Series TY -FRB — 2.8, 4.2, 5.6, and 8.0 K -factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY -FRB, 2.8, 4.2, 5.6, and
8.0 K -factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY -FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at -
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the `INSTALLER
WARNING' that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY -FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY -FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 -
Upright 2.81K, 1/2"NPT
TY1231 -
Pendent 2.81K, 1/2"NPT
TY2131 -
Upright 4.21K, 1/2"NPT
TY2231 -
Pendent 4.21K, 1/2" NPT
TY3131 -
Upright 5.61K, 1/2"NPT
JULY, 2004
TY3231 - Pendent 5.61K, 1/2"NPT
TY4131 - Upright 8.OK, 3/4"NPT
TY4231 - Pendent 8.OK, 3/4" NPT
Technical
Data
Approvals
UL and C -UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psis/2 (40,3 LPM/bars/2)
K = 4.2 GPM/psis/2 (60,5 LPM/bars/2)
K = 5.6 GPM/psis/2 (80,6 LPM/bars/2)
K = 8.0 GPM/psil/2 (115,2 LPM/bars/2)
Temperature Ratings
Refer to Table A and B
TFP171
Page 2 of 8
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING1/2„ ** NOMINAL
SURFACE NPT MAKE -IN
1
1
2-1/4"
(57,2 mm)
1-9/16"
(39,71 mm)
' 1
SSP DEFLECTOR
PENDENT
STYLE 10 or 20
RECESSED
ESCUTCHEON
SSU*
DEFLECTOR
2-7/8"(73,0 mm) DIA.
7/16"
(11,1 mm)
i NOMINAL
MAKE -IN
NRENCH 2'3/16"
FLATS (55,6 mm)
1/2" NPT**
RECESSED PENDENT UPRIGHT
TFP171
CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame.
Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K -FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING1/2„ ** NOMINAL
SURFACE NPT MAKE -IN
1
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
SSP DEFLECTOR*
PENDENT
STYLE 10 or 20
RECESSED SSU*
ESCUTCHEON DEFLECTOR
~— 2-7/8"(73,0 mm) DIA.
I'N 7/16"
(11,1 mm)
NOMINAL
MAKE -IN
� � � 2-3/16"
NRENCH (55,6 mm)
FLATS
1/2" NPT**
RECESSED PENDENT UPRIGHT
CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw "Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K -FACTOR, 1/2 INCH NPT
Finishes Bulb . . . . . . . . . . . . Glass n
Sprinkler: Refer to Table A and B Compression Screw . . . . . Bronze operation
Recessed Escutcheon: White Coated, Deflector . . . . . . . Copper/Bronze
Chrome Plated, or Brass Plated Bushing (K=2.8) . . . . . . . Bronze The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
Physical Characteristics
Frame . . . . . . . . . fluid expands sufficiently to shatter the
Bronze glass Bulb, allowing the sprinkler to
Button . . . . Brass/Copper
Sealing Assembly activate and water to flow.
. . . . . Beryllium Nickel w/Teflont
Y
M
E
a)
m
m
ar
Ln
is
0
a
0
t
TFP171
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING1/2„ ** NOMINAL
SURFACE NPT MAKE -IN
1
2-3/16"
(55,6 mm) �
1-1/2"
(38,1 mm)
STYLE 10 or 20
RECESSED
ESCUTCHEON
SSU*
DEFLECTOR
SSP DEFLECTOR* — 2-7/8" (73,0 mm) DIA.
7/16"
(11,1 mm)
NOMINAL
MAKE -IN
�� 2-3/16"
NRENCH (55,6 mm)
FLATS
1/2" NPT** +
PENDENT RECESSED PENDENT UPRIGHT
Page 3 of 8
CROSS SECTION
6*
5
4
3
1
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K -FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE 3/4 MAKE -IN ESCUTCHEON SSU
NPT � � DEFECTOR
1/2" 5
2-5/16" I
(58,7 mm) NOMINAL
I
� � NOM4
MAKE -IN
1-9/16" 2-1/4" 2
(39,7 mm) WRENCH—ter t + (57,2 mm)
FLATS 11 3
SSP DEFLECTOR* — 2-7/8" (73,0 mm) DIA. 3/4" NPT **
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame.
Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY -FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K -FACTOR, 314 INCH NPT
Listing is based on the requirements of
Design NFPA 13, and FM Approval is based Installation
Criteria on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style The Series TY -FRB Sprinklers must be
10, 20, 30, or 40 Recessed Escutch- installed in accordance with the follow -
The Series TY -FRB Pendent and Up- eon, as applicable, is to be used for ing instructions:
right Sprinklers are intended for fire recessed pendent installations.
protection systems designed in ac- NOTES
cordance with the standard installation Do not install any bulb type sprinkler if
rules recognized by the applicable the bulb is cracked or there is a loss of
Listing or Approval agency (e.g., UL liquid from the bulb. With the sprinkler
Page 4 of 8
TFP171
SPRINKLER FINISH (See Note 7)
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
K TYPE
TEMP. BULB NATURAL
CHROME
WHITE***
(13,4 to 26,8 Nm). A maximum of 30
LIQUID BRASS
PLATED
POLYESTER
ft. lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 314 NPT con -
135°F/57°C Orange
nections. Higher levels of torque may
PENDENT
155°F/68°C Red
distort the sprinkler inlet and cause
(TY1231 )
1, 2, 3, 5
leakage or impairment of the sprinkler.
and
175°Fl79°C Yellow
UPRIGHT
200°F/93°C Green
Do not attempt to make-up for insuffi-
(TY1131)
cient adjustment in the escutcheon
2.8
286°F/141°C Blue
plate by under- or over -tightening the
1/2"
sprinkler. Readjust the position of the
NPT
135°F/57°C Orange
sprinkler fitting to suit.
RECESSED
PENDENT
155°F/68°C Red
ThP-
e Series TY -FRB Pendent and U
(TY1231)*
1750F/79°C Yellow
right Sprinklers must be installed in
Fi ure 5
g
200°F/93°C Green 1, 2, 5
accordance with the following instruc-
tions.
135°F/57°C Orange
Step 1. Pendent sprinklers are to be
RECESSED
155°F/68°C Red
installed in the pendent position, and
PENDENT
upright sprinklers are to be installed in
(TY1231)**
175°F/79°C Yellow
the upright position.
Figure 6
200°F/93°C Green
Step 2. With pipe thread sealant ap-
135°F/57°C Orange
plied to the pipe threads, hand tighten
PENDENT155°F/68°C
the sprinkler into the sprinkler fitting.
(TY2231)
Red
Step 3. Tighten the sprinkler into the
and
175°F/79°C Yellow
sprinkler fitting using only the W -Type
UPRIGHT
200°F/93°C Green
6 Sprinkler Wrench (Ref. Figure 13).
(TY2131)
With reference to Figures 1, 2, 3, and
42
286°F/141°C Blue1 2
4, the W -Type 6 Sprinkler Wrench is to
1/2"
NPT
135°F/57°C Orange
be applied to the sprinkler wrench
RECESSEDflats.
155°F/68°C I Red
PENDENT
(TY2231)*
175°F/79°C I Yellow
The Series TY -FRB Recessed Pen -
Figure 7
200°F/93°C I Green
dent Sprinklers must be installed in
accordance with the following instruc-
135°F/57°C I Orange
tions.
RECESSED
155°F/68°C I Red
Step A. After installing the Style 10.
PENDENT
(TY2231p*
175°F/79°C I Yellow
20, 30, or Mounting Plate, as
cable, overr the sprinkler threads and and
Figure 8
200°F/93°C I Green
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
NOTES:
kler into the sprinkler fitting.
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Step B. Tighten the sprinkler into the
2. Listed by Underwriters
Laboratories, Inc. for use in Canada (C -UL) as Quick Response
sprinkler fitting using only the in Type
Sprinklers.
3. Approved by Factory
Mutual Research Corporation (FM) as Quick Response Sprin-
7 Recessed Sprinkler Wrench (Ref.
klers.
Figure 14). With reference to Figure 1,
5. Approved by the City of New York under MEA 354-01-E.
2, 3, and 4, the W -Type 7 Recessed
7. Where Polyester Coated Sprinklers are noted to be UL and C -UL Listed, the sprin-
Sprinkler Wrench is to be applied to
klers are UL and C -UL Listed as Corrosion Resistant Sprinklers.
the sprinkler wrench flats.
* Installed with Style
10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Step C. After the ceiling has been in -
Recessed Escutcheon, as applicable.
" Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
stalled or the finish coat has been ap-
Recessed Escutcheon, as applicable.
lied, slide On the St
p le 10, 20, 30, Or y
**' Frame and Deflector only. Listings and approvals apply to color (Special Order).
40 Closure over the Series TY -FRB
N/A: Not Available
Sprinkler and push the Closure over
the Mounting Plate until its flange
TABLE A
comes in contact with the ceiling.
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K -FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 112 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1116 inch to 14 ft. lbs. (9,5 to 19,0 Nm). A maxi -
(1,6 mm) for the 135°F/571C to 3132 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286°F/141 °C may be used to install sprinklers with
temperature ratings. 112 NPT connections. A leak tight 314
TFP171
Page 5of8
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE 8
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K -FACTOR SPRINKLERS
SPRINKLER FINISH (See Note 8)
K
TYPE
TEMP.
BULB
NATURAL CHROME WHITE***
LEAD
LIQUID
BRASS PLATED POLYESTER
COATED
135°F/57°C
Orange
PENDENT
155°F/68°C
Red
(TY3231)
1, 2, 3, 4, 5, 6, 7
1, 2, 3, 5
and
175°F/79°C
Yellow
UPRIGHT
200°F/93°C
Green
5.6
(TY3131)
286°F/141°C
Blue
1/2"
NPT
135°F/57°C
Orange
RECESSED
155°F/68°C
Red
PENDENT
1, 2, 4, 5
N/A
(TY3231)*
175°F/79°C
Yellow
Figure 9
200°F/93°C
Green
135°F/57°C
Orange
RECESSED
155°F/68°C
Red
PENDENT
1, 2, 3, 4, 5 1, 2, 4, 5
N/A
(TY3231)**
175°F/79°C
Yellow
Figure 10
200°F/93°C
Green
135°F/57°C
Orange
PENDENT
155°F/68°C
Red
(TY4231)
1, 2, 5
and
175°F/79°C
Yellow
1, 2, 3, 4, 5, 6, 7
UPRIGHT
200°F/93°C
Green
8.0
(TY4131)
286°F/141°C
Blue
3/4"
NPT
135°F/57°C
Green
RECESSED
155°F/68°C
Orange
PENDENT
1, 2, 4, 5
N/A
(TY4231)*
175°F/79°C
Red
Figure 11
200°F/93°C
Yellow
135°F/57°C
Orange
RECESSED
155°F/68°C
Red
PENDENT
1, 2, 3, 4, 5
N/A
(TY4231)**
175°F/79°C
Yellow
Figure 12
200°F/93°C
Green
Page 5of8
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C -UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C -UL Listed, the sprinklers are UL and C -UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE 8
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K -FACTOR SPRINKLERS
Page 6 of 8
5/8t1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
SURFA E
SURFACE
CLOSURE
2-7/8" DIA. _
(73,0 mm)
2-1/4" DIA.
157 7 mml
3/4" (19,1 mm)
1/4" (6,4 mm)
OOUNTING
PLATE
SERIES
TY -FRB
1/8"
(3,2 mm)
1-5/16" (33,3 mm)
13/16" (20,6 mm)
FIGURE 5
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K -FACTOR, 1/2 INCH NPT
2-7/8" DIA. _
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE
FITTING
(3,2 8MM)
A-,
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TY -FRB 3/4" (19,1 mm)
FIGURE 7
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K -FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY -FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
itcontrols, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
_ 1/2t1/8"
(12,7t3,2 mm)
FACE OF
SPRINKLER
FITTING
f \
MOUNTING
SURFACE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA, y
IS7 � mml
TFP171
1/2" (12,7 mm)
1/4" (6,4 mm)
4OUNTING
PLATE
1/8"
(3,2 imm)
CLOSURE SERIES 1-5/16" (33,3 mm)
TY -FRB 1-1/16" (27,0 mm)
FIGURE 6
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K -FACTOR, 112 INCH NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE/
CLOSURE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA. yl
(S7 9 mm,
1/2" (12,7 mm)
1/4" (6,4 mm)
WING
.ATE
SERIES 1-1/4" (31,8 mm)
TY -FRB 1" (25,4 mm)
FIGURE 8
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K -FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFP171
5/811/4"
(15,9±6,4 mm)
FACE OF
SPRINKLE
FITTING
MOUNTIM
SURFACE
2-7/8" DIA. _
(73,0 mm)
�- 2-1/4" DIA. -�
(57 2 mm)
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
CLOSURE SEHIEb 1-1/4" (31,8 mm)
TY -FRB 3/4" (19,1 mm)
FIGURE 9
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K -FACTOR, 112 INCH NPT
CLOSURE SERIES 1-5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm)
FIGURE 11
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K -FACTOR, 314 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
Page 7 of 8
2-7/8" DIA.
_ 1/211/8" (73,0 mm) 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
SPRINKLER 71- PLATE
FITTING
1/
(3'2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm)
TY -FRB 1" (25,4 mm)
FIGURE 10
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K -FACTOR, 1/2 INCH NPT
1/2±1/8"
(12,713,2 mm)
FACE OF
SPRINKLE
FITTING
\
MOUNTINi
SURFACE
2-7/8" DIA _
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8'.
(3,2 mm)
CLOSURE SERIES 1-5/16" (33,3 mm)
TY -FRB 1-1/16" (27,0 mm)
FIGURE 12
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K -FACTOR, 3/4 INCH NPT
2-7/8" DIA
_
5/8±1/4"
(73,0 mm)
3/4" (19,1 mm)
(15,9±6,4 mm)
2-1/4" DIA.
1/4" (6,4 mm)
(57,2 mm)
FACE OF
MOUNTING
SPRINKLER
(END "B" USED FOR
PLATE
FITTING
IN TO ENSURE
ENGAGEMENT
1/8"
FIGURE 13
WRENCHING AREA
(3,2 mm)
WRENCH
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TY -FRB 13/16" (20,6 mm)
FIGURE 11
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K -FACTOR, 314 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
Page 7 of 8
2-7/8" DIA.
_ 1/211/8" (73,0 mm) 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
SPRINKLER 71- PLATE
FITTING
1/
(3'2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm)
TY -FRB 1" (25,4 mm)
FIGURE 10
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K -FACTOR, 1/2 INCH NPT
1/2±1/8"
(12,713,2 mm)
FACE OF
SPRINKLE
FITTING
\
MOUNTINi
SURFACE
2-7/8" DIA _
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8'.
(3,2 mm)
CLOSURE SERIES 1-5/16" (33,3 mm)
TY -FRB 1-1/16" (27,0 mm)
FIGURE 12
SERIES TY -FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K -FACTOR, 3/4 INCH NPT
FIGURE 14
local requirements and/or national W -TYPE 7 RECESSED
codes. SPRINKLER WRENCH
WRENCH
RECESS
/
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
PUSH WRENCH
3/4" NPT MODELS)
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
FIGURE 13
WRENCHING AREA
W -TYPE 6 SPRINKLER
WRENCH
FIGURE 14
local requirements and/or national W -TYPE 7 RECESSED
codes. SPRINKLER WRENCH
r
Page 8of8
TFP171
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE,
Ordering
Procedure
Ow-damt yqun local distributor for avail-
abfl$t'y.indicate the
full product
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K -factor), (specify
temperature rating), Series TY -FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2" (15 mm)
Style 10
Chrome Plated ............ P/N 56-701-9-010
White Coated ............. P/N 56-701-4-010
White RAL9010' ........... P/N 56-701-3-010
Brass Plated .............. P/N 56-701-2-010
1/2" (15 mm)
Style 20
Chrome Plated ............ P/N 56-705-9-010
White Coated ............. P/N 56-705-4-010
White RAL9010'........... P/N 56-705-3-010
Brass Plated .............. P/N 56-705-2-010
3/4" (20 mm)
Style 30
Chrome Plated ............ P/N 56-705-9-011
White Coated ............. P/N 56-705-4-011
White RAL9010"........... P/N 56-705-3-011
Brass Plated .............. P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated ............ P/N 56-700-9-010
White Coated ............. P/N 56-700-4-010
White RAL9010' ........... P/N 56-700-3-010
Brass Plated .............. P/N 56-700-2-010
" Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W -Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W -Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
P/N 57 -
XXX - X
i
- XXX
I
TEMPERATURE
I
MODEUSIN
RATING
SPRINKLER
330
2.8K UPRIGHT (1/2"NPT)
TY1131
135
135'F/57'C
331
2.81K PENDENT (1/2"NPT)
TY1231
1
NATURAL BRASS
155
155'F/68'C
340
4.2K UPRIGHT (1/2"NPT)
TY2131
4
WHITE POLYESTER
175
175'F/79'C
341
4.2K PENDENT (1/2"NPT)
TY2231
3
WHITE (RAL9010)'
200
200'F/93'C
370
5.6K UPRIGHT (1/2"NPT)
TY3131
9
CHROME PLATED
286
286°F/141°C
371
5.6K PENDENT (1/2"NPT)
TY3231
7
LEAD COATED
390
8.OK UPRIGHT (3/4"NPT)
TY4131
391
8.OK PENDENT (3/4"NPT)
TY4231
' Eastern
Hemisphere sales only.
TABLE C
PART
NUMBER SELECTION
SERIES TY -FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE,
Ordering
Procedure
Ow-damt yqun local distributor for avail-
abfl$t'y.indicate the
full product
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K -factor), (specify
temperature rating), Series TY -FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2" (15 mm)
Style 10
Chrome Plated ............ P/N 56-701-9-010
White Coated ............. P/N 56-701-4-010
White RAL9010' ........... P/N 56-701-3-010
Brass Plated .............. P/N 56-701-2-010
1/2" (15 mm)
Style 20
Chrome Plated ............ P/N 56-705-9-010
White Coated ............. P/N 56-705-4-010
White RAL9010'........... P/N 56-705-3-010
Brass Plated .............. P/N 56-705-2-010
3/4" (20 mm)
Style 30
Chrome Plated ............ P/N 56-705-9-011
White Coated ............. P/N 56-705-4-011
White RAL9010"........... P/N 56-705-3-011
Brass Plated .............. P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated ............ P/N 56-700-9-010
White Coated ............. P/N 56-700-4-010
White RAL9010' ........... P/N 56-700-3-010
Brass Plated .............. P/N 56-700-2-010
" Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W -Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W -Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TECHNICAL
Permit # 11656
Address R31 Cox-ok'�ve, Sf
Project description al,�,��„C, kosp�'61
CC�ln�rnpiG V�lm.,��cal i,P.t�Aen-� ��Y-rie�'' Wc01 Iq DI
Date the permit was finaled 7
Number of technical pages I I
C��t,(. (--t l� a.r✓ a ��� �L 4 L. Q � �i
� r f
oM L -i ,je� u e.g t e� �. t r�� - s�t-w�--dC' ,,..� ,/eti ...�,•� c.o ....G...'� c
b eA--l& ems+ .� { _� 1� 't f� o Q i-
07, 40
i� W A„
LAJ t ,N tz) co Oy
/ 1l.A vi n• ti t
IST 6
ON
4 o Ci g' 105
b0 CTble. /b�'c
t�
CCuPai-
cy C4,1 -,e -d /y S a� %GG/r
/6.z:,: fid. 2 �i•.o.Ls 5f4fr� �st•i 6'3a 2.•3 x/�v.wc
e-Ql W 3 a (D 36)
CAL.
a
b't4` l
2r. 5S u G
ACL) �-
�S� IMOD p'Sr
tA, 2
.y :ai,xfnt...�;bCeGY. r:..¢Sf.S 1 .. •,� f�'' � � ( ..._..» } _—. �-SSv�--a, ,.. .,
dui a to 5t'1p
t
dove/tet 5.
G.3 I2
i
;? •t:
�
E - J D J
C LAr-o, I I 4;L " 5
A55�-
A
- T y -4T;l G. m 7 -DI O� L"IV
-p tot-- of - -2.. '.5-
W 1. yYo's-xISa -- !3/2 3r +o9y
Z6 Z, z s 5 188
ISO
S� , L13 S
S W� III Zl$
yah 3
-
` s�
!vim
j S�yti
r
Z, 31r ,v
� o Gso
p � ` � z Cwa63� � i'aoa pS�,L tj oo IOS� v1
W3
Y5;W ,1, flb 33 _ I, 93 ' v/
3 7 -,s -
"C'
-S
4 = 11,063-,y 914141
3
Y5;W ,1, flb 33 _ I, 93 ' v/
3 7 -,s -
"C'
-S
`a o � to e.- Oo..rk(o�- K 3� i...X, 3 .}� = 1 7,l 3
{ Zs
f
3 t v
13ep
I ,
rL 11 �- I $ _ `i %.g
41 urE,
S3Y�
fZ86G /s-vo Pig
4 = 11,063-,y 914141
t'}
4,.
Vol
r `
1.3cac PIS
, Bio
.. :2 or,
t
}f�
`a o � to e.- Oo..rk(o�- K 3� i...X, 3 .}� = 1 7,l 3
{ Zs
f
3 t v
13ep
I ,
rL 11 �- I $ _ `i %.g
41 urE,
S3Y�
fZ86G /s-vo Pig
0
<1 IQ 'A I't A- 0,11
IIN
,
ov 9"/
7f-
0 z
rw
Cn
04 2
I A )4 z )e Iz
0 S"z CI? -U(Z t Y YO, po
of
srl o0oly
0
4 ol-�ao
v
ly T C, j
v
4T 4-rara
71n -v, c4l
o
I
M&
pv()n
104
000
an 4A #A
xxx
in f" m
"I rn m
-4-4-4
SA tA 1A
%z E-roJG
v
FHl4A-
W
t
wo
/a — gra �t yes
co
Z
_o _v'I
y "r'D Z
conn
cvww
t10f Z
k
j
U - !/ 5'/> t t� r�L
fly_ _- G► Pd rpt _ o �o
3"t�Cycv/d �r4 ex `
It f �, wi
�. •art
0 4 D fi i 3,YAA
v���
,,A ! 6
o,q
A S T -//t, 5 T��s
is 4 96► P r
A-5
2
6,A t4 W."'t
AAS
DS
OA Ln LM
(�_) AA
LUWW
lu LU W
xxx
V) V) t
Ln r
000
In2o
04 it
av
2 7-At 7.
A
C4 C4 C4 C4 C4
IQJ ki
/k Aly
41
49,
5 !Z, 7a-
0
6, 0
-4.
A"La-Ov� f&l 'Yl '- S ,
vrl7LO
bw
4/
5 -Y
0', 00Z 0 Z. Ale
kyrZ
�3 6 14� (,z
0, 7,Y
T
bukd Li
v13 C, '9 7- A
?- c e. Q ? I, tepj.
10 )(Jj PS
a
t!9W ff 0-1
s 0
-FV-4,T j=qlG-t'-4�4,tl'
VJ Si--.C,-T
il ft2r_
Iry
0 o
Tt� J> 4 , tye.,*
-7 1
-Z% '--
T
bukd Li
v13 C, '9 7- A
?- c e. Q ? I, tepj.
10 )(Jj PS
a
/,-Jow--j 0sf-,40
tA4 parAv
01111
17X-VY7�' "A ley 1z (TZ tj
?R --z is /-S,
I
..Z /S
A
-A
Z,,Z./..y/
ow-, = J
Hro 56,31 -tow 1(41�1
000
07
mmm
F—IM jv.�
m m m
-4 - LA 4 _f
fA vii
0
9
rn
Q
X� 1, b Q*0-1
-_zV (.4 a
FA
f
i'
�1��-0= 3}3 (G 33 7b 0,Z) 1$3�
.lfIL2 j
\l/lr Flt:-, 0 1„1- fib- to =
-
V /
b
19 Z/ "L
`�'
1
1 � 8 3 •
W W W
1. S3 f
N N N
ao�
N0O
wci t�0.4,'�C1l.33'� n"Yo = 1Y14'�/
�G L•LG•I ) V e' CAI's`�+, // Y/ G04 S •6Y U�Y 4�
P ry
`
W
N
C4 t4 C4
AA JA-
:•;�' y�,,_
:4. ,�,�. ,�.��.5.
� � �.
i x.20' 1. '
3 fij7 }- 14 3.3)
b�'�-.e:,;
Ah
t
/
Uti} �.) = � a r i 3� �` �i• 33� � ^�; t.SZf _
I i }L � �l t'E .111�.1.tc•f" � 1~'t[SS-`'yt �'t�rr"t+ ��'re.s$
2400,0
f
i'
A
K
orev
'7- "b
I zrwP
6,� Wt,,l /
AAODL 3=
i—; Fy --a rwe., t w,,—Vb
It, I,, _ q 10 -- 11,
N-- 1%
lvcj--: i4i7*At
�l A4 =d
3
+14+{.141'0
V�
v
J
6, 4-t, (. C)
.5 ,t
-6 3d >
Alf
961'r eql'uAy
lo -c- Vll Seip J�.r AA -d-` 777 'C"J
fp .4
Z-2.
-AA 31 14 -5 0 6 4 + 2-0 o lz�
T. -:�. 313 ( t 3 -5) + I Ll I
10
LU
WW C2 W%G-
i" lu Im
xxx
An 0 0
co00 o cvv
&M
IC',
—
C4 A C4
C4 C4 C4 "Oote- +y 4 4-,j �i6
Nor- 31301 3- +'100
+ loo A/
v its ,v -
Wit
Mof
f SS'6
10
A)Orf,;,,' -rc,, s'o Dda.-le-le, i6l
7-f 0 -Tiv of '7W6 5-1
/_e r4 kievi
0 3
04-?, 0 04 (0
lk,l
��I-
W W W
to 1A Yf
OOO
of O O
C4
C4rC4
i109 otf
V
),Ve5
W- 313111�t ��.MQ_ o = 3,3(6,33) f 1 L y��)
yt�
J.
t_ h
r
lb 42,61
C; Co
-330" xc m:66��- ,�f- 2`.3fl G e.s6 �� = 6.Q'Z:v
o � .3.�•.3��G, :3°3�� t: l Yl �C, a_ y�.��:,�,.- �• :� s �?� � ' '� �J� �� b __ ` .._
~--
i
i r
S b -ea
Cje� �l2�id� S
0-
fg,5-0 o ;;, /Y/,7
c �6- L /,D
CA-
F he+" -
Ileo x. DA7.j. ! _. /s. P. 7 vSe t¢ � 30 ok �_
32t�
3
j
�$SO
D�J3
i109 otf
V
),Ve5
W- 313111�t ��.MQ_ o = 3,3(6,33) f 1 L y��)
yt�
J.
t_ h
r
lb 42,61
C; Co
-330" xc m:66��- ,�f- 2`.3fl G e.s6 �� = 6.Q'Z:v
o � .3.�•.3��G, :3°3�� t: l Yl �C, a_ y�.��:,�,.- �• :� s �?� � ' '� �J� �� b __ ` .._
~--
i
i r
S b -ea
Cje� �l2�id� S
0-
fg,5-0 o ;;, /Y/,7
c �6- L /,D
CA-
F he+" -
Ileo x. DA7.j. ! _. /s. P. 7 vSe t¢ � 30 ok �_
ig os- W&W
5e ol- C 5-0
"." I= .9 /ft
3 /3 65-) — IZO (6 err?
-r6
13
S70
WWW
xx us A,
in 0 vi
000
-04
:!,13
A A A
C14 04 C4
a
A4
rat rC�c
_)LOA,
re
.,I
'E
e,
S'll x
I
��C4- op -
O—eoP
all t "-21
6� Al
21 L?o
A le-
/�Y 7"
A4 Aso 69 3 3,� -d-P
its,
71
•;;f 4 W,•al w 06 TO"
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
fitly 14 a .
w ift
ikvf
.4" V
WIM
Z
Im Mt "
rt M
kAX' v
P"1141L
J,
_W "gx.
0S
mill;
MW
IPA
F V
i
I J "tch
mi'v
ww.
MM
W -*1 Ni -Al A, �t yh�.011Z.1i, Lou W.
00r
20
� t
o! I I. -
"oo
—4; /1 10),
�e
. �"4NMOk'I"i
"1411
t's
NOW,
'N'
i
I J "tch
mi'v
ww.
MM
W -*1 Ni -Al A, �t yh�.011Z.1i, Lou W.
00r
20
� t
o! I I. -
"oo
—4; /1 10),
�e
A
t's
NOW,
mv
1.
4".
A
TECHNICAL
117
Permit #
Address 3 q ar o vle,
Project description
aVA,
O � 1 CAPAMOIii al POS-Pi�(
(�a�h �himnce -Re-�octet 4
L a st Ch~%ra vl ce A -AA,+ o vi C KS 41`6 313
COP -2.o P -p u nivLi vx A A,+oh
Date the permit was finaled
Number of technical pages
2-o
Dear Mr Swanson,
We are responding to DOH review and comments dated June 4, 2002 for the addition of a QP
freestanding water sculpture feature to the hospital main lobby We have reviewed and
provided responses to each of the noted comments. The attached response addresses each
comment. Additionally we have attached sketches detailing the associated utilities. The
medical centers infection control practitioner had endorsed the design.
There are no structural issues as the fountain sits on an existing interior concrete slab on F
grade.
incerel
Ji Paapke, irector, Facility Management
encl Comments responses
Fountain rendering
O
PAP
Penny Becker PhD,Infection Control
n
Functional Program
Kloppenberg Shop Drawings (6 pages)
Architectural sketches ASK -20 1 and ASK — 20.2 (2 pages)
Mechanical sketches MSK -20 1, MSK -20.2, and MSK -20.3 (3 pages)
Floor sink cut sheet (1 page)
Electrical sketches ESK-20 1 and ESK-20.2 (2 pages)
Cc Donna Davison, Olympic Memorial Hospital
Gary Braun, Mahlum Architects
Lou Haehnlen, City of Port Angeles
Julie Haguewood, Distinctive Designs
Steve Wander, Harmonic Environments
OLYMPIC
MEDICAL CENTER
939 Caroline Street • Port Angeles, Washington • 98362 3997 • (360) 417 7000
D
E� +
June 27 2002
Richard M. Swanson, Architect
JUL ` 2 2002 J
Washington State Department of Health
Construction Review & Acute Care Services
CITY Of PORT ANGELES
2725 Harrison Avenue, NW, Suite 500
COMMUNITY DEVELOPMENT
Olympia, Washington,98504-7852 ,
Project: Olympic Memorial Hospital Main Entrance Remodel and
East Entrance
Addition CRS #6313
Subject: COP -20 Fountain Addition
Dear Mr Swanson,
We are responding to DOH review and comments dated June 4, 2002 for the addition of a QP
freestanding water sculpture feature to the hospital main lobby We have reviewed and
provided responses to each of the noted comments. The attached response addresses each
comment. Additionally we have attached sketches detailing the associated utilities. The
medical centers infection control practitioner had endorsed the design.
There are no structural issues as the fountain sits on an existing interior concrete slab on F
grade.
incerel
Ji Paapke, irector, Facility Management
encl Comments responses
Fountain rendering
O
PAP
Penny Becker PhD,Infection Control
n
Functional Program
Kloppenberg Shop Drawings (6 pages)
Architectural sketches ASK -20 1 and ASK — 20.2 (2 pages)
Mechanical sketches MSK -20 1, MSK -20.2, and MSK -20.3 (3 pages)
Floor sink cut sheet (1 page)
Electrical sketches ESK-20 1 and ESK-20.2 (2 pages)
Cc Donna Davison, Olympic Memorial Hospital
Gary Braun, Mahlum Architects
Lou Haehnlen, City of Port Angeles
Julie Haguewood, Distinctive Designs
Steve Wander, Harmonic Environments
CRS 6316 Comments Response
S24(1) Ozone is an air pollutant and lung irritant. How will you monitor this
operation?
We will install and atmospheric ozone monitor that will automatically shut
off the ozone generator if off -gas levels are too high. If the ozone
generator is shut down as a result of;high levels, the entire system will be
drained, cleaned and refilled.
Since ozone concentrations cannot be monitored in water, how will
you assure efficacy and efficiencies?
Ozone levels in the water will be monitored by and ORP (Oxidation -
Reduction Potential) meter With the ORP type meter can be connected to
the main hospital alarm PLC, we will be assured that as long as a .2 to 4
residual is maintained in the water, the waterfall will be micro -biologically
clean. Further since disinfecting is the priority, we will employ the use of
a backup system that will be integrated with the ORP .Meter above. This
backup system will inject small amounts of Hydrogen Peroxide into the
waterfall. The same ORP meter measures both ozone and H2O2 levels.
S24(2) What organisms will you be looking for in the "water culturing"?
We will us a millpore heterotropic plate count sampler A heterotropic
count will determine the overall microbiological status of the system. We
will be looking for Enteric gram negative rods, Pseudomonas species,
yeast and other aerobic bacteria.
And at what frequency of testing?
Water culturing will occur once a week for a year to establish a correlation
to the ORP readings, seasonal variation, and preventative maintenance
schedule. We will then adjust the samplmg schedule to obtain relevant
data points or sets.
S24(3) What problems or infection control do you expect with children
playing with the water?
With the system described above, the system would be safe. Stainless
steel panels, the water returns to the reservoir via a 1 slot in the stainless
steel, protect the reservoir
S24(4) What parameters were used to establish semi and annual
maintenance?
The manufacturers recommended maintenance schedule was used to
establish the semi and annual maintenance schedule. The schedule will be
adjusted, in conjunction and consultation with the Infection Control
Practitioner, based on the water culturing and historical experience.
With the addition of the hydrogen peroxide, the storage container of H2O2
will be filled monthly The ozone system will require service annually
(that's how long the bulb would last on a 2417 operational basis), the RO
(Reverse Osmosis) system will require annual service if it were operating
continuously
S24(5) Please explain how the water is "self -disinfected"?
With the addition of the systems above, the system is continuously
disinfected and monitored.
S24(6) How will you monitor and control moisture and humidity from this
display?
This display is located in the main lobby of the facility adjacent to the
main entrance of the facility In conjunction with water culturing, we will
utilize a particle counter Pacific Scientific Instruments Met One Model
227A .5 1 CE NIMH, which in addition to measuring particles, measures
temperature and relative humidity This information will be downloaded
into a computer program and trended.
S24(7) Please provide a copy of this display's plans for plumbing and the
"water maintenance system" (RO and Ozone). The partial copy of the
plan is incomplete.
Please see the attached drawings, Kloppenberg Shop Drawings (6 pages),
Architectural sketches ASK -20 1 and ASK — 20.2 (2 pages), Mechanical
sketches MSK -20 1, MSK -20.2, and MSK -20.3 (3 pages), Floor sink cut
sheet (1 page), Electrical sketches ESK-20 I and ESK-20.2 (2 pages)
S24(8) The reduced pressure backflow assembly shall be accessible per
Section 603.3.3 UPC.
Please refer to the attached drawings noted above All devices will be
installed per all applicable codes and regulations.
4w
OLYMPIC
1)1(,Al, CF-NTER
OLYMPIC MEDICAL CENTER
FUNCTIONAL PROGRAM
Lobby Fountain
May 13, 2002
CRS # 6313
The purpose of this water feature is to provide patients, visitors, staff, and guests with an
eye pleasing sculpture that is soothing and relaxing while creating low level background
noise to aide in preserving confidentiality of adjacent areas.
PROJECT GOALS, PRIORITIES & OBJECTIVES
1 To provide an eye pleasing, soothing, and relaxing water feature/sculpture.
2. A feature/sculpture that creates water noise, low level background noise, that
is not offensive, that is soothing and relaxing while improving confidentiality
of adjacent areas.
3 Provide a visual impact feature to complement the remodeled lobby
4 Install a "state of the art" system that will provide pure water and is self -
disinfecting.
MAINTENANCE
The following items have been put together jointly by Penny Becker, Infection
Control, Jim Paapke, Director of Facilities Management and manufacturers
recommendations.
Weekly -
Check and measure dissolved solids to check water purity
Check sump water levels
Check and verify operation of the Reverse Osmosis Unit
Check and verify operation of the Ozone (Silent Air) Unit*
*Note Penodic water culturing of in and out water to establish baseline and/or as needed
based on Ozone Unit operation.
Semi -Annually -
Completely drain, clean and refill fountain
Annually-
RO Unit
Replace carbon and sediment filters
Replace RO membrane
Silent Air Unit (Ozone)
Refurbish/charge Silent Air ozone unit
pke, Dir tor, Facility Management
PtennyBecker hD, Infection Control
N
GENERAL NOTES
OWNER IS TO PROVIDE THE FOLLOWING
1) MANPOWER AND EQUIPMENT REQUIRED TO UNLOAD THE CRATED
PRODUCTS FROM THE CARRIER'S TRUCK DELIVERED TO THE JOB, AND
TO ASSIST OUR INSTALLATION SUPERVISOR IN MOVING MATERIALS INTO
PLACE PLEASE CAREFULLY INSPECT THE CRATES, NOTING ANY
VISIBLE DAMAGE ON THE BILL OF LADING, AND PROVIDE SAFE STORAGE
FOR THEM PRIOR TO INSTALLATION.
2) PLUMBING CONNECTIONS
A - STANDARD 3/8° WATER LINE TO THE BASIN, CONNECTED TO AS
PURIFIED A WATER SOURCE AS POSSIBLE, SUCH AS DISTILLED OR
DEIONIZED WATER OR A REVERSE OSMOSIS SYSTEM, TO MINIMIZE
CLEANING AND MAINTENANCE
B - 1 1/2" NPT S/S COUPLING DRAIN WITH PVC STAND PIPE O'FLOW
BY HARMONIC ENVIRONMENTS, FOR CONNECTION TO 1 1/2" DRAIN LINE
BY OTHERS
3 ) STANDARD 12" X 12° COMMERCIAL FLOOR SINK, FLOOR DRAIN, OR
HARD PIPE TO BLDG WASTE LINE
4) STANDARD 115 VOLT GFI OUTLET(S)
5) LEVEL SURFACE FOR THE BASIN.
6.) STRUCTURAL SUPPORTS AS NECESSARY
PROJECT- GL
OLYMPIC MEDICAL CENTER SINE SIDED
K L O P P E N 13 E R G PORT ANGELES, WA. STAINLESS STEEL
262, WEST OXFORD PREPARED FOR HARMONIC ENVIRONMENTS WATER FEATURE
3o 61. COLORADO 80110w�� is � FORT LAUDERDALE, FL.
DATE: W-30-02
DRAWN BY: M.L.S.
SCALE: AS NOTED
JOB NO.
9884 -
SHEET 1 OF 6
GRANITE
LIMESTONE
SHOWN
ISOMETRIC
WATER FEATURE
1/2' = 1 -0'
KLOPPENBERG "" OLYMPIC MEDICAL CENTER SINGLE SIDED
PORT ANGELES, WA. STAINLESS STEEL
2627 WEST OXFORD PREPARED FOR- HARMONIC ENVIRONMENTS WATER FEATLIRE
ENGLEWOOD, COIDRAD0 6D116
SOY76H60i QuaUtV
a'sm sur swr FORT LAUDERDALE FL.
DATE 01-30.02
DRAWN BY: H.L.S.
SCALE: AS NOTED
JOB N0.
9884—
SHEET 2 OF 6
GRANITE
LIMESTONE
SHOWN
6
L lL
PLAN VIEW
WATER FEATURE
7/16 = 1 -0'
19� 179h
1
N
------------------------------------
I` 18$ I 21j' —I— 135'
I 1774'
LEFT SIDE
WATER FEATURE
7/16 = 1 -0'
KLOPPENBERG
2627 WEST OXFORD
ENGLEWOOO*COLORADO SOHO
303-761-1615 Quality is
the But Buy
FRONT VIEW
WATER FEATURE
7/16 = 1 -0'
PROJECT- OLYMPIC MEDICAL CENTER
PORT ANGELES, WA.
PREPARED FOR- HARMONIC ENVIRONMENTS
FORT LAUDERDALE, FL.
SINGLE SIDED
DATE 01-30-W
STAINLESS STEEL
DRAWN BY: M.L.S.
WATER FEATURE
SCALE: AS NOTED
JOB NO.
9884—
SHEET 3 OF 6
DRAWING NOTES
LETTER DESCRIPTION
(4f 1 SLOT TO ACCOM. PLUG/CORD @ BOTH
ENDS OF WATER FEATURE BASIN. 115V
WALL OUTLET BY OTHERS. (20 ft.cord)
3A. (T-304) S/S
KET SUPPORT
LIMESTONE LIDS
IDS
W rT I LI\ I LI -1 I UI\L
1/2' = 1 -0'
GRANITE
LIMESTONE
NOT SHOWN
KLOPPENBERG P"0JEcT OLYMPIC MEDICAL CENTER
PORT ANGELES, WA.
1627 WEST OXFORD FFEYARED FOR' HARMONIC ENVIRONMENTS
SHS-La1-1615 COLORADO 60116 auat+iv is the Best Buy FORT LAUDERDALE, FL.
ISOMETRIC
WATER FEATURE
1/2' = I -0'
SINGLE SIDED
DATE 0I-30-02
STAINLESS STEEL
DRAWN BY: M.L.S.
WATER FEATURE
KALE: AS NOTED
JOB NO.
9884—
SHEET 4 OF 6
DRAWING NOTES
LETTER DESCRIPTION
2A SLOT @ BOTH ENDS OF WATER FEATURE
BASIN, TO ACCOM. WATER INLET
CONNECTION BY HARMONIC ENVIRONMENTS.
3/8' WATER LINE BY OTHERS.
2B 1 1/2'NPT S/S COUPLING DRAIN WITH PVC
STAND PIPE O'FLOW BY HARMONIC
ENVIRONMENTS, FOR CONNECTION TO 1 1/2'
DRAIN LINE BY OTHERS.
_ 36 1 TYP11-
PLAN VIEW
WATER FEATURE
1/2' = 1 -0'
57'
.D
m
�u
2A
r7-
e
2B 6 2B
18' 135'
LEFT SIDE FRONT VIEW
WATER FEATURE WATER FEATURE
1/2' = 1 -0' 1/2' = 1 -0'
OLYMPIC MEDICAL CENTER
KLOPPENBERG PORT ANGELES, WA.
z62TWEST OXFORD PREPARED FOR HARMONIC ENVIRONMENTS
303-6w�' `°L°R"°° °d1D Qwa:iv u N. eue a I, FORT LAUDERDALE, FL.
GRANITE
LIMESTONE
NOT SHOWN
I
1 TYP 36
_1 _ _
SINGLE SIDED
DATE: 01-30-02
STAINLESS STEEL
DRAWN BY: M.L.S.
WATER FEATURE
SCh: AS NOTED
JOB NO.
9884—
SHEET 5 OF 6
COMPONENT LIST
NO. QTY DESCRIPTION
(� 10 C,H.G. #A10-0854 - #16 GA. S/S FLANGED
ADJ. FOOT INSERT WITH MOUNTING HOLES,
O 2 NAUTILUS 45 FOUNTAIN PUMP
(20 ft. cord)
O 1 NAUTILUS 60 FOUNTAIN PUMP
(20 ft. cord)
i 3'
_2
D II
II
® � 0-o
I
�OA I N (M) 3/4 POLISHED LIMESTONE.
U LEGS 1 5/8'0 X #16 GA. (T-304)
S/S TUBING.
(K srIFNR #18 GA. <T-304> S/S 2B.
(J-HANNEL #18 GA. (T-304) S/S 2B.
rI I (H BAFLE #18 GA. (T-304) S/S 2B.
(G SINK #16 GA. (T-304) S/S 2B.
L F TOWER #16 GA. (T-304) S/S WITH A NO. 4
II BRUSHED SATIN FINISH.
FT
luf (E) TOWER 3/4 HONED GRANITE, OWNER TO
FACE VERIFY LOCATION OF LOGO.
18, _ (D? LID #14 GA. (T-304) S/S 2B.
- (C) BASIN #14 GA. (T-304) S/S 213.
� (B? LEVEL #11 GA. (T-304) S/S 2B.
SECTION i� 1\ (A) REINF'D #11 GA. (T-304) S/S 2B.
j LETTER PART FABRICATION NOTES
1 1/2° = 1'-00 11'6MATERIAL LIST
PROJECT
K L O P P E N B E R G OLYMPIC MEDICAL CAL CENTER SINGLE SIDED DATE 01-30-02
PORT ANGELES, WA. STAINLESS STEEL DRAWN BY: M.L.S.
WATER FEATURE SCALE: AS NOTED
Zen WEST OXFORD PREPARED FDR- HARMONIC ENVIRONMENTS JOB NO.
30 6"�' COLORADO°°"° �UV v eA. sue &W FORT LAUDERDALE FL. HEFT —
SHEET 6 OF e
J
SAP L ZY ZZ hS ZL ZOOZ/ZZ/S
I MEN WOMEN 1
10 O 117 118 I O 01
REM LEG TE
U S BY FOU NN
M GR. TO A(CESS 150�p �
FLOQR SINK, E _ECT R�D� CED PRESSURE
I OUTLETS AND RPBP BACiFIOW PREVENTE4 �
L_J
15000 FLOOR SINK � t FOUNTAIN BY
RECESiED IN CONCRETE OWNER �
SLAB. CENTER WITHIN FOUNTAIN CENTE LINE FOUNTAIN
_ BASE ENCLOSURE.
� ED EQ I
NORTH WAITING
1 � 119
O O
Partial Main Lobby Plan
2. SCALE 1/4"=1'-0"
QL)
OLYMPIC
MEDICAL -CENTER
WW RDA= AM Mff BaItAM AODM
PROJECT NUMBER: 200060771
DESCR�T60t�t COP -20
REfHtE1�CE DRAMgQ AM
DATE 03/20/02
ASK -20.1
i
09900
PAINT (TYP )
GRP L -5Y LZ SZ IL Z002/52/£0
-09255 GWB W/ -EXISTING
09900 PLANT SKYLIGHT
TO
REMAIN
I I�
FOUNTAIN WITH 15000 REDUCED PRESSURE 09950 WALL
GRANITE BASE BACKFLOW PREVENTER COVERING
ENCLOSURE 8Y WITHIN FOUNTAIN END � �
OWNER ENCLOSURE \
i rte .
I !l__J
1 1
15000 FLOOR SINK. CENTER WITHIN /06200
FOUNTAIN END ENCLOSURE. WOOD
-16000 GA OUTLETS BASE
Partial Main Lobbv Elevation
5 SCALE. 1/4"=1'-0"
AA A H L U M
architects
PROJECT NUMBER: 200060771
D SC TK) kES RiP COP -20
RHIRBJCE DRAWNCc A5.1
DATE: 03/20/02
ASK -202
BASEMENT I
BELOW
r
� I
I �
I
"y
I'
1 /2"CIN,• DOWN TO
FOUNTAIN CONNEC
WITH R LM PR
BACITL�ffPI EN
H
`
I , �-TT
(E) 4 WASTE
IN BASEMENT
'I a
I
PATCH OF CONCIVE
SLAB FOR WASTE &
- —VENT INSTALLATION
--_ __ -_
LJ/ -CONNECT 2'b TO (E) --Y - -
2'Y7fV PLUMBING
b _ CHASE
141
f 1/2"CW DOWN Tb
�+ ! I I AUTOMATIC FLOOR
E i j k MAIN WITH TRAP
PRIMER \•
II E 2-1/2- VTR
i,
—iz
II�
r,
L 0c)Ji WUSN
- AA A1V F LO OIC f AR T -I
IA A H L U IA
srciltect•
PLUMBING PLAN
1/4•=1'-0"
o
PROJECT NL QOM- 200060771
DESCRPTKK COP -20
REI Rma DRAWL: P-1
DATE 3-20-02
MSK -20.1
fX:
C
v ;g
N
0 1/2• 1/2'
-5- - - - -
I -�
CEILING t i
(E) 2-VJ i' PROVIDE 1 /2'CW CONCEALE
I
PROVIDE 2" VENT 1
IN WALL AND
BELOW SLAB
� 1
1
1 �
� 1
I
, 1
FIRST FLOOR 1
t
(E) ,w
I�
BASEMENT
3IN
WATER
NIS
IN WALL AND BEHIND WATER PROVIDE 11,L " CW IN I
CONCEALED WALL AND
FEATURE SKIRT TO TRAP
PRIMER do FLOOR DRAIN BEHIND WATER FEATURE ,
ICONNECTION SKIRT I
WATER FEATURE do I
AUTOMATIC TRAP GRANITE SKIRT BY
I PRIMER FOR OTHERS
—\
FLOOR DRAIN I
L_ VALVE
riI
rim
t
PROVIDE WATER TIGHT
SEAL AT FOUNDATION
- PENETRATION
II D—
PVC DRAIN
WITH PVC GATE
SHUT—OFF VALVE
1/2' REDUCED
PRESSURE BACKFLOW
PREVENTERS ROUTE
DRAIN UNE TP D--1
UPiREs &V4/NO/
FEATURE PIPING DIAGRAM
COP -20 WATER FEATLRE MECHANCAL NOTES:
1 THE FOLLOWING NOTES SUPPLEMENT THE CONSTRUCTION DOCUMENTS DATED
JULY 18, 2001
2. VERIFY LOCATION OF WASTE AND WATER CONNECTIONS TO WATER FEATURE
PRIOR TO FABRICATION AND INSTALLATION OF FLOOR DRAIN.
3. FIELD VERIFY LOCATION OF EXISTING SERVICES PRIOR TO FABRICATION AND
INSTALLATION.
4. PROVIDE SAW CUTTING OF FLOOR SLAB FOR INSTALLATION OF WASTE, AND
THAT PORTION OF THE VENT AND TRAP PRIMER THAT IS BELOW THE SLAB.
PROVIDE BACKFILL AND CONCRETE PATCH TO MATCH ADJACENT MATERIALS.
COORDINATE FINISH WITH GENERAL CONTRACTOR.
5. PROVIDE WALL CUTTING AND PATCHING TO PREVENT PIPING FROM EXPOSED IN
OCCUPIED AREAS. COORDINATE FINISHES WITH GENERAL CONTRACTOR.
6. FLOOR DRAIN. D-1 PROVIDE CAST IRON 12 INCH SQUARE WITH 8 INCH SUMP.
ACID RESISTANT ENAMEL INTERIOR, ALUMINUM DOME STAINER. ? NICKEL
BONZE HINGED GRATE, AND TRAP PRIMER WITH % INCH TAP MANUFACTURER:
WADE NO. 9143-6-16, OR APPROVED EQUAL JOSAM OR ZURN.
7 TRAP PRIMERS: MECHANICAL. ADJUSTABLE -TYPE AUTOMATIC TRAP SEAL
VALVE, PRESSURE DIFFEFOM ACTUATED, N INCH MINIMUM SIZE.
MANUFACTURER: E & S VALVE. INC. OR PRECISION PLUMBING PRODUCTS.
8. REDUCED PRESSURE BACKFLOW PREVENTERS: REDUCED PRESSURE TYPE, LINE
PRESSURE OPERATED; STATE AND LOCAL APPROVED; LOW-PRESSURE DROP WITH -
ACCESSORIES AND FITTINGS REQUIRED FOR TESTING BY WATER PURVEYOR OR
AUTHORITY HAVING JURISDICTION; GATE VALVE ON EACH SIDE. SUPPORTED ON
STEEL WALL BRACKETS. MANUFACTURER: AMES. ZURN/WILKINS, WATTS, CLA-
VAL, FEBCO. OR APPROVED.
9. BALL VALVES 2-1/2- AND SMALLER FOR WATER SOME, BRONZE, 2 PIECE BODY
STYLE, FULL PORT. CHROME PLATED SOLID BRASS BALL, TEFLON SEATS,
ADJUSTABLE PACKING, LEVER HANDLE. BLOWOUT PROOF STEM, 150 WSP. 600
WOG. MANUFACTURED APOLLO NO. 77, NIBCO NO. T-585-70. WATTS NO. B6080.
10. SOIL. WASTE AND VENT PIPING BELOW GROUND: ALL SOIL. WASTE AND VENT
PIPING SHALL CONFORM TO THE REQUIREMENTS OF CISPI STANDARD 301. ASTM
A-888 OR ASTM A-74 AND SHALL BE CAST-IRON SOIL PIPE AND FITTINGS.
A. MANUFACTURER: AB&I, CHARLOTTE PIPE OR TYLER PIPE.
B. HUBLESS PIPE AND FITTING JOINTS BELOW GRADE. JOINTS FOR HUBLESS
PIPE AND FITTINGS SHALL CONFORM TO THE REQUIREMENTS OF
ANSI/AWWA C-564 AND FACTORY MUTUAL STANDARD 1680 AND SHALL BE
TYPE 304 STAINLESS STEEL FULL SHIELDED COUPLINGS HAVING 4
C.
D.
E.
M A H
•rcbitccts
SEALING CLAMPS FOR PIPE SIZES 1-1/2" THROUGH 4"
MANUFACTURED ABACI, CHARLOTTE OR TYLER PIPE.
COUPLING
AND SHALL
FREE JOI
NTGASKETS SHALL BE MADE OF ANSI/ANNA C564 NEOPRENE [al
INTERLOCK WITH THE HOUSING ASSEMBLY TO MAKE A SL
TWO -BAND COUPLINGS ARE NOT ACCEPTABLE.
MANUFACTURER: CLAMP -ALL CORPORATION "HIGH TORQUE". ANACO
'HUSKY SERIES 4000" OR APPROVED MISSION.
PROJECT NUMBER: 20 M771
DESCRPTIOht COP -20
REFERENCE DRAWIM P-1
DATE: 3-20-02
MSK -203
03/22/2002 11 15 ET TO 2063819561 LHAN0641 RCV'D(03/22/02 11 15; ;2066245613)
Floor Sinks - Square
9140 (12k 12-8) 1
Cast iron 12" square floor sink with 8" sump, A.R.E. interior,
aluminum dome strainer and nickel bronze, hinged top
NOTE: Seepage flange standard.
ANSI load Class Light Duty (Under 2,00016s.)
Grate Free Area 36.7 Sq. In. (Nickel Bronze)
54.8 Sq. In. (A.R.E.)
141/2
08'Y$
TY -SEAL
2
i
1
J
Page 2 of 2
1193/4
NO -HUB
M
TOTAL P 02
11 J_ Il
PIPE SIZE 1�---
"ADD Y2"
FOR (64), A.R.E. TOP
OP71ONS
FUNNELS
catI•o.
�
5ufxx p
suffix
oesaVw
0 9142
2 47
Q 6 Trap Primer t/2 -in. tap
= 15 Grate
= EF4
4" Dia. NB Funnel
= 9143
O 9144
3 47
4 47
9/2
= 16 /4 Grate
= EF6
E= EG6
6" Dia. N$ Funnel
2-1/2x6" NB Elongated
O 26 Clamp Device
Funnel
OUTLET
O 27 Sediment Bucket
EG8
3-'/2x8-1/4" NB
0 TY
Ty -Seal
(Aluminum)
Q 64 A.R.E.'Cast Iron To p
Elongated Funnel
C7 NH
No -Hub (3", 4")
Q i 79 Security Screws
= IC
Inside Caulk (3", 4")
3-2-98
Tylsr Pipe/Wade Division • P.O. Box 2027 • Tyler, TX 75710-2027• (903) 882.5511 • FAX (888) 879-9233 Floor A C
Sinks 2G J
TOTAL P 02
7
ELECTRICAVDATA
121
DIRECTORS OMCE
128
OFRCE
_ 134
i00M
2-1 F OFFlCE
135
w
CORRIDOR
114
EXISTING
PANEL IA6
MEN WOMEN
CORRIDOR O O l 117FI-18-1 10 O
115
CORRIDOR
116
00 �, Ij �r1 O
2 32 2
(1) NAUTILUS 60 FOUNTAIN L(2) NAUTILUS 45
PUMP & OZONE PUMP FOUNTAIN PUMPS
NORTH WAITING
119
VOLUNTEER DESK
136
FOUNTAIN AREA PLAN
SCALE 1/8" = 1'-0"
CONSTRUCTION NOTES
REMOVE EXISTING SPARE 50A -2P BREAKER AT 1 A6-3234 & REPLACE WITH
(2) 20A -1P CIRCUIT BREAKERS.
COORDINATE RECEPTACLE LOCATIONS WITH MECHANICAL EQUIPMENT
jejopg; 71ON
arckitects OLYi'vIPIC
PROJECT NUMM 2000607.7VM
DISCRPI ole COF-20
MAWM E11
DATE 03/26/02
EW --2111
LOAD SUMMARY - PANEL 1A6
200A, 208Y/120 V., 3 PHASE
OLYMPIC
MED: CAL CENT E:R
kA a
PROJECT NUMOM 2000607.71/1D33
DBO PTU t COP -20
R efa DRAWNG ELI
DATE 03/26/02
ESK--202
CONNECTED
DEMAND
DEMAND LOAD
DESCRIPTION
LOAD -kVA
FACTOR
kVA AMPS
EXISTING LOAD PER RECORD DWGS
62.2
1.00
62.2 173
DELETED LOAD -MAIN LOBBY REMODEL
RECEPTACLE LOAD
-0.5
1.00
-0.5 -1
LIGHTING LOAD
-0.1
1.00
-0.1 0
TOTAL DELETED LOAD
-0.6
-0.6 -2
ADDED LOAD -WATER FOUNTAIN
CKT 1A6-32: PUMPS
1.2
1.00
1.2 3
CKT 1A6-34 PUMPS
1.0
1.00
1.0 3
TOTAL DELETED LOAD
2.2
2.2 6
TOTAL LOAD - PANEL 1A6
63.8
63.8 177
0 208Y/120V
3PH, 4W
OLYMPIC
MED: CAL CENT E:R
kA a
PROJECT NUMOM 2000607.71/1D33
DBO PTU t COP -20
R efa DRAWNG ELI
DATE 03/26/02
ESK--202