = 4686 lb --
Punching Shear Calculations(Two Way Shear): 0.833 ft
Critical Perimeter: Bo 0 in
Punching Shear: Vu2= 0 lb
Allowable Punching Shear(ACI 11-35): vc2-a= 0 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-36): vc2-b= 0 lb Live Load: PL= 591 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 0 lb Dead Load: PD= 230 lb
Controlling Allowable Punching Shear: vc2 0 lb Total Load: PT= 821 lb
Bending Calculations: Ultimate Factored Load: Pu= 1222 lb
Factored Moment: MU 1526 in-lb
Nominal Moment Strength: Mn 83091 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a 0.74 in
Steel Required Based on Moment: As(l)= 0.01 in2
Min.Code Req'd Reinf.(Shrink./Temp.(ACI-10.5.4):As(2)= 0.20 in2
Controlling Reinforcing Steel: As-reqd�— 0.20 in2
Selected Reinforcement: #4's @ 3.5 in.o.c.e/w(2)Min.
Reinforcement Area Provided: As= 0.39 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup 2 in
Note: Plain concrete adequate for bending,therefore adequate development length not required.
NOTES
Project:
Location:Uniformly Loaded Floor Beam 1
Uniformly Loaded Floor Beam
[2006 International Building Code(2005 NDS)]
3.5 IN x 7.25 IN x 3.25 FT
#1 -Hem-Fir(North)-Dry Use
Section Adequate By:385.0% StruCalc Version 8.0.100.0 4/18/2013 11:27:21 AM
Controlling Factor:Shear LOADING DIAGRAM
DEFLECTIONS Cente
Live Load 0.00 IN U7895
Dead Load 0.00 in
Total Load 0.01 IN U5682
Live Load Deflection Criteria:U360 Total Load Deflection Criteria: U240
REACTIONS A B
Live Load 569 lb 569 lb
Dead Load 222 lb 222 lb
Total Load 790 lb 790 lb
Bearing Length 0.56 in 0.56 in
Center
BEAM DATA
Span Length 3.25 ft A 3.25 ft
Unbraced Length-Top 1.33 ft
Floor Duration Factor 1.00
Notch Depth 0.00 FLOOR LOADING
MATERIAL PROPERTIES Side 1 Side 2
#1 -Hem-Fir(North) Floor Live Load FLL 40 psf 40 psf
Base Values Adausted Floor Dead Load FDL 15 psf 15 psf
Bending Stress: Fb= 1000 psi Fb'= 1298 psi Floor Tributary Width FTW 4.4 ft 4.3 ft
Cd=1.00 C10.00 CF=1.30 Wall Load WALL 0 plf
Shear Stress: Fv= 145 psi Fv'= 145 psi BEAM LOADING
Cd=1.00 Beam Total Live Load: wL= 350 plf
Modulus of Elasticity: E= 1600 ksi E'= 1600 ksi Beam Total Dead Load: wD= 131 plf
Min.Mod.of Elasticity: E—min= 580 ksi E—min'= 580 ksi Beam Self Weight: BSW 5 pif
Comp.-L to Grain: Fc--L= 405 psi Fc--L = 405 psi Total Maximum Load: wT 486 plf
Controlling Moment: 642 ft-lb
1.625 ft from left support
Created by combining all dead and live loads.
Controlling Shear: -506 lb
At a distance d from support.
Created by combining all dead and live loads.
Comparisons with required sections: —Rg-q:d Provided
Section Modulus: 5.94 in3 30.66 in3
Area(Shear): 5.23 in2 25.38 in2
Moment of Inertia(deflection): 5.07 in4 111.15 in4
Moment: 642 ft-lb 3315 ft-lb
Shear: -506 lb 2453 lb
NOTES
Project:
Location:Footing 2
Footing
[2069 International Building Code(2005 NDS)]
Footing Size: 1.75 FT x 1.75 FT x 10.00 IN
Reinforcement:#4 Bars @ 7.00 IN.O.C.EAN/(3)min.
Section Footing Design Adequate StruCalc Version 8.0.100.0 4118/2013 11:28:45 AM
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: Qs= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy= 40000 psi
Concrete Reinforcement Cover: C 3 in
FOOTING SIZE
Width: W= 1.75 ft
Length: L= 1.75 ft
Depth: Depth= 10 in
Effective Depth to Top Layer of Steel: d 6.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: rn 5.5 in
Column Depth: n 5.5 in 5.5 in
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: Qu= 1072 psf
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf
Required Footing Area: Areq= 2.39 sf
Area Provided: A 3.06 sf 10 in
Baseplate Bearing:
Bearing Required: Bear= 4883 lb
Allowable Bearing: Bear-A 83566 lb T
Beam Shear Calculations(One Way Shear): 3 in
Beam Shear: Vul = 988 lb
Allowable Beam Shear: Vc1 = 9844 lb
Punching Shear Calculations(Two Way Shear): 1.75 ft
Critical Perimeter: Bo 47 in
Punching Shear: Vu2= 3354 lb
Allowable Punching Shear(ACI 11-35): vc2-a= 66094 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-36): vc2-b= 80625 lb Live Load: PL 2362 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 44063 lb Dead Load: PD 920 lb
Controlling Allowable Punching Shear: vc2 44063 lb Total Load: PT 3282 lb
Bending Calculations: Ultimate Factored Load: Pu 4883 lb
Factored Moment: Mu 12818 in-lb
Nominal Moment Strength: Mn 126876 in-lb
Reinforcement Calculations:
Concrete Compressive Block Depth: a 0.53 in
Steel Required Based on Moment: As(l)= 0.06 in2
Min.Code Req'd Reinf.(Shrink./Temp.(ACI-10.5.4):As(2)= 0.42 in2
Controlling Reinforcing Steel: As-reqd 0.42 in2
Selected Reinforcement: #4's @ 7.0 in.o.c.e/w(3)Min.
Reinforcement Area Provided: As= 0.59 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup 7.5 in
Note: Plain concrete adequate for bending,therefore adequate development length not required.
NOTES
Project:
Location:Multi-Loaded Multi-Span Beam 2
MultL-Loaded Multi-Span Beam
[2009 International Building Code(2005 NDS)]
5.5 IN x 11.5 IN x 5.0 FT
#2-Hem-Fir(North)-Dry Use StruCalc Version 8.0.100.0 4/1912013 7:22:26 AM
Section Adequate By: 18.1% LOADING DIAGRAM
Controlling Factor:Moment
DEFLECTIONS Cente
Live Load 0.02 IN U3131
Dead Load 0.01 in
Total Load 0.03 IN U1773
Live Load Deflection Criteria: U360 Total Load Deflection Criteria:U240
REACTIONS B
Live Load 2613 lb 2613 lb
Dead Load 2002 lb 2002 lb
Total Load 4614 lb 4614 lb
Bearing Length 2.07 in 2.07 in
BEAM DATA Cente 5ft R
Span Length 5 ft A
Unbraced Length-Top 1.33 ft
Unbraced Length-Bottom 5 ft
Live Load Duration Factor 1.00 UNIFORM LOADS Cente
Notch Depth 0.00 Uniform Live Load 1045 plf
MATERIAL PROPERTIES Uniform Dead Load 788 pif
#2-Hem-Fir(North) Beam Self Weight 13 plf
Base Values Ad'usted Total Uniform Load 1846 plf
Bending Stress: Fb= 675 psi Fb' 674 psi
Cd=1.00 C1=1.00 CF=1.00
Shear Stress: Fv= 135 psi Fv' 135 psi
Cd=1.00
Modulus of Elasticity: E= 1100 ksi E'= 1100 ksi
Min.Mod.of Elasticity: E—min= 400 ksi E—min'= 400 ksi
Comp.-L to Grain: Fc--L= 405 psi Fc-J- = 405 psi
Controlling Moment: 5768 ft-lb
2.5 Ft from left support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Controlling Shear: -2861 lb
At a distance d from right support of span 2(Center Span)
Created by combining all dead loads and live loads on span(s)2
Comparisons with required sections: _Rg_q�d Provided
Section Modulus: 102.63 in3 121.23 in3
Area(Shear): 31.79 in2 63.25 in2
Moment of Inertia(deflection): 94.36 in4 697.07 in4
Moment: 5768 ft-lb 6813 ft-lb
Shear: -2861 lb 5693 lb
NOTES
i/ol
Project:
Location:Footing 4
Fooling
(2009 International Building Code(2005 NDS)]
Footing Size: 1.6 FT x 1.6 FT x 10.00 IN
Reinforcement:#4 Bars @ 12.00 IN.O.C.EM/(2)min.
Section Footing Design Adequate StruCalc Version 8.0.100.0 4/19/2013 11:00:54 AM
FOOTING PROPERTIES LOADING DIAGRAM
Allowable Soil Bearing Pressure: QS= 1500 psf
Concrete Compressive Strength: F'c= 2500 psi
Reinforcing Steel Yield Strength: Fy 40000 psi
Concrete Reinforcement Cover: C 3 in
FOOTING SIZE
Width: W 1.6 ft
Length: L= 1.6 ft
Depth: Depth 10 in
Effective Depth to Top Layer of Steel: d 6.25 in
COLUMN AND BASEPLATE SIZE
Column Type: Wood
Column Width: m= 4 in 4 in
Column Depth: n= 4 in
FOOTING CALCULATIONS
Bearing Calculations:
Ultimate Bearing Pressure: QU= 664 psf
Effective Allowable Soil Bearing Pressure: Qe= 1375 psf
Required Footing Area: Areq= 1.24 sf
Area Provided: A 2.56 sf 10 in
Baseplate Bearing:
Bearing Required: Bear= 2466 lb
Allowable Bearing: Bear-A 44200 lb T
Beam Shear Calculations(One Way Shear): 3in
Beam Shear: Vul = 430 lb
Allowable Beam Shear: Vc1 = 9000 lb
Punching Shear Calculations(Two Way Shear): 1.6 ft
Critical Perimeter: Bo 41 in
Punching Shear: Vu2= 1763 lb
Allowable Punching Shear(ACI 11-35): vc2-a= 57656 lb FOOTING LOADING
Allowable Punching Shear(ACI 11-36): vc2-b= 77813 lb Live Load: PL 1063 lb
Allowable Punching Shear(ACI 11-37): vc2-c= 38438 lb Dead Load: PD 638 lb
Controlling Allowable Punching Shear: vc2 38438 lb Total Load: PT 1701 lb
Bending Calculations: Ultimate Factored Load: Pu 2466 lb
Factored Moment: Mu= 5919 in-lb
Nominal Moment Strength: Mn 85594 in-lb
Reinforcement Calculations:
Concrete Com p ressive,Block Depth: a 038 in
Steel Required Based on Moment: As(l)= 0.03 in2
Min.Code Req'd Reinf.(Shrink./Temp.(ACI-10.5.4):As(2)= 0.38 in2
Controlling Reinforcing Steel: As-reqd= 0.38 in2
Selected Reinforcement: #4's @ 12.0 in.o.c.e/w(2)Min.
Reinforcement Area Provided: As= 0.39 in2
Development Length Calculations:
Development Length Required: Ld= 15 in
Development Length Supplied: Ld-sup 6.6 in
Note: Plain concrete adequate for bending,therefore adequate development length not required.
NOTES
ANCHORPANEL PERIMETER FOUNDATION SYSTEM - ALLOWABLE LOADS
DRAFT LOAD TABLE- FOR ICC-ER(ICBO-ER) FILE#01-05-15 APPLICATION IN PROGRESS
TABLE 1 -ALLOWABLE AXIAL LOADS
DESIGN LOADS -AXIAL ONLY 12 3
MAXIMUM MAXIMUM
PANEL HEIGHT 6 AXIAL LOAD
(inches) (pif)
48 6566
72 5000
100 3433
TABLE 2-ALLOWABLE COMBINED LOADS
DESIGN LOADS FOR FOUNDATION-WALLS,AXIAL LOADS COMBINED WITH SHEAR/RACKING
MAXIMUM MAXIMUM SHEAR/RACKING LOAD FROM WIND OR SEISMIC FORCES (pIfl rigio
PANEL AXIAL WOOD SPECIES OF G =0.35 WOOD SPECIES OF G =0.42 WOOD SPECIES OF G 0.49 7
HEIGHT 6 LOAD 2 3 4 NORMAL + 50% + 100% NORMAL +50% + 100% NORMAL +50% + 100% 8
(Inches) (plf) 2Lags/Ft. 3Lags/Ft. 4Lags/Ft. 2Lags/Ft. 3Lags/Ft. 4Lags/Ft. 2Lags/Ft. 3Lags/Ft. 4Lags/Ft. 9
72 2000 597 895 1240 822 1233 1240 882 1240 1240
72 3000 597 850 850 822 850 1 850 850 850
48 3000 597 895 1588 822 1233 1 1644 1 882 1323 1 17301
i These allowable loads are based upon Allowable Stress Design(ASD) loads. No design load reduction or allowable load
increase is permitted for use with these allowable loads.
2 Allowable loads are not to exceed local soil allowable bearing values.
3 Axial loads combined with backfill equivalent to 30"high maximum fluid pressure of 40 pcf, or 24"high maximum of 64 pcf.
4 This is a maximum axial allowable load in combination with allowable shear and backfill loads.Where the enforced Model
Code permits,the live and snow load portions of the design axial load combinations may be reduced 25%maximum.
May use TABLE 1 for any panels with gravity loading.only(panels not required for shear/racking resistance).
s These allowable loads are for Model Codes that permit a 25% reduction of transient design loads, or a 33%allowable stress
increase.Where the local code does not allow either of these adjustments,these allowable loads must be reduced by 25%.
6 Panel Height is the total height including 4.5"embedment into concrete. Net panel height is 4.5"less than these values.
7 Minimum species density factor of member accepting lag screws from panels. G of 0.49 includes DF-Larch,
0.42 includes Hem-Fir and Spruce-Pine-Fir, and 0.35 includes Redwood and Cedar.
8 This indicates the number of lag screws per lineal foot of attached panel: "NORMAL"=2; "+50%"=3; "+100%"=4.
9 A 0.25"diameter by 2"long lag screw, minimum. Must be standard"full body"diameter dimension per NDS.
Fasteners are assumed to be loaded parallel to wood grain, a 33%reduction must be taken for perpendicular loading.
Any other fastening or connection design must be shown by rational analysis to meet the required loadings.
10 Seismic force design factors are as follows: Under the 2005 through 2010 ASCE-7 table 12.2-1, R=6.5, Oo=3, Cd 4