HomeMy WebLinkAbout2140 W 18th St - EngineeringClient: Golden West Spraybooth Project Engineer: Kevin ~liI ;r
Order Number: 3053017 Reviewer initials:
Product: Paint Spray Booth Model Number: ATDS
Test Sample Number: 03-3666-A, 03- Date: 30 December 2[ 03 I Standard: NFPA 33, 2000 Ed
3666-B, and 03-3666-C, production
units installed at West Port
Shipbuilders in Port Angeles, WA
Par. # Complies Comment
CHAPTER 9 AUTOMATED ELECTROSTATIC SPRAY EQUIPMENT
9.1 to 9.5 N/A No such spray equipment used.
CHAPTER 10 HAND-HELD ELECTROSTATIC SPRAY EQUIPMENT
10.1 to 10.5 N/A No such spray equipment used.
CHAPTER 11 DRYING, CURING, OR FUSION PROCESS
1 1.1 N/A Genera{. No separate drying/curing apparatus, Drying is incorporated by heater in the
listed air make-up unit,
1 1.2 YES Spray Enclosures Used for Ambient Air Drying. Spray booth can be used for ambient
drying. Provides proper ventilation (same as when painting) and does not allow vapors to
exceed 25% of the lower flammability limit.
11.3 YES Spray Enclosures Used for Drying et Elevated Temperatures. Because of heater in air
make up unit the enclosure can be considered to be used for drying at elevated
temperatures.
11.3.1.1 YES Interior surfaces are smoothed and easily cleaned.
YES
11.3.1.2 Spray booth is provided with a high temperature limit switch that automatically shuts off
the drying process if 200 °F (93 °C) is reached. (Note - UFC required a maximum of
160°F.)
Temperature setting of the booth set to exceed 175°F (71 °C).
11.3.1.3 YES Control interlock is provided so that the spraying cannot be performed during the drying
or curing process at elevated temperatures.
11.3.1.4 N/A No radiant drying apparatuses are used.
11.3.1.5 N/A No radiant drying, curing or fusion apparatus are used.
11.3.1.6 N/A No radiant drying, curing or fusion apparatus are used.
1 1.3.1,7 N/A Operations are not part of the manufacture's responsibility and are not part of the scope
of this evaluation. Containers of flammable or combustible liquids are the end user
responsibility.
1 1.3.1.8 N/A Operations are not part of the manufactures responsibility and are not part of the scope
of this evaluation. Automobiles are not the product sprayed in this operation. Used to
spray cabinets for yacht interiors.
1 1.3.2 N/A Heating is performed in the same room as the spray application. Spray application is
interlocked with the heating cycle.
Client: Golden West Spraybooth Project Engineer: Kavin Mllel ~,~,~
Order Number: 3053017 Reviewer Initials:
Product: Paint Spray Booth Model Number: ATDSI~OP[:
Test Sample Number: 03-3666-A, 03- Date: 30 December 2003 Standard: NFPA 33, 2000 Ed
3666-B, and 03-3666-C, production
units installed at West Port
Shipbuilders in Port Angeles, WA
Par. # Complies Comment
1 1.4 N/A Flash-Off Areas. None provided
1 1.5 N/A Ventilation. Fusion apparatus are not used.
1 1.6 N/A Warning Signs. No drying, curing or fusion apparatus are used.
CHAPTER 12 MISCELLANEOUS SPRAY OPERATIONS
1 2.1 N/A Vehicle Undercoating and Body Lining. Spray booth is not used for this application.
12.2 N/A Preparation Workstations. Spraybooth is not a preparation workstation.
1 2.3 N/A Limited Finishing Workstations. Not considered as a limited finishin~l workstation.
CHAPTER 13 POWDER COATING
13.1 to 13.12 N/A Powder coating is not performed.
CHAPTER 1¢ ORGANIC PEROXIDES AND PLURAL COMPONENT COATINGS
14.1 to 14.9 N/A No such coatings used.
CHAPTER 15 STYRENE CROSS-LINKED COMPOSITES MANUFACTURING
(GLASS FIBER REINFORCED PLASTICS)
1 5.1 to 1 5.7 N/A No such application is performed.
CHAPTER 16 TRAINING
16.1 Yes All personnel employed are properly trained to use equipment and application.
CHAPTER 17 REFERENCE PUBLICATIONS
1 7.1 -- Referencing NFPA Standards to be considered for particular portions of this standard.
ETL SEMKO ~t~
Intertek Report No. 3053017-1 Issue Date: 12/30/2003
Attachment Three: Resolution of Discrepancies
Clause No. I Discrepancy I Resolution
None
ETL SEMKO
Intertek Report No. 3053017-1 Issue Date: 12/30/2003
Attachment Four: Testing
The product was tested in accordance with the Standard for Spray Application Using Flammable or
Combustible Materials; (NFPA 33: 2000).
The following tests were performed:
Note: Evaluated for construction only. No tests performed.