ARMOUR UNSDERFER ENGINEERING, INC
13456 SE 27th Pl., Suite. 200
Bellevue, WA 98005 (425) 614-0949 Fax (425) 614-0950
STRUCTURAL CALCULATIONS FOR:
Qwest Port Angeles
Port Angeles, WA 98363
Client:
All
KDW Architects
AUn: Arnold Kraakmo
10202 5th Ave NE, Suite 102
Seattle, WA 98125
By
I E~f>IRES. 2- 23-07
Bill Armour PE, SE
AUE No. 6012
"1'1" ,.-'1
STRUCTURAL CALCULATIONS FOR THE MECHANICAL UNIT DESIGN
OF
QWEST Port Angeles - MECHANICAL UNITS
Port Angeles, Washington
Provide the design and analysIs for the addition of two roof top mechanical Units on raised pedestals
and new openings In the eXisting interior CMU walls No other modifications have been reviewed
Objective
TOPIC:
PAGES:
Index
1
Design & Loading Criteria
2
Wind and Seismic Design
3
Wall Reinforcing Design
4
Existing Slab Support of Mechanical Units
5 to 6
Armour Unsderfer Engineering, 13456 SE 27th PI , Ste 200, Bellevue, WA 98005 (425) 614-0949
Project Qwest Port Angeles Mechanical Units Pg No 1
Address Port Angeles, WA Date 1/18/06
Client KDW Architects Job No 6012
...
"
Design & Loading Criteria:
Iwall Dead Load:
I Root Dead Load:
8" CMU
Insulation
Mtl Panels
Studs @ 16" 0 C
M&E
Mlsc
85.0 pst
0.0 pst
0.0 pst
0.0 pst
0.0 pst
0.0 pst
50.0 pst
28.0 pst
0.0 pst
0.0 pst
0.0 pst
1.0 pst
2.0 pst
81.0 pst
4" Slab
Beams
M&E
Mlsc
ITot
81.0 pst ITot
85.0 pst
USE:
85.0 pst
USE:
ILive Load
ITotal Load =
0.0 pst
81.0 pst
USE: 125.0 pst
275.0 pst
Wind Criteria:
Seismic Criteria:
BasIc Wind Speed (3 sec gust) V 35 =
Wind Exposure B, C, or D ( IBC 2003)
Category I, II, III, or IV (Table 16045 IBC 2003)
Mean Roof Height =
Transversly
Gable Roof (70 < e < 450) Actual Slope (deg ) =
Roof Rise In 12" (Table 1609621(1) IBC 2003)
Longitudinally
Gable Roof (70 < e < 450) Actual Slope (deg ) =
Roof Rise In 12" (Table 1609621(1) IBC 2003)
Short-period Spectral Response, S5 =
One-second Spectral Response, S1 =
Response Modlficatloln Coefficient, R =
Category I, II, III, or IV (Table 16045 IBC 2003)
Site Class, (Table 16151 1 IBC 2003) =
Seismic Use Group (Section 1616 2 I BC 2003) =
Standard-Occupancy Buildings
Height of the BUllldlng, hn =
BUilding Penod CoeffiCient, Cr =
1.46
0.9
5
I
D
85 mph
B Exp.
II Cat.
38 ft
0.00
flat ..
I
38 ft
0.02
00
flat ..
200, Bellevue, WA 98005 (425) 614-0949
Pg No 2
Date 1/18/06
Job No 6012
Armour Unsderfer Engineering, 13456 SE 27th PI , Ste
Project Qwest Port Angeles Mechanical Units
Address Port Angeles, WA
Client KDW Architects
'"
Lateral Loading
IBC Seismic
Ss= 146 Fa= 1 Fv= 16
S1= 09 le= 125
Sms= 146
Sm1= 144 Wall Wgt= 85 psf
Sds= 0973
Sd1= 0960
See procedure IBC 1620.2.7
Fp=O 4*le*Sds*Ww
For Wall
Fp=
Fp=
For General Load:
41 37 psf ~ ultimate ~ Fp= 0 486667 *Welght
2955 psf .-- Allowable -----. Fp= 0347619 *Welght
IFlnal Seismic Force =
30lbs
Allowable design
I
I Method 2 Analytical Proceedure per ASCE 7-02
Top of Wall Height = 38 feet
V= 85 MPH Kd=
Iw: 1 Kz=
Exposure B Kzt=
qz=O 00256*Kz*Kzt*Kd*V^2*1 =
ASCE Wind
085
076
2
23 90 psf
P 76, Table 6-4
p 75, Table 6-3
p 47, Figure 6-4
Per Drawings Wind Load =
N/A
psf
Final Wind Pressures
GCp (Cor)= 140
GCp (Typ)= 1 10
CornerWlnd Pressure =
TYPical Wind Pressures =
-qh*(GCp-GCpl)
P 57, fig 6-11A
GCpl= 018
37.8 psf
30.6 pst
Section 651244
P 49, Fig 6-5
10 pst min.
IFlnal Wind Force =
37.8 Ibs
Armour Unsderfer Engineering, 13456 SE 27th PI ,Ste 200, Bellevue, WA 98005 (425) 614-0949
Project Qwest Port Angeles Mechanical Units Pg No 3
Address Port Angeles, WA Date 1/18/06
Chent KDW Architects Job No 6012
'.
Suppport at end of EXisting Masonry Wall being cut short
Trlbutary= 4 ft
OUT OF PLANE LOAD= 11819 Ibs/ft
Axial Load (PLF)=
o
plf
Uniform load on
stud "1/11'
I Span "L"
Wall Span (FEET)=
14
feet
Support at top with angle on either side, KWlk bolted to Concrete Slab above
USing a 5"x5"x5/16" angle 9" long with (2) 5/8" dla KWlk Bolts, embed 3"
Bending on Angle leg =
236381
Inch-Ib
827 Ibs
"S" Required =
Thickness Required =
o 006583
0066245 Therefore 5/16" IS OK
capacities of 5/8" KWlk Bolts
Tallow= 710 Ibs
Va II ow= 2875 Ibs
Unity = 0 159407 < 1 0 therefore OK
2l
reaction
..
Shear = 827
951bs
Where eXisting CMU wall IS cut short provide 9" long angle
5"x5"x5/16" with (2) 5/8" dla KWlk Bolts embedded 3" Into the
eXisting concrete slab and spaced 6" olc on either side of the wall
The angles should be Installed tight to the eXisting CMU wall but
not attached to It
Armour Unsderfer Engineering, 13456 SE 27th PI ,Ste 200, Bellevue, WA 98005 (425) 614-0949
Project Qwest Port Angeles Mechanical Units Pg No 4
Address Port Angeles, WA Date 1/18/06
Client KDW Architects Job No 6012
-, .
..
,
I~
613 feet
.1
I~ 3 855 feet
.1
4 25 feet
mechanical Unit on
roof
2 feet
~
Unit Wgt=
1200 Ibs
SIDE VIEW
END VIEW
<AM=
491 83 ft-Ibs
Maximum Wind Load on Unit =
9836641008 Ibs
Seismic Load on Unit =
4171428571 Ibs
~ Shear
7
Wind Controls~
Uplift Tension
Load on an Individual post =
245.92 Ibs
Moment on Post =
491 83 ft-Ibs
Try
3" dla Std Pipe
S=
Fb=
Allowable Fb =
172
3431 39 OK
21780
Iuse
3" dla Std Pipe
Try
12"x12"x1/2" base plate
s= 0.50
11,804 OK
27,000
Iuse
Fb=
Allowable Fb=
12"x12"x1/2" base plate
USing 4
Tension IBolt =
Shear/Bolt =
bolts at 7
421 57 Ibs
6148
Inch olc
Capacity of 5/8" dla threaded rods epoxied 3"
Tension = 2405
Shear = 1450
Unity = 022 OK
Use
4
5/8" dla threaded rods epoxied 3" I
Armour Unsderfer Engineering, 13456 SE 27th PI , Ste 200, Bellevue, WA 98005 (425) 614-0949
Project Qwest Port Angeles Mechanical Units Pg No 5
Address Port Angeles, WA Date 1/18/06
Client KDW Architects Job No 6012
, I;
Capacity of Existing Roof Slab
Per the 1947 structural/architectural drawings the 4" cast In place concrete roof slab was designed for
Live Load = 45 psf
Wgt of each Unit =
Dlst weight over footprint of unlt+12" around =
eqUlv uniform load =
1200 Ibs
47 60 sq ft
25 21 psf
OK
EXisting roof slab IS adequate to support Units
24 "
4 "
~ Total wldth= 32 " 1
Effective bearing area of base plate on slab = 7111111 sq ft
Equlv uniform loading = 42 1875 psf < 45 psf OK
Use 1/2" X 24" X 24" base plate under each of
the four pipes supporting the 1200 Ibs
mechanical Units
Armour Unsderfer Engineering, 13456 SE 27th PI ,Ste 200, Bellevue, WA 98005 (425) 614-0949
Project Qwest Port Angeles Mechanical Units Pg No 6
Address Port Angeles, WA Date 1/18/06
Client KDW Architects Job No 6012
"1--"~7 l-EAJIi\lG
D () D .,;'\ ! \tENTILAJING
\ \ D I! ' A,ND
~/) ;~I~.COj\JD!TIONING
----..-' c:QUIP~l/jE;-..J I
NORBY COMPANY
3805 108TH AVE NE, BELLEVUE WA 98004
PHONE 425-828-6636 - FAX 425-828-3982
WESTERN WA 1-800-501-6636
EMAIL.Jonh((unorbvco.com
QWEST
PT. ANGELES, WA
SUBJ\lIITTAL DATA FOR
MCQUAY AIR HANDLER
SPEC. # 15720 2.02
TAG: AHU- 2.1 + 2.2
JVIECH. ENGR: TRES WEST ENGINEERS
TACOMA WA
SOLD TO: QWEST COMMUNICATIONS
SEATTLE, W A
2/28/06
PROVIDED BY: NORBY COMPANY
BELLEVUE W A
STACKED AIR HAi~DLERS PROVIDED WITH 2" DOUBLE WALL
CONSTRUCTION, 30% PRE-FILTERS, 85% FINAL FILTERS (2 SETS), DX
COOLING COIL AND SS DRAIN PAN, INTERNALLY ISOLATED PLENUM
FAN, SPECIAL DISCHARGE PLENUM WITH ISOLATION DAMPERS, 10"
EQUIPMENT BASE RAIL. TWO SINGLE CIRCUIT OUTDOOR CONDENSING
UNITS PROVIDED TO SERVE MATCHING INDOOR COILS.
PROVIDED BY OTHERS:
MOTOR STARTER, DISCONNECT (SPECED IN DIV. 16), J\lIIXING BOX,
DAMPER OPERATORS, CONTROLS, REFRIGERANT, SPECIALTIES (TXV,
ETC.)
Opening X Y Z W(Width) H(Height)
A E:,ll..J.~~llnlet 000 2.00 12.00 70.00 3800
B OX Connection 32.35 81.00 1700 1x1.381ns
C OX Connection 26.10 81.00 48.00 1 x1 63ins
0 Condensate dram conn 3700 76.90 1300 1 25ins. MPS -
[ L11._~~l ~_lU 110.00 L00 000El 78.80 C0 0€l
F Supply Inlet 000 2.00 5400 70.00 38.00
G OX Connection 32.35 81.00 5900 1 x1.381ns
H OX Connection 26.10 81 00 9000 1x1 63ms 20" x 70" TOP DISCHARGE
I Condensate dram conn. 37.00 76.90 55.00 1 25ins. MPS - WITH INTERNAL ISOLATION
J Supply outlet 9400 2.00 94.00 7000 20.00 DAMPERS
Dimensions measured from EEl
22.0
II
o
('\J F
~
II
o
('\J
~
r
22.0
NOTE.
30.0
LtO 0
+
+
+
24.0
1
30.0
40.0
Base 1 O.OOInS deep, Cross members extend 4lns on each side of the Unit.
VIEW'
DRAWN:
JOB NAME.
UNIT TAGGING'
MODEL.
Right Side
February-27 -2006 (20:27)
QWEST PT ANGELES
AHU 2.1 + 2.2 6K CFM
CAH014GDDC
L:.xMcOuCIY"
Air Conllitiening
I Opening X y Z W(Width) H(Height)
IA [,J ,~~vl inlet 000 2.00 12.00 7000 3800
IB OX Connection 32.35 81.00 17.00 1 x1 38ins
C OX Connection 26 10 81 00 4800 1x1.631ns
0 Condensate dram conn. 3700 76.90 13.00 1 25ins. MPS -
E [AI ,......."'l v...lkl I I ZJ.JO L CJ :"C.CC T5 ':;C IC.C':'
F Supply Inlet 0.00 2.00 54.00 7000 38.00
G OX Connection 32.35 81.00 59.00 1 x1.38ms
H OX Connection 26.10 81 00 9000 1 x1 63ms
I Condensate drain conn. 37.00 76.90 5500 1 251ns. MPS -
J Supply outlet 9400 2.00 94.00 7000 20.00
Dimensions measured from EB
20" x 70" TOP DISCHARGE
WITH INTERNAL ISOLATION
DAMPERS
400 30.0 22.0
,~._--_.-_._--------_.....
, ,
, ,
, ,
1 j
I I
! !
i i
1 1
N
:,i
.~
N
<1
I'J
: !
:" !
:~
i"JI
, !
, .
. ,
, ,
....... ~
t__________________J
-----------,
.---1
:",1
I N: I
, ,
, ,
~i
: ,,:
N
~I
:"J
: !
t___________________________-=~J
.----------------.....
, ,
, ,
i 1
1 !
i i
j i
! I
: I
r
+
40.0
+
24.0
NOTE.
H
II
G
I
i
i
l_____
F
o
B
c
i
I II
j
i
!
!
i
i
I
1_____-
o
o
30.0
+
22.0
~
Base 10.00ins deep, Cross members extend 4ms on each side of the Unit.
VIEW:
DRAWN:
JOB NAME.
UNIT TAGGING
MODEL.
Left Side
February-27 -2006 (20:27)
QWEST PT ANGELES
AHU 2.1 + 2.2 6K CFM
CAH014GDDC
x-1McOuay@
y/
Air Conditi.ning
Opening
A C.,I ,uwl Inlet I
B OX Connection
C OX Connection
o Condensate drain conn.
E [,.1.__,:,[ __U~l
F Supply Inlet
G OX Connection
H OX Connection
I Condensate drain conn
J Supply outlet
Dimensions measured from EB
22.0
o
..q-
f'...
F
22.0
NOTE:
x
0.00
3235
2610
3700
11 U 08
0.00
32.35
2610
37.00
9400
y
2.00
81.00
81.00
76.90
:.00
2.00
81.00
81 00
76.90
2.00
Z
1200
1700
48.00
13.00
00.00
5400
59.00
90.00
55.00
9400
W(Width) H(Height)
70.00 38 00
1x1.38ins
1 x1 63ins
1.25ins. MPS -
7000 [8.00
70.00 38 00
1 x1.381ns
1 x1 631ns
1 251ns. MPS -
70.00 20.00
20" x 70" TOP DISCHARGE
WITH INTERNAL ISOLATION
DAMPERS
40.0
30.0
B
40.0
J
240
Base 10.00ins deep, Cross members extend 4ins on each side of the unit.
VIEW:
DRAWN:
JOB NAME.
UNIT TAGGING:
MODEL:
Top
February-27 -2006 (20:27)
QWEST PT ANGELES
AHU 2.1 + 2.2 6K CFM
CAH014GDDC
J-,McOuay"
z
Air Conditionin!r'
VISION AIR HANDLING UNIT TECHNICAL DATA
Date Saved 27/02/2006
JOB NAME 4VD729(XX 001) REP. OFFICE Norby Company
JOB DESCRIPTION QWEST PT ANGELES SALESPERSON LDH
MODEL NUMBER CAH014GDDC ENGINEER TRES WEST ENGINEER
UNIT TAGGING AHU 2.1 + 2 2 6K CFM VERSION 821
Unit configuration Stacked with parallel air flows
Dnve (handing) location Left
LOWER SUPPL Y UPPER SUPPL Y
Air volume 6000 6000 s cfm
Altitude 0 0 ft
Turning loss 0.00 0.00 In WC
External static 1 00 1 00 In WC
Total static 295 2.95 In WC
External H x W 42 x 74 42 x 74 (Not Including base rails) inS
CASING DETAILS
Outer panel Painted standard G60 galv steel
Liner Galvanized steel (Unless noted per section)
Insulation R-13 Injected Foam !unless noted per section)
Frame 2 inS
Base 10" formed channel
Sound baffies None (unless noted per section)
Tread Plate floor liner None (unless noted per section)
11 LOWER COMBINATION FILTER(22 ins) ISECTION
Access Side Face velocity 416
Air volume 6000 cfm Face area 14.4
I PRE-FILTER I FILTER
Type Throwaway (MERV 8) Vancel SH cartndge ( MERV 13 )
Efficiency 35 85
Clean air press. drop 0 27 0 43
Mean air press. drop 0.63 0.81
Dirty air press drop 1 00 1 20
Depth 2.00 1200
I BANK ARRANGEMENT
No. of Filters Size H x W
2 24 00 x 24.00 x 2.00 Ins
1 24.00 x 20 00 x 2.00
2 12.00 x 24 00 x 2.00
I DOOR DATA
Door location Dnve Side Window size None
Door Width 18 Ins Light None
Door opening Outward
I SPECIAL
Extra filters 1 set(s) Pre-filter Intersept Antimicrobial treatment
11
fpm
ft2
%
Ins WC
ins we
InsWC
Ins
Liner
Insulation
(As casing details)
(As casing details)
(AHU 2.1 + 2.2 6K CFM) @ McQuay International 27/02/2006, www mcauaY.com
Page 1 of 5
McQuaY'
1"a-rT.'T'nll loll> .
VISION AIR HANDLING UNIT TECHNICAL DATA Date Saved. 27/02/2006
12 LOWER DIRECT EXPANSION COIL(30 ins) ISECTION 21
COil model 5EN12058 Number of calls 1
Total capacity 181472 Btu/h Number of rows 5
Sensible capacity 166309 Btu/h Fins per Inch 12
Air volume 6000 cfm
Entering db/wb 80.0 1 64.0 F Evaporatmg temp. 47.0 F
Leaving db/wb 54.7 1 53 8 F Refrigerant R22
Finned height x length 33 x 61 ms
Face area 1398 ft2 Refngerant pd 0 ftHD
Face velocity 429 ft/m
COil air pressure drop 049 msWC
Connection type 00 Sweat Fin matenal Aluminum (.0075)
Suction 1 Liquid conn. 1-1 63 1 1-1.38 1 - ins Tube matenal Copper ( 020)
Connection location Dnve side Header matenal Copper
Case matenal Galv steel
Drain pan Stamless steel
Drain pan side Dnve side
Turbosplrals None
COil code 5EN1205B Electro-fin coat None
I DOOR DATA
Door location Removable panels Window size None
Door width 14 ins Light None
Door openmg Outward
13 LOWER FAN SECTION(40 ins) ISECTION 31
Air volume 6000 cfm Motor power 7.5 HP
External static pressure 1 00 il'lsWC Motor type ODP
Total static pressure 295 InsWC Frame size 213 T frame
Electncal supply 200/60/3
Type Plenum Motor effiCiency Premium
Blade type/Class AirFoil 1 2 Motor speed 1750 rpm
Fan wheel diameter 18.25 Ins Motor pole 4
Brake horsepower 535 HP Full load current 4/22.3 A
Operating/Max speed 2393 1 2959 rpm Lock rotor current 185 A
Discharge AXial Motor supplier Genenc
Air modulation None Actual dnve service fac. 1 52
Drain pan None Beanng type Standard - L50 (500K)
Dram pan side Outlet velocity ft/m
Wheel guard PrOVided Inlet screen ProVided
Belt guard ProVided Outlet screen None
Inspection port None
I DRIVES
Fan sheave 3TB38 Motor sheave 3BK57H
Number of belts 3 Belt A60
I ANTI-VIBRATION MOUNTS 1 SPRINGS
Type Spnng
SeismiC restramt With snubbers
I DOOR DATA
Door location Drive side Window size 12 x 12 Ins
Door width 24 ins Light Manne light kit With GFI outlet
Door openmg Outward 115 VOLT REQ'D
I SPECIAL
Extra belts 1 set( s)
Lmer (As casing details)
Insulation (As casing details)
(AHU 2.1 + 2.2 6K CFM) @ McQuay InternatIonal 27/02/2006, www.mcauay com
Page 2 of 5 McOuaY'
1'17-rT:T'n.. I,ll., I
VISION AIR HANDLING UNIT TECHNICAL DATA
Date Saved 27/02/2006
14 LOWER PLENUM SECTION(24 ins) WITH ISOLATION DAMPER
Drain pan None Drain side
Openrn location End upper 0 enlng size
DOOR DATA
Door location
Door width
Door opening
I SPECIAL
Dnve side
20
Outward
Ins
Window size
Light
I SECTION
41
20 00 x 70.00 Ins
None
None
Lmer
Insulation
(As casing detaIls)
(As casmg details)
15 UPPER COMBINATION FIL TER(22 ins) I SECTION
Access Side Face velocity 416
Air volume 6000 cfm Face area 14 4
I PRE-FILTER I FILTER
Type Throwaway (MERV 8) Vancel SH cartndge ( MERV 13 )
Efficiency 35 85
Clean air press. drop 0 27 0 43
Mean air press. drop 0.63 0.81
Dirty air press. drop 1.00 1 20
Depth 200 1200
I SANK ARRANGEMENT
No. of Filters Size H x W
2 24.00 x 24 00 x 2.00 Ins
1 24 00 x 20.00 x 2 00
2 1200x24.00x200
I DOOR DATA
Door location Dnve Side Window size None
Door Width 18 ins Light None
Door opening Outward
I SPECIAL
Extra filters 1 set(s) - Pre-filter Intersept Antimicrobial treatment
Tread Plate floor Imer None
Liner (As casmg details)
Insulation (As casmg details)
51
fpm
ft2
%
insWC
insWC
insWC
ins
16 UPPER DIRECT EXPANSION COIL(30 ins)
Coli model 5EN1205B
Total capacity 181472 Btu/h
Sensible capacity 166309 Btu/h
Number of COils
Number of rows
Fms per Inch
Air volume 6000 cfm
Entenng db/wb 80 0 1 64 0 F Evaporatmg temp.
Leaving db/wb 54 7 1 53 8 F Refngerant
Finned height x length 33 x 61 ms
Face area 13.98 ft2 Refrigerant pd
Face velOCity 429 ft/m
COil air pressure drop 0.49 msWC
Connection type 00 Sweat Fin matenal
Suction 1 Liquid conn 1-1 63 1 1-1 38 1 - Ins Tube material
Connection location Dnve Side Header matenal
Case matenal
COil code 5EN1205B Drain pan
Drain pan Side
I SECTION
61
1
5
12
470
R22
F
o
ftHD
Alummum ( 0075)
Copper (.020)
Copper
Galv. steel
Stainless steel
Drive side
(AHU 2.1 + 2.2 6K CFM) @ McQuay International 27/02/2006, www.mcquaV.com
Page 3 of 5
McQuay'
tr.Jor'T.'T"n, , I" .
VISION AIR HANDLING UNIT TECHNICAL DATA
6 UPPER DIRECT EXPANSION COIL(30 ins)
DOOR DATA
Door location
Door width
Door opening
Date Saved 27/02/2006
ISECTION 6
Removable panels
14
Outward
Ins
Window size
Light
None
None
17 UPPER SUPPLY FAN SECTION(40 ins) ISECTION 71
Air volume 6000 cfm Motor power 7.5 HP
External static pressure 1.00 InsWC Motor type ODP
Total static pressure 2.95 InsWC Frame size 213 T frame
Electrical supply 200/60/3
Type Plenum Motor efficiency Premium
Blade type/Class AirFoil /2 Motor speed 1750 rpm
Fan wheel diameter 1825 ins Motor pole 4
Brake horsepower 5.35 HP Full load current 4 / 22.3 A
Operating/Max speed 2393 / 2959 rpm Lock rotor current 185 A
Discharge AXial Motor supplier Generic
Air modulation None Actual drive service fac. 1 52
Drain pan None Bearing type Standard - L50 (500K)
Drain pan side Outlet velocity fi/m
Wheel guard Provided Inlet screen Provided
Belt guard Provided Outlet screen None
Inspection port None
I DRIVES
Fan sheave 3TB38 Motor sheave 3BK57H
Number of belts 3 Belt A60
I ANTI-VIBRATION MOUNTS / SPRINGS
Type Spring
Seismic restraint With snubbers
I DOOR DATA
Door location Drive side Window size 12 x 12 ins
Door width 24 Ins Light Marine light kit with GFI outlet
Door openrng Outward 115 VOLT POWER REQ'D
I SPECIAL
Extra belts 1 set( s)
Tread Plqte floor liner None
Liner (As casing details)
Insulation (As casing details)
Sound baffles None
Special static pressure - insWC Filter Gauge
IS UPPER PLENUM SECTION(24 ins) WITH ISOLATION DAMPER ISECTION 81
Drain pan None Drain side
Opening location Top Openrng size 20 00 x 70 00 Ins
I DOOR DATA
Door location Drive side Window size None
Door width 20 Ins Light None
Door openrng Outward
I SPECIAL
Tread Plate floor liner None
Liner (As casing details)
Insulation (As casing details)
(AHU 2.1 + 2.2 6K CFM) @ McQuay International 27/02/2006, www.mcquaV.com
Page 4 of 5
McQuaY'
11":I."...,-;'T"n.. "",i .
VISION AIR HANDLING UNIT TECHNICAL DATA
Date Saved 27/02/2006
SHIPPING SECTION DETAILS
Length (inches I Weight ObI
Section 1 22 - LOWER FILTER 380
Section 2 30 - LOWER COIL 722
Section 3 40 - LOWER FAN 959
SectIOn 4 24 - LOWER DISCH PLENUM 295
Section 5 22 - UPPER FILTER 292
Section 6 30 - UPPER COIL 603
Section 7 40 - UPPER FAN 833
Section 8 24 - UPPER DISCH. PLENUM 305
TOTALS 116.00 (Lower level totah 4389 (Entire unit weight)
UNIT SOUND
Radiated
Unit discharge
Unit return
63 Hz
73
88
86
125 Hz
68
86
84
250 Hz
66
87
82
500 Hz
66
90
84
1000 Hz
58
84
73
2000 Hz
50
82
67
4000 Hz
42
77
55
8000 Hz
37
72
49
NOTES
Isolation dampers provided between fan and discharge plenum.
Provided by others in this contract:
Disconnect, starter, refngerant, piping and specialties, damper operators, controls.
(AHU 2.1 + 2.2 6K CFM) @ McQuay International 27/02/2006, www.mcquav com
Page 5 of 5
McQuay"
'tI"2:-!""T:'T"llfl 101101 .
Vision™ Air Handler
Sizes 003 thru 090
c~us. .
MEA
342-99-E
See page 1
Nomenclature
Model
CAH = Custom modular air handler
CAC = Custom modular component
CAH
I
003
Nommal Unit Size
(nominal square foot of coil)
003,004,006,008,010,012,014,017,021,025,
030,035,040,050,065,080,085,090
Vintage of McQuay Air Handling Unit
ARt Certification
e~
~
. -,
Standard & custom size Units certified
In accordance With the central station
air handling units certification program,
which IS based on ARI Standard 430
NOTE: Ratings at other than wide open
pOSition of the inlet vanes are outside
the scope of ARI Standard 430
Agency Listed
c@us
F
o
A C
L Unit Cross Section
C = Standard Unit cross section
M = Custom size cross section
Motor Location
A =Motor along side of fan housing
D =Motor downstream of belt drive plenum fan
F =Motor on Inllne fan
G =Motor downstream of direct drive plenum fan
T =Motor behind twin housed fans
Unit Type/Coil Position
B = Blow-thru cooling cOil location
D = Draw-thru cooling cOil location
H = Heating only
V = Vent only
M = Multlzone
Certified In accordance With the forced
circulation air cooling and air heating
COils certification program, which is
based on ARI Standard 410.
All standard Units
All custom size Units
All Canadian Units
MEA
Contents
Nomenclature ..........................,..,1
The Vision advantage at a glance . . . . , . . , . . . . . ,2
Introduction, . . . . . . . . . . . . . . , . . . , . . , . . . , . . . , .4
Vision's Unique Standard Features ...........,6
Vision's customized options ,........".......8
Component types ".........,........,.....10
Document Number:
342-99-E
Air handler selection ......,."............ 16
Quick select table ...... . . . . . . . . . . . . . . . . . .. 17
^
Application considerations ............ ./. . .. 19
Engineering and physical data .............. 23
.
Dimensional data .............,........... 42
Engineering guide specification ............. 74
Cat 550-3
"VISion" and "SelectTOOLS " are trademarks of McQuay International. All nghts reserved.
@ 2003 McQuay Intematlonal All nghts reserved throughout the world
Bulletin Illustrations cover the general appearance of McQuay International products at the time of
publication We reserve the nght to change design and construction speCifications at any time Without notice
The VISion air handler frame channel deSign IS covered under patent number 5,713,651.
Cat 550-3
The Vision advantage at a glance
Flexibility
Vision's Unique Design
Custom-modular platform
Vanable Dimensioning TM design
Ships assembled or by section
Multiple call, fan and filter selections
Wide selection of base rail heights (4"-12")
Painted cabinet
Indoor air quality
Vision's Unique Design
Low-leakage cabinet construction (capable of less
than 0 5 CFM/ft2 of cabinetry at 5 0" positive w c )
Double sloped microbial-resistant coated galva-
nized (standard) or stainless steel drain pan
Multiple filter types (flat, angular, bag and car-
tndge) With side-load and front-load capabilities
Double-wall construction
Patented splice collar
Easy-to-remove access panels
Hinged access doors With full-gnp handles
What It Does For You
Allows "customizing" of the system With a Wide selection of components
and sizes
Allows cabinet to be sized In two-inch Increments (height and Width) to meet
Installation or aesthetic reqUirements
Minimizes Install time, reduces Installation cost, allows passage through
doors, tight spaces and In elevators (great for retrofit Jobs).
Allows optimum selections for cost, energy effiCiency, performance, Indoor
air quality, and low nOise
Allows for adequate condensate trapping, eliminates need for costly house-
keeping pad Provides space required between condensate connection and
traps on steam applications.
Enhances exterior appearance for Units In vIsible locations
What It Does For You
Minimizes air leakage, nOise and unfiltered air
Inhibits bacterial growth, eliminates standing water that can
support bacteria
Gives full range of filter efficienCies, final filter arrangements, and filter
section depth fleXibility
Prevents fibers from eroding Into the air stream, prevents dirt and mOisture
from penetrating fiberglass Insulation
Prevents unfiltered, unconditioned air from entering the system Allows for
leak-reSistant section to section JOining In the field
Allows for easy Inspection and cleaning of drain pans, promotes
regular Inspections
Allows for proper Inspection
2
Cat 550-3
Operating efficiency
Vision's Unique Design
Low-leakage cabinet design
Patented gasketed frame channels
Energy recovery (plate heat exchanger or
energy recovery wheel)
Fan selection options (housed forward curve or
airfoil, belt drive or direct drive plenum, Inline
and twin fans)
Patented UltraSeal™ low-leak dampers
Solid or perforated double wall liners
Easy, low cost installation
Vision's Unique Design
Ships assembled or by section
Complete disassembly
Patented section splicing
Extended call connectIons wIth gasketed
alrseal, external drains and vents
Bolted frame construction with removable
panels
Fan system factory tested and balanced
Discharge or Inlet plenum sections
What It Does For You
Increases operating efficiency, reduces energy loss and operating costs.
MinimiZeS direct exposure of metal to metal In cabinet framework to
reduce cold bridging and condensate collection, lowers operating costs
Reduces cost of heating or cooling outside air; recovers up to 50% of the
energy normally exhausted from a bUIlding
Results In lowest possible BHP requirements
Maximizes operating efficiency, reduces operating cost
Acts as a barner between Internal and external panels to reduce
condensation and leakage for energy savings
What It Does For You
Minimizes Install time, reduces Installation cost, allows passage through
doors, tight spaces and In elevators (Ideal for retrofit Jobs).
Allows for complete knock down dunng Installation If required for tight fit
applications
Saves Installation time, creates an airtight enVIronment.
Eliminates need to remove panels for connection dUring Installation,
preserves air-tight environment; saves time and cost
ProVides complete accessibility to unit components
Saves time dUring InstallatIOn and promotes proper operation.
Adapts eaSily to ductwork and proVides a turning section for
stacked components.
Vision's Unique Design
Easy maintenance and serviceability
What It Does For You
Easy-to-remove access panels In a Wide range
of section depths
Removable cross-member frame
channels
Extended fan bearing lube lines
Extended COil drain connections
Hinged access doors With full-gnp handles
Makes It fast and easy to clean and Inspect drain pan, clean or remove COil,
clean Interior.
Allows for top or Side COil removal Without disrupting unit Integrity
Makes lubncating fan system easier
Reduces COil venting time, helps COil condensate drain completely
Allows for proper Inspection
Cat 550-3
3
Introduction
Quality
McQuay air handling equipment has been respected and
regarded as a high quality product for nearly 60 years.
McQuay has taken a major step in redefining the indoor
air handler with the VIsion air handler. Demands for
Improved indoor air quality, low sound, high operating effi-
ciency and smaller mechanical rooms require a better
product for today's air handler market. The McQuay VISion
air handler has been designed to meet or exceed these
demands
The key to providing such a high quality product IS In the
basIc design. The McQuay VISion air handler's patented
construction has been designed to provide unequaled
thermal effiCienCies and to be airtight. In addition, VISion
air handlers offer tremendous flexibility in SIZing, compo-
nent options, and unit arrangements to meet the indoor air
quality, operating effiCiency, sound and installation
requirements for today's extensive commercial and cus-
tom markets
Flexibility
By virtue of ItS unique frame design, the McQuay Vision
air handler offers tremendous flexibility ThiS flexibility IS
reflected In our unique Vanable Dlmensloning™ feature
that allows VISion air handlers to be sized In two-inch
Increments (height and width) to fit the available space
Numerous section and component options, and the ability
to arrange components In whatever arrangement
required, allow ViSion air handlers to be customized to the
requirements of each job Without expensive field modlfica-
lions Finally, VISion air handlers can be shipped as a
completely assembled unit, In modules or by component
sections for new or retrofit applications that reqUire
smaller sections for passage through the bUilding
Cabinet .Construction
McQuay VISion air handler cabinetry consists of a box-
type frame channel - the backbone of the Unit - and easy-
to-remove panels or hinged access doors The unique,
patented frame channel deSign allows three Identical
pieces to be bolted together to form a corner of the unit.
Channels are formed of G90 galvanized steel or G60
painted galvanized with factory applied neoprene gasket-
Ing on all flanges to minimiZe leakage. Gasketing IS also
factory applied at all contact surfaces between intenor and
extenor metal components to minimiZe thermal bndging
Panels are secured to the Unit With fasteners that can be
eaSily removed to access the Unit intenor. The frame
channel and panels can be eaSily disassembled and reas-
sembled, giving contractors tremendous fleXibility In
installing and servicing the Units - even where space is
very limited - and saving time and money. Patented splice
JOints help gUide sections together for a tight fit, saving
addilional time and money on installation. Splice JOints are
also fully insulated at the factory.
Patented gasketed frame channel
ThiS unique cabinet deSign results In air tight, thermally
effiCient units, which translates Into energy savings over
the life of the Unit. VISion air handlers are capable of leak-
age rates less than 0 5 CFM per square foot of cabinetry
at 5 0" pOSitive static pressure Units Will not sweat when
exposed to intenor air temperatures down to 50oF, and
extenor room conditions up to 70% relative humidity.
VISion air handlers are available With or without Insulation,
and With Single or double wall construction Double wall
units are available With solid or perforated galvanized and
solid stainless steel liners Fiberglass insulation IS avail-
able In 1- or 2-inch thickness and 1-1/2, or 3 pound per
cubiC foot denSities The thickness of the Insulation IS
never compromised for maximum thermal effiCiency A full
thickness of uncompressed Insulation IS proVided through-
out the unit - including underneath the drain pan.
Base rails are proVided as an option on Unit sizes through
21 square feet and are standard on larger Units. They are
available to meet jobslte height requirements, ranging from
4" to 12" and can eliminate the need for a housekeeping
pad - saving time and money on Installation. A full penme-
ter base rail per shipping section IS factory assembled
"'?::. >>, <- ,
Patented splice joint for section to section joming
4
Cat 550-3
Access and Serviceability
Equipment must be designed to perform efficiently and
withstand the wear and tear of everyday use. It must also
be designed to provide easy access to Intenor compo-
nents for routine maintenance and service to maintain
peak performance The patented frame channels and
easy-to-remove panels or hinged access doors of the
VIsion air handler cabinet provide complete access to the
unit Interior and components Components, including the
fan and cOil assembly, can be removed through the Side of
the Unit, top of the unit, or a combination of both, which
reduces required service clearances. COil removal on
unstacked cOlis does not reqUIre access to the non-con-
nection end of the COIl. A unique COil tie down method sim-
plifies COil removal and replacement
Easy access for routine mamtenance and servIce
Top and SIde panel, frame channel removal for
component replacement
Vision SelectTOOLS ™ Software
Selection Program
Because the McQuay air handler IS so flexible and has
many different component types, there are Virtually an infi-
nite number of unit arrangements pOSSible To help the
customer easily define their product requirements,
McQuay provides a user fnendly selection program, called
the ViSion SelectTOOLS ™ Software Selection Program.
ThiS program configures and sizes both standard and cus-
tom Units. Components can be selected in minutes. ThiS
Windows@ based program Will lead the user through the
selection process by prompting for pertinent Input data for
all components required. Component sections are
selected by plaCing them on a configuration screen. Once
the unit laYDut IS defined, the options and access ones are
Identified The program gives Immediate feedback regard-
Ing fan and COil selection, offenng a chOice of many differ-
ent options based on the performance Inputs Once final
component selections have been made, the program Will
provide all output needed for speCification and submittal
purposes, Including fan curves, COil performance psycho-
metnc charts, weights, dimenSional draWings, and a Unit
speCIficatIon A fully detalled.DXF file IS also available.
The VISion SelectTOOLS Software IS a comprehenSive,
effiCient and user fnendly selection program
Cat 550-3
5
Vision's Unique Standard Features
Patented U1traSeaJTM Low-leak Dampers
. MaXimizes operating efficiency
. Reduces operating cost
Custom Modular Design with
Variable Dimensioning Feature
. Allows custom selection and
confIguration of components
Allows design of system to
meet space and performance
requirements
Rugged Cabinet Enclosure
16- or 18-gauge outer panels
provide rigidity.
G-90 galvanized or painted
finish
Promotes longer unit life
Gasketed Frame Channel
Eliminates metal-to-metal
contact between paneling and
framework
. Minimizes cabinet condensate
and corrosion
. Facilitates top and side
component removal.
. Promotes long life.
'.-'
/t
, '-
Extended Coil Connections
. Save installation costs
. Reduce maintenance time.
. Aid proper drainage
Smooth Interior Surface
. Reduces dirt accumulation
. FacIlitates cleaning
. Improves IAQ.
6
Cat 550-3
~
Frame Channel Disassembly
. Allows two-sided access
. Easier, faster service and maintenance
Patented Splice Collar
Reduces Installation cost
. Creates an air tight
environment
Visible Double-Sloped
Drain Pan
Makes inspection and
cleaning easier
. Improves IAQ
Microbial-resistant
galvanized or optional
stainless steel drain
pan Inhibits bacteria
growth
Variable Height Base Rails (4"-12")
. Eliminates costly housekeeping pad
Allows for adequate condensate trapping
Cat 550-3
7
"
C'\
\
\
t::'''--\/7 hEATIf\;G
D (1 L <\ / VENTILATING
^' \ D 1/' , ,'\ND
\ l I
__~--:::::.//i AIR-CONDlTlOI\IIi"lG
EQUIPMENT
NORBY COMPANY
3805 108TH AVE NE, BELLEVUE WA 98004
PHONE 425-828-6636 -- FAX 425-828-3982
WESTERN WA 1-800-501-6636
EMAIL lonh@norbyco.com
QWEST
PT. ANGELES, WA
SUBMITTAL DATA FOR
MCQUAY AIR COOLED CONDENSING UNIT
TAG: CU-2.1 + 2.2
SPEC. # 15720 2.03
MECH. ENGINEER: TRES WEST ENGINEERS
TACOJVIA, WA
SOLD TO: QWEST COMMUNICATIONS
SEATTLE, WA
r
2/28/06
PROVIDED BY: NORBY COMPANY
BELLEVUE W A
GENERAL NOTES:
AIR COOLED DUAL SCROLL CONDENSING UNIT WITH INTERNAL SAFETY AND
OPERATING CONTROLS, MCQUAY JVIICROTECH II INTERNAL CONTROLS, NON-
FUSED DISCONNECT. ONE YEAR PARTS ONLY WARRANTY + 5 YEAR
COMPRESSOR PARTS WARRANTY, STARTUP, TEST
PROVIDED WITH COATED CONDENSER COILS AS REQUIRED
CD-l.2 MCQUAY MODEL ACZ - 016A
193.1 MBH 16.1 TONS @ 45 SST & 85F OUT DOOR TEMP.
184.8 MBH 15.4 TONS @45 SST & 95F OUTDOOR TEMP.
175.2 MBH 14.6 TONS @ 45 SST & 105F OUT DOOR TEMP.
65 MCA / 80 AMP FUSE @ 208/3/60
14.7 EER, 14.3 IPL V @ ARI CONDITIONS
2 STAGE CAPACITY CONTROL + SPEEDTROL CONDENSER CTL. TO OF
UNIT SHIP WEIGHT = 1200 LB.
BY OTHERS:
EXTERNAL CONTROLS, REFRIGERANT, PIPING AND ACCESSORIES,
VIBRA TION ISOLATION
Physical Data
I MCQUAY MODEL ACZ-016A
208/3/60
Table 25, Physical Data, ACZ 010A through 020A
ACZ MODEL NUMBER '"
013A 016A
1\ 010A
\
\ 1
~ 0 (10 0)
73 \ x 46.3 x
\08
(1869)\< (1176)
x (1~89)
1000 ~54)
1080 (<\10)
220 (99 '()
\
~ ~n\ &~
Nominal Horsepower 4 0 I 4 0 \ 6 0 I 6 0
Oil Charge Per Compressor, Oz (g) 57 (1616) 60 (1701)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESS ~
DISPLACEMENT \
Standard Staging 0 - 50 - 100 I ,- 50 -100 0 - 50 - 100
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH ~TEGRAL SUBCOOLlNG
COil Face Area,Sq Ft (M2) 30 3 (2 8) ~ 3 (2 8) 30 3 (2 8)
Finned Height x Finned Length, In 84 x 52 8\ x 52 84 x 52
Finned Height x Finned Length. (mm) (2134) x (1321) (2134)\< (1321) (2134) x (1321)
Fins Per Inch x Rows Deep 16x2 16\2 16x3
Pumpdown Capacity Ib (kg) 353 (16 0) 353 ('J\l 0) 503 (22 8)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE \
N.umber Of Fans - Fan Diameter, In (mm) 2 - 26 (660) 2 - 26 (6~)
Number Of Motors - HP (kW) 2 - 1 0 (0 75) 2 - 1 0 (0 7\)
Fan And Motor RPM, 60 Hz 1140 1140 \
60 Hz Total Unit Airflow, CFM (lIs) 13950 (6584) 13950 (6584) \
ACZ-A
PHYSICAL DATA
BASIC DATA
Number Of Refngerant Circuits
Unit Operating Charge, R-22, Lb (kg)
1
22 0 (10 0)
73 6 x 46 3 x
508
(1869) x (1176)
x (1289)
1000 (454)
1080 (490)
220 (99 7)
Cabinet Dimensions, LxWxH, In
Cabinet Dimensions, LxWxH, (mm)
Unit Operating Weight, Lbs (kg)
Unit Shipping Weight, Lbs (kg)
Add'l Weight If Copper Finned COils, Lb (kg)
COMPRESSORS
1
240(109)
73 6 x 46 3 x
508
(1869) x (1176)
x (1289)
1220 (554)
1300 (590)
220 (99 7)
Scron
75/75
140 (3969)
2 - 26 (660)
2 - 1 0 (0 75)
1140
12000 (5664)
/
020A
I
1
31 0 (141)1
73 6 x 46 31<
508
(1869) x (11 6) x
(1289)l
1340 (6cJ.)
1420 (6 5)
220 (9 7)
Sc~ n
9 0 /9 0
140 13969)
0- 0-100
3 (2 8)
84 x 52
(234)x(1321)
16 x 3
503 (22 8)
2 - 26 (660)
2 - 1 0 (0 75)
1140
12000 (5664)
40
ACZ 01 OA through 1558
Product Manual ACZ-3
Dimensional Data
I MODEL ACZ 016A 208/3/60
Figure 9, ACZ 010A through 039A
POWER ENTRY
KNOCKOUT
(OTHER SIDE)
POWER
ENTRY
L ~I X
~132
(54153)
4623 (1174 24)
4906 (1246 12)
7355 (1868 17)
CONTROL PANEL
CONTROL \ ACCESS DOORS
ELECTRICAL 51 0
KNOCKOUT I (129540)
SUCTION - Dlf
INLET J
ACCESS DOOR
HOT GAS BYPASS
LIQUID _."' . .',' ,
OUTLET
I-L-::!" ,J) L1
L MOUNTIN 755
} LIFTING SLOTS
394 (100 08)
MOUNTING HOLES
QTY 4 01 00 (25 4)
HOLES
(19177)
ACZ
Unit Size
liquid Conn.
Inches (mm)
7/8 (22 2)
7/8 (22 2)
Suction
Conn
Inches mm
1 1/8 (28 6)
1 5/8 (41 3)
Optional
Hot Gas
Bypass
5/8 (15 8)
5/8 (15 8)
Center of Gravity Inches mm)
x
y
Z
23 (584 2)
23 (5842)
010A, 013A
016A, 01!8l!il"
Figure 10, ACZ 025A - 039A
. I; 4626
POWER ENTRY (117526)
KNOCKOUT _ _ ..
(OTHER SIDE) -
Optional Hot
Gas Bypass
51 (1295)
59 (1499)
5/8(158)
5/8(158)
Product Manual ACZ-3
ACZ 01 OA through 1558
47
Performance Data
I MCQUAY MODEL ACZ-Oi6A
I-P Units
Table 2, ACZ 010A through 039A
ACZ Sat Fan & 800F 850F 950F 1050F 1150F
Unit Suet Control Unit PWR Unit Unit PWR Unit Unit PWR Unit Unit PWR Unit Unit PWR Unit
Size Temp Power Mbh kW, EER Mbh kW, EER Mbh kW, EER Mbh kWI EER Mbh kWI EER
(OF) (kW)
30 18 864 80 109 852 83 102 804 89 90 756 97 78 708 105 68
35 18 960 81 11 8 936 84 11 1 888 91 98 840 98 85 780 106 74
010A 40 18 1056 83 127 1032 86 120 972 92 106 924 100 92 864 108 80
45 18 1152 84 137 1128 87 129 1068 94 11 4 1008 101 100 948 11 0 87
50 18 1260 86 146 1236 89 138 iJc1,7,i 51 i: 9 6" f'1'2.2J:, 1104 103 107 1044 11 2 93
55 18 1368 89 155 1344 92 146 1272 98 130 121 2 106 11 4 1140 11 4 100
30 1 8 111 6 104 107 1080 109 100 1032 11 8 87 972 129 75 912 141 64
35 18 1248 107 11 7 1212 11 1 11 0 1152 121 96 1092 132 83 1020 144 71
40 18 1392 109 127 1356 11 4 11 9 1296 123 105 1224 134 91 1152 147 78
013A 45 18 1548 113 137 1512 117 129 1440 126 114 1356 137 99 1284 150 85
50 18 1704 116 147 1668 120 139 ~158r~;1 f~13:01 ~1203- 151 2 141 107 141 6 153 93
55 18 1872 11 9 157 1836 12.4 148 1752 133 131 1656 144 11 5 1560 157 100
30 1 8 1488 136 109 1452 142 102 1380 155 89 1308 170 77 1236 185 66
35 18 1644 139 11 8 1596 145 11 1 1524 157 97 144 0 172 84 1356 188 72
40 18 1800 141 128 1764 147 120 1680 160 105 1596 175 91 1500 191 78
016A 45 18 1980 144 137 1932 150 129 1848 163 11 3 1752 178 98 1644 194 85
/ ~ 50 18 2172 147 147 2124 153 138 ,20l1' 6, ,'16'61 "'12f!%, 1920 18 1 106 1800 197 91
55 18 2376 151 157 2328 157 148 2208 170 130 2100 185 11 3 1980 201 98
30 18 1788 168 107 1752 175 100 1656 191 86 1560 209 75 1464 227 64
35 18 1968 172 11 5 1920 179 107 1824 195 93 171 6 21 3 81 1608 232 69
40 18 2160 176 123 211 2 183 11 5 1992 200 100 1884 21 8 87 1764 237 75
020A 45 18 2364 180 131 2304 188 123 2184 204 107 2064 222 93 1932 242 80
50 18 2568 185 139 2508 193 130 ,231"6' ,20:9,' ;' 11.4,# 2244 227 99 2112 247 85
55 1 8 2796 190 147 272 4 198 138 2580 21 4 120 2436 233 105 2292 253 9 1
30 27 2328 21 8 107 2280 227 100 2160 247 88 2028 268 76 1896 292 65
35 27 2568 223 11 5 2508 232 108 2376 252 9"4 2244 274 82 2100 298 70
40 27 2820 228 124 2748 238 11 6 261 6 258 101 2460 280 88 2304 304 76
025A 45 27 3084 234 132 301 2 243 124 2856 263 108 2700 286 94 2532 31 1 82
50 27 3372 241 140 3288 250 132 t~11'?iO , t2?:.0, i>':111(6:: 2940 292 101 2760 31 7 87
55 27 3660 247 148 3576 257 139 3396 277 123 3204 299 107 3012 325 93
30 27 2544 243 105 2484 253 98 2352 274 86 2208 298 74 2064 324 64
35 27 2808 249 11 3 2736 259 106 2592 281 92 2436 305 80 2280 331 69
40 27 3072 256 120 3000 266 11 3 2844 288 99 2676 312 86 2508 339 74
028A 45 27 3360 263 128 3276 273 120 3108 295 105 2940 320 92 2748 347 79
50 27 3660 271 135 3576 281 127 :339'6 ~30~3~ H1~2' 3204 328 98 3000 355 84
55 27 3984 279 143 3888 289 134 3684 31 1 11 8 3480 336 103 3264 364 90
30 27 3180 280 11 4 3108 293 106 2952 321 92 2784 351 79 2616 383 68
35 27 3504 288 122 3420 300 11 4 3240 328 99 3060 359 85 2880 392 74
033A 40 27 3840 295 130 3744 308 122 3552 337 106 3360 367 92 3156 401 79
45 27 4188 304 138 4092 31 7 129 3888 345 11 3 3672 377 98 3456 41 1 84
50 27 4560 313 146 4452 326 137 :42'3:9' ~35!5;; ! 11i;9~' 4008 387 104 3768 421 89
55 27 4956 323 153 4836 336 144 4596 365 126 4344 397 109 4080 432 95
30 27 3936 367 107 3840 382 101 3636 41 5 88 3408 450 76 3156 487 65
35 27 4332 377 11 5 4224 393 107 3996 427 94 3744 463 81 3480 501 70
40 27 4740 389 122 4620 405 11 4 4368 439 99 4104 476 8.6 381 6 51 5 74
039A 45 27 5160 401 129 5028 41 8 121 4764 452 105 4476 490 9 1 4176 529 79
50 27 5604 41 5 135 5472 431 127 !S;1Iif:~ 11;fE;;6J: Ilii1l-11tr, 4872 504 97 4536 545 83
55 27 6084 429 142 5928 446 133 5604 481 11 6 5268 520 101 4920 561 88
NOTES:
1 Ratings based on HCFC-22, and sea level altitude
2 Interpolation IS allowed, extrapolation IS not permitted Consult McQuay for performance outside the cataloged ratings
3 KW, and COP are for the entire unrt, including compressors, fan motors and control power.
Product Manual ACZ-3
ACZ 0i0A through 1558
13
Part Load Data
Table 8, ACZ 010A through 155B
Unit % Load Capacity Power EER IPLV Unit % Load Capacity Power EER IPLV
Size Mbh kWI Size Mbh kWI
010A 100 126 86 146 129 100 918 650 141
53 62 52 121 0658 76 694 478 145 144
013A 100 1704 11 6 147 138 50 459 330 139
54 85 64 133 26 235 159 14.8
016A 100 217 147 147 143 100 984 699 14 1
/ 54 109 79 140 70 692 475 146
0708 458 322 142 145
020A 100 257 185 139 142 47
56 132 93 142 24 234 163 144
025A 100 3372 241 140 142 100 1047 770 136
50 156 110 142 72 757 544 139
366 135 0808 50 524 390 134 139
028A 100 271 139
55 187 135 139 22 233 164 142
033A 100 456 31 3 146 151 100 1198 843 142
55 233 153 152 76 905 640 14 1
090B 426 141
039A 100 569 41 5 135 148 50 599 141
56 292 193 151 26 306 223 137
100 437 304 144 100 1316 928 142
030B 76 330 232 142 139 100B 73 964 676 143 142
50 219 157 139 46 599 426 14 1
26 112 85 131 23 306 223 137
100 484 339 143 100 1434 101 3 142
035B 73 355 245 145 141 110B 75 1082 761 142 142
45 219 157 139 50 717 51 1 140
23 112 85 13 1 25 365 259 14 1
100 532 374 142 100 1587 1107 143
040B 76 403 280 144 142 120B 71 1130 829 136 141
50 266 192 139 44 691 469 147
26 137 98 140 19 306 236 130
100 619 42.1 147 100 1792 1286 139
045B 76 468 31 9 147 145 130B 67 1202 874 138 137
50 309 21 5 144 50 896 648 138
26 159 113 140 17 306 236 130
100 683 483 141 100 1967 1423 138
0508 73 501 343 146 144 140B 70 1378 101 1 136 138
45 309 21 5 143 46 896 648 138
23 158 11 3 140 19 365 272 135
100 753 515 146 100 2143 1560 137
055B 76 569 388 147 145 1558 67 1437 1046 137 137
50 376 263 143 50 1071 785 136
26 193 136 142 17 365 272 135
100 836 583 143
0608 73 611 41 1 149 146
45 376 263 143
23 193 136 142
Certified according to ARI Standard 365
Product Manual ACZ-3
ACZ 010A through 1558
19
Sound Data
Table 9, ACZ 010A-155B Sound Pressure
ACZ Unit Octave Band at Center Frequencv Overall
Model 63 125 250 500 1000 2000 4000 8000 A-Weighted
010A 52 52 52 54 48 46 44 42 55
013A 52 52 52 54 48 46 44 42 55
.....::!I 016A 53 54 54 55 48 47 45 42 56
020A 58 56 55 53 52 50 48 48 57
025A 58 57 56 54 52 50 48 48 58
028A 58 58 56 55 52 50 48 48 58
033A 59 59 61 58 54 53 51 50 61
039A 61 62 63 59 55 54 53 51 63
0308 65 64 61 60 56 51 46 41 61
0358 65 64 61 60 56 51 46 41 61
0408 65 64 62 60 56 51 46 41 61
0458 65 64 63 61 57 52 47 42 62
0508 66 65 64 62 58 52 47 42 63
0558 66 66 64 62 58 52 47 42 63
0608 66 66 66 62 59 54 49 44 64
0658 67 66 67 62 59 54 49 44 64
0708 68 67 67 62 60 54 49 44 65
0808 68 68 67 62 60 54 49 44 65
0908 68 68 68 62 60 54 49 44 65
1008 67 65 65 64 62 56 54 54 66
1108 67 66 66 64 62 56 54 54 66
1208 66 68 65 65 62 56 56 55 67
1308 66 69 66 65 62 56 56 55 67
1408 67 68 66 65 62 58 59 56 68
1558 67 69 67 65 62 59 59 56 68
Note Data at
1 30 feet (9m) from side of umt
2 Q=2, umt on a flat roof or ground with no adjacent wall
Table 10, ACZ 010A-155B Sound Power
ACZ Unit Octave Band at Center Frequency (per ARI Standard 370) Overall
Model 63 125 250 500 1000 2000 4000 8000 A-Weighted
010A 79 79 79 81 75 73 71 69 82
013A 79 79 79 81 75 73 71 69 82
~ 016A 80 81 81 82 75 74 72 69 83
020A 85 83 82 80 79 77 75 75 84
025A 85 84 83 81 79 77 75 75 85
028A 85 85 83 82 79 77 75 75 85
033A 86 86 88 85 81 80 78 77 88
039A 88 89 90 86 82 81 80 78 90
0308 92 91 88 87 83 78 73 68 88
0358 92 91 88 87 83 78 73 68 88
0408 92 91 89 87 83 78 73 68 88
0458 92 91 90 88 84 79 74 69 89
0508 93 92 91 89 85 79 74 69 90
0558 93 93 91 89 85 79 74 69 90
0608 93 93 93 89 86 81 76 71 91
0658 94 93 94 89 86 81 76 71 91
0708 95 94 94 89 87 81 76 71 92
0808 95 95 94 89 87 81 76 71 92
0908 95 95 95 89 87 81 76 71 92
1008 94 92 92 91 89 83 81 81 93
1108 94 93 93 91 89 83 81 81 93
1208 93 95 92 92 89 83 83 82 94
1308 93 96 93 92 89 83 83 82 94
1408 94 95 93 92 89 85 86 83 95
1558 94 96 94 92 89 86 86 83 95
20
ACZ 010A through 1558
Product Manual ACZ-3
Electrical Data
MCQUAY MODEL ALP-016A 208/3/60
Table 12, ACZ 010A - 039A, Single Point Electrical Data
Power Supply Field Fuse Size
Minimum Hub (Conduit or HACR (Heating/Air-
ACZ Field Wire Condition lng/Refrigeration)
Unit Volts CircUit Connection) Breaker Size
Size Ampacity Nommal
(MCA) Quantity Wire Quantity Size Recommended Maximum
Gauge In. (mm)
208 42 3 8 1 100 (25) 50 50
230 42 3 8 1 1 00 (25) 50 50
010A
460 22 3 10 1 100 (25) 25 25
575 18 3 10 1 1 00 (25) 20 20
208 54 3 6 1 100 (25) 60 70
230 54 3 6 1 1 00 (25) 60 70
013A
460 26 3 10 1 100 (25) 30 30
575 23 3 10 1 1 00 (25) 30 30
'-. 208 65 3 6 1 100 (25) 80 80
/' 230 65 3 6 1 1 00 (25) 80 80
016A
460 34 3 10 1 1 00 (25) 40 45
575 27 3 10 1 100 (25) 30 35
208 79 3 4 1 1 00 (25) 90 100
230 79 3 4 1 100 (25) 90 100
020A
460 41 3 8 1 100 (25) 45 50
575 33 3 10 1 100 (25) 40 40
208 103 3 2 1 1 25 (32) 125 125
230 103 3 2 1 1 25 (32) 125 125
025A
460 53 3 6 1 100 (25) 60 70
575 45 3 8 1 1 00 (25) 50 60
208 110 3 2 1 125 (32) 125 150
230 110 3 2 1 125 (32) 125 150
028A
460 58 3 6 1 1 00 (25) 70 70
575 48 3 8 1 100 (25) 60 60
208 136 3 1/0 1 150 (38) 150 175
230 136 3 1/0 1 150 (38) 150 175
033A
460 62 3 6 1 1 00 (25) 70 80
575 58 3 6 1 100 (25) 70 70
208 157 3 2/0 1 150 (38) 175 200
230 157 3 2/0 1 1 50 (38) 175 200
039A
460 79 3 3 1 1 00 (25) 90 100
575 75 3 4 1 100 (25) 90 100
NOTE See page 37 for all Electrical Data notes
24
ACZ 010A through 1558
Product Manual ACZ-3
Table 15, ACZ 010A - 039A Compressor and Condenser Fan Motor Amp Draw
Rated Load Amps Locked Rotor Amps
ACZ Compressors No of Compressors
Umt Volts Hz. Fan Fan Fan
Size Motor Mtrs Motor Across- The-Lme
No.1 No.2 (Each) (Each)
No.1 No.2
208 135 135 58 2 237 115 115
230 135 135 58 2 21 4 115 115
010A 60
460 70 70 28 2 107 475 475
575 50 50 30 2 11 5 375 375
208 186 186 58 2 237 156 156
230 186 186 58 2 21 4 156 156
013A 60
460 90 90 28 2 107 75 75
575 74 74 30 2 11 5 54 54
~A 208 237 237 58 2 237 189 189
---- 230 237 237 58 2 21 4 189 189
60
460 125 125 28 2 107 99 99
575 91 91 30 2 11 5 74 74
208 299 299 58 2 237 232 232
230 299 299 58 2 21 4 232 232
020A 60
460 153 153 28 2 107 125 125
575 11 6 11 6 30 2 11 5 100 100
208 336 41 0 58 3 237 278 350
230 336 41 0 58 3 21 4 278 350
025A 60
460 165 21 8 28 3 107 127 158
575 137 173 30 3 11 5 100 125
208 41 0 41 0 58 3 237 350 350
230 41 0 41 0 58 3 21 4 350 350
028A 60
460 21 8 21 8 28 3 107 158 158
575 173 173 30 3 11 5 125 125
208 526 526 58 3 237 425 425
230 526 526 58 3 - 21 4 425 425
033A 60
460 237 237 28 3 107 187 187
575 21 7 217 30 3 11 5 148 148
208 620 620 58 3 237 448 448
230 620 620 58 3 21 4 448 448
039A 60
460 31 0 31 0 28 3 107 225 225
575 290 290 30 3 11 5 180 180
NOTE See page 37 for all Electrical Data notes
Product Manual ACZ-3
ACZ 01 OA through 1558
27
Table 18, ACZ 010A - 039A, Field Wiring Data, Single Point Power
Wiring to Wirmg to
ACZ Standard Power Block Terminal Optional Disconnect SWitch
UNIT Volts Maximum Connector Wire Disconnect Connector Wire Range
SIZE Terminal Range
Amps (Copper Wire Only) Size (Copper Wire Only)
208 175 14 GA - 2/0 100 8 GA - 2/0
230 175 14GA-2/0 100 8 GA - 2/0
010A 14 GA - 2/0 45 14 GA-4 GA
460 175
575 175 14 GA - 2/0 63 14GA-1 GA
208 175 14 GA - 2/0 100 8 GA - 2/0
230 175 14 GA - 2/0 100 8 GA - 2/0
013A 460 175 14 GA - 2/0 45 14 GA - 4 GA
575 175 14 GA -2/0 63 14GA-1 GA
~ 208 175 14 GA - 2/0 100 8 GA - 2/0
;I" 230 175 14GA-2/0 100 8 GA - 2/0
016A 460 175 14 GA -2/0 45 14GA-4GA
575 175 14 GA - 2/0 63 14 GA - 1 GA
208 175 14 GA -2/0 175 6GA - 300 kemll
230 175 14 GA-2/0 175 6GA - 300 kemli
020A 460 175 14 GA - 2/0 45 14 GA-4 GA
575 175 14 GA - 2/0 63 14 GA - 1 GA
208 175 14 GA-2/0 200 6GA - 300 kernll
230 175 14GA-2/0 200 6GA - 300 kernli
025E 460 175 14 GA-2/0 100 8 GA - 2/0
575 175 14GA-2/0 160 8 GA-1/0
208 175 14GA-2/0 200 6GA - 300 kernli
230 175 14GA-2/0 200 6GA - 300 kernli
028A 460 175 14GA-2/0 100 8 GA - 2/0
575 175 14 GA-2/0 160 8 GA-1/0
208 175 14GA-2/0 200 6GA - 300 kernil
230 175 14 GA - 2/0 200 6GA - 300 kernil
033E 460 175 14 GA-2/0 100 8 GA - 2/0
575 175 14 GA - 2/0 160 8 GA - 1/0
208 335 6 GA - 400 kernll NA
230 335 6 GA - 400 kernll NA
039A 175 14 GA - 2/0 6GA - 300 kern II
460 175
575 175 14 GA- 2/0 175 6GA - 300 kernll
NOTE See page 37 for all Electncal Data notes
30
ACZ 01 OA through 1558
Product Manual ACZ-3
Notes for "Electrical Data Single-and Multi-Point" Power:
1. Ulllt wire SIze ampacIty (MCA) is equal to 125% of the largest compressor-motor RLA
plus 100% of RLA of all other loads m the Clrcmt mcludmg the control transformer
2. The control transformer IS furnIshed and no separate l15V power IS reqmred. For both
smgle- and multI-pomt power connectIOns, the control transformer IS m CIrcmt #1 wIth
control power wIred from there to CIrcUit #2. In multI-pomt power, dIsconnectmg
power to CIrcUit WIll dIsconnect all control power to the umt.
3. If a separate 115V power supply is used for the control cIrcuit, then the WIre sizmg
amps IS 10 amps for all ulllt SIzes.
4. Recommended power lead WIre sIzes for 3 conductors per condUit are based on 100%
conductor ampacny m accordance wIth NEC. Voltage drop has not been mc1uded.
Therefore, It is recommended that power leads be kept short. All termmal block
connectIOns must be made with copper (type THW) WIre.
5. "Recommended Fuse Sizes" are selected at approxImately 150% to 175% of the largest
compressor RLA, plus 100% of all other loads m the CIrCUit.
6. "MaXImum Fuse or HACR breaker sIze" is selected at approxImately 225% of the
largest compressor RLA, plus 100% of all other loads in the CIrCUit.
7. The recommended power lead wire SIzes are based on an ambIent temperature of 860F
(300C). Ampacny correctIOn factors must be applIed for other ambient temperatures.
Refer to the NatIOnal Electncal Code Handbook.
8. Must be electncally grounded accordmg to natIOnal and local electrical codes.
Voltage Limitations:
Withm :t 10 percent of nameplate ratmg
Notes for "Compressor and Condenser Fan Amp Draw":
1. Compressor RLA values are for wmng sizmg purposes only but do not reflect normal
operatmg current draw at rated capaCIty
Notes for "Field Wiring Data"
1 ReqUIres a smgle dIsconnect to supply electncal power to the Ulllt. ThIS power supply
must eIther be fused or use an HACR type CIrcmt breaker.
2. All field wmng to unit power block or optIOnal non-fused disconnect SWItch must be
copper.
3. All field WIre SIze values gIVen in table apply to 750C rated wire per NEe.
Product Manual ACZ-3
37
ACZ 01 OA through 1558
Figure 7, ACZ 010 - 039, Typical Single-Point Field Wiring
3 PHASE
POWER
SUPPLY
UNIT MAIN
TERMINAL
,'"'O'"'~' , ~
- -,- ----- +- - - -
i I
--'-~-r----
_ _:_ _____ .L _ _ _ _
I )
DISCONNECT
--111 GND LUG
i
f ~
....~rll
TO COMPRESSOR(S)
AND FAN MOTORS
NOTE ALL FIELD WIRING
TO BE INSTALLED AS NEC
CLASS 1 WIRING SYSTEM
WITH CONDUCTOR RATED
600 VOLTS
.,..r'l;~~
DISCONNECT ~
N _ _ ~Ir'.~'"" I~';- _ ___ _ ( _-".~ __ _ffi';
FUSE ...............
120VAC ---'-r:D~-----2: :~
CONTROL POWER I (BY OTH'ERS) 11: CONTROL
: CIRCUIT
I FUSE
"t LIQUID LINE SOLENOID 2 I
120VAC10AMPMAX I
(~ , :
1--....'('::>-------- I ~'3: -120VAC
"~~~~:~======-t::: I H,"VAC
120VAC 1 OAMPMAX
r---:::-----------l~12 -120VAC
L_---( '-------__ fj N
J - 17
OX EVAP FAN PUMP RELAY
(BY OTHERS)
120 VAC 1 DAMP MAX
FUSED CONTROL
CIRCUIT
TRANSFORMER
ALARM BELL
OPTION
FACTORY SUPPLIED ALARM
FIELD WIRED
,~
~~---
J ALARM BELL RELAY
L_______
r
-------~
I 11 i
-------~ i
J~>/
-120VAC
1
GND
REMOTE STOP
SWITCH
(BY OTHERS)
TIME
_ _ " _ _ -=rc~_ _ _A~O~ ';."F TB2
: ''--------0.:;. "--__J___~
: ______ __ ____..___ __J__ _ jj25
AIR/WATER FLOW SWITCH MANUAL I 35
--MANDATORY- J
(BY OTHERS)
....----S.-----~ f---- ----15
1 ^ NOR OP~N PUMP AUX I 26
1- _ _ _ _ '=' _ _ _ _ _ SSN2-<:!:.S 2P!!O!:!.A!:L _ - _ _ -15
I 36
I
I :22-1 -------
J ~---------
,__________________ ___-1531
I STAGE 1 NOR OPEN CONTACTS I 23
L___________~ t----+4l ~
I I 33 J5.107
j- - - - - - - - -;r:E-;- ~R-;,,;;N~O;,.A~r:;l- - - ~ 28
L___________---j f-----~ @
I 34 J5lD8 I
843
IF REMOTE STOP CONTROL
IS USED REMOVE LEAD 843
FROM TERM 25 TO 35
ALARM BELL
RELAY
----1 f--l
,~OM NO ..J
1e2 ----
ALARM BELL OPTION
DWG. 330539401 REV.OOA
38
ACZ 01 OA through 1558
Product Manual ACZ-3
Air-Cooled Scroll Condensing Units
ACZ 010A-ACZ 1558, Condensing Units
10 to 155 Tons, (35 to 540 kW)
60 Hertz, R-22
PM ACZ-3
Engineered for flexibility and performance. TM
Table of Contents
Introduction.................... ............ ...................... .... ........... ............... 3
Features and Benefits .... ....... ....... ........................... ........................ 4
Design Advantages.... ..... ............ ..... ................. .............. .......... ..... 6
Selection Procedure... ..... ....... ...................................................... 12
Performance Data............. ...... ............. ..... ........... ......................... 13
Part Load Data............... ....... .... ........................... ................ ........ 19
Sound Data............................................................................ ....... 20
Electrical Data....................................................... ....................... 24
Physical Data....................... ....... ........................................ ......... 40
Dimensional Data ................................ ........... ............................. 47
Application Data...................... .................................................... 51
Warranty Statement............................................. .................. ... .... 59
Optional Features......................................................................... 60
Product Specification................................................................... 62
@
~
OUf facility is ISO Certified
Document Number:
PM ACZ-3
September 2002
PM ACZ-2, PMACZl
PM ACR
Issued:
Replaces:
"McQuay" IS a registered trademark of McQuay International
"'2002 McQuay International
"Illustrations and information cover the McQuay International products at the time of publication and we reserve the
nght to make changes In design and construction at anytime without notice"
2
ACZ 01 OA through 1558
Product Manual ACZ-3
Introduction
The ACZ famIly of air-cooled scroll condensing umts offers a wIde selection ofumts
from 10 to 155 tons. The ACZ-A series has capacities from 10 to 39 tons with a
single refrigerant CIrcuit usmg a tandem set of scroll compressors. The ACZ-B
series has capacities from 30 to 155 tons with dual refngerant cirCUIts with eIther
two or three scroll compressors per CIrCUIt.
The ACZ senes of air-cooled scroll condensmg units continues McQuay's legacy of
high quality, hIgh efficiency, latest technology and qUIet operation. These features
make the ACZ family the best overall value in aIr-cooled condensing units available
today.
Efficient Operation
The ACZ umts utIlIze R22 to meet the effiCIency reqUIrements of ASHRAE
90.1-1999. With eIther two or three scroll compressors for each of two
refrIgerant CIrCUIts, excellent part load performance IS achIeved.
Latest Control Technolo2V
These umts have the latest control technology through utilizatIOn of the new
McQuay MIcrotech IJ1M products. Interfacing With your bUIlding automatIOn
system IS easy With Protocol SelectabIlityTM through LonTalk@, BACnet@ or
MODBUS@ standard protocols.
Compact Size
Our reputatIOn for compact deSIgns with small footprints to mlllimize space
reqUIrements contlllues to be a primary feature.
Ouiet Operation
The ACZ units further enhance McQuay's reputatIOn for low operatlllg sound
levels to make these condenslllg umts "neIghborhood fnendly"
Product Manual ACZ-3
ACZ 010A through 1558
3
ACZ-A, Single Circuit, 10 to 39 Tons
Great values also come in small packages. The ACZ-A units have a smgle refrigerant circuit
with capacIties from 10 to 39 tons. Customer benefits include high efficiency operation,
low sound levels, scroll compressor technology and Microtech IrM controls.
High Efficiency Operation
The ACZ-A umts operate at high efficiency with IPLVs up to 14.5 EER. Through the
use of tandem scroll compressors and the latest control technology, excellent part load
performance occurs.
Quiet Operation
ACZ-A umts have low sound ratmgs through the use of scroll compressors. These
compressors are housed m a sheet metal enclosure to further reduce the levels. All
umts have a sound power ratmg of 90 dBA or less.
Superior Control With Microtech IITM
The Microtech IITM controller is provided on the ACZ-A models provIding control
strategIes expected of much larger condensmg umts.
Building Automation System Interface
The Microtech IITM controller allows for easy BAS mterfaces through Protocol
SelectabilityTM using LonTalk, BACnet or MODBUS. This IS another feature
expected of larger condensmg umts.
Product Manual ACZ-3
ACZ 01 OA through 1558
5
Design Advantages
The McQuay ACZ Air-Cooled Condensmg Unit is a product of the McQuay commitment
to offer quiet, relIable, energy efficient eqUIpment. An approach incorporating high quality
compressors, state-of-the-art coil desIgn, and innovative packaging.
Construction
Factory assembled and mounted on a heavy-gauge steel channel base. The base ralls,
supports and cabmetry are powder-coat pamted. The base distnbutes the umt weIght for
roof loadmg. Vaned and convement mstallatlOn IS pOSSIble by VIrtue of the unit's small
footpnnt.
Compressors
Copeland's Compliant ScrolFM tandem or triple compressors are used. These rugged
hermetIC compressors are constructed with an mtegral cast Iron frame, cast Iron scrolls,
three Teflon Impregnated bearings, and three oil filtratlOn deVIces for each compressor.
Using Copeland's ComplIant Scroll tandem compressors proVIdes two, four or SIX steps of
capaCIty modulatIOn depending on model SIze. One compressor can run alone, depending
on the load of the system, resultmg m excellent part-load effiCIency. Each refngerant
CIrcmt has specIally deSIgned 011 and gas equalizatlOn Imes to control 011 rmgratlOn.
The design also offers radIal and aXIal complIance (no tip seals), a large mternal volume for
lIqmd handlIng, a removable suctlOn screen, and a rotary dIrt trap and 011 screen. In
addItion, the compressor IS self-compensating for wear, handles liqmd and debns, and
mherently YIelds the hIghest effiCIency for its class.
ThIS well protected compressor mcludes a solid-state motor protection module, 4 mdIvIdual
motor-wmdmg sensors, a patented internal discharge temperature probe, and a patented
shutdown feature that prevents reverse rotatlOn. An internal dIscharge check valve helps
prevent shutdown nOlse and comes standard WIth hIgh and low pressure taps WIth Schrader
valves, a SIght glass, an 011 level adjustment valve, and an off cycle crankcase heater.
Umts are avmlable in 60 Hertz electncal voltage configuratlOns from 208 to 575 volt
operatmg at 3500 RPM.
Condenser Coils
Condenser coIls have mternally enhanced seamless copper tubes arranged m a staggered
row pattern. The COlIs are mechamcally expanded mto McQuay lanced and nppled
alummum fins WIth full fin collars. A vanety of optlOnal COlI matenal and coatmgs are
available for corrOSIve atmospheres. An mtegral subcooler cIrcmt prOVIdes subcooling to
greatly reduce the pOSSIbilIty of liqmd flashmg The external condenser COlIs are fitted WIth
a protective WIre mesh guard as standard eqmpment.
Condenser Fans and Motors
MultIple dIrect drive dynarmcally balanced propeller fans operate m formed ventun
openmgs at low tip speeds for maXImum efficiency and minimum nOlse and vlbratlOn. A
heavy-gauge vmyl-coated fan guard protects each fan.
Each condenser fan motor IS heavy-duty, 3-phase, Totally Enclosed AIr Over (TEAO) WIth
permanently lubricated ball bearings and inherent overload protectlOn. SpeedTrol option
includes a single-phase motor with fan speed control on the lead fan for each circmt.
Copeland's ComplIant Scroll@ IS a regIstered trademark of the Copeland CorporatIon, Sidney, OhIo
6
ACZ 01 OA through 1558
Product Manual ACZ-3
Figure 1, ACZ-B Condensing Unit Piping Schematic
LIQUID
TUBING
CHARGING
VAlVE
SUCTION
TUSING
SCHRADER
VALVES
./ ~ FIELD GONNEC1l0N
...L . SUCTION UNE
- ---I
I
I
I
I
REMOTE I
/~/PPORATOR Jr
--- --- -bo---- __ ___ __I
~\
I FIELD
I CONNECTION
I HOT GAS
; BYPASS
SCROLL COMPqeSSORS
L1aUID
SHUT..oFF
~'ti~l "
HOT GAS
BYPASS TIJ8lNG
{OPTIONAL) ------:.
I
-----, V
t I
----: ~ -r---h---!
I L----------___i!Ja-_______J!
, SCHRADER SCHRADER I
, VALVE 00 VALVE I
'- - - - - -- - - - -- --- g - - 4- - -~~- - - ~~.L 1t-~~;'ON
FiELD C;JNNECTION
:"IQUID UNE
NOTE A shell-and-tube water chiller IS shown. A wide vanety of evaporator types can be used.
Electrical Control Center
Operatmg and eqUIpment protectIOn controls and motor starting components are separately
housed m a centrally located, weather resIstant control panel with hmged and key locked
doors. In additIOn to the MicroTech IITM controller descnbed m the next sectIOns, the
following components are housed in the panel:
.
Power termmal block, smgle pomt connectIOn standard
Control, mput, and output termInal block
Control transformer
.
.
.
Power connectIOns are per followmg table'
Connection Power Block Disconnect Circuit High Short
Swt Breakers Circuit Current
..---; ~Slngle POint (Standard) Std Opt Std Opt
- .. ~ ,",u - " ^ . '"'-"
~
.
Phase voltage mom tor wIth under/over voltage and phase reversal protectIOn
Fan contactors wIth short CIrCUIt protective deVIces
OptIOnal ground fault protection
.
.
.
The standard FanTrol head pressure control system controls fan stagmg for control of
refrIgerant discharge pressure. The FanTrol system cycles condenser fans based on
discharge pressure and outdoor temperature and IS desIgned for operatIOn down to 350F
(1.70C).
.
Models OIOA through 039Ahave the optional SpeedTrol control usmg both fan cycling
and fan speed control on the lead fan per CIrcuit and allows operatIOn to OOF (-180C)
outdoor temperature. Models 020B through 155B use fan VFD for operation between
350F and OOF (1.70C and -180C).
.
Mechamcal hIgh pressure cutout
Product Manual ACZ-3
7
ACZ 010A through 155B
Control System
The NhcroTech IITM advanced DDC Uillt controller surpasses all other microprocessor-
based umt control systems avaIlable today. ThIS powerful, user-friendly control system
provIdes the flexIbIlIty and performance needed for eIther stand-alone Uillt operation or the
controller can be easIly tIed llltO your BUllding AutomatIOn System of choIce USlllg
McQuay's exclusIve Protocol SelectabllityTM. Protocol SelectabIlItyTM allows you to
choose from open standard protocols such as BACnet@, MODBUS@, and LonTalk@ to
commuillcate easIly wIth the BUllding AutomatIOn System that best meets your facIlIty
reqUlrements. These optional commUillcatIOns modules are aVailable factory lllstalled or
can be easily field mstalled.
MicroTech IITM's state-of-the-art desIgn WIll not only permIt the UnIt to run more efficiently,
but WIll also sImplIfy troubleshootlllg If a system failure occurs. Every MicroTech IITM
controller IS programmed and tested pnor to shipment to help prOVIde a trouble-free start-
up.
Operator-friendly
The MIcroTech IITM menu structure IS separated lllto four dIstinct categones that prOVIde
the operator or serVIce techniCian with a full descriptIOn of current umt status, control
parameters, and alarms Secunty protectIOn helps prevent unauthonzed changlllg of the
setpolllts and control parameters.
MicroTech IITM continuously performs self-diagnostIc checks, momtonng system
temperatures, pressures and protection devices, and It will automatically shutdown a
compressor, a refngerant ClrcUlt or the entire Uillt If a fault occurs. The cause of the
shutdown will be retained m memory and can be easIly displayed m plain EnglIsh or metrIC
UnIts for operator review. The MlcroTech IITM UnIt controller can also retalll and display
the time the fault occurred and the operatlllg conditIOns that were present at the tIme of the
fault, whIch IS an extremely useful feahIre for troubleshootlllg. In additIOn to dlsplaYlllg
alarm diagnostIcs, the NhcroTech IITM controller also prOVIdes the operator with a wamlllg
of pre-alarm condItIOns. Alarm notIficatIOn data can also be passed to your BAS through
an optIOnal commUnICatIOns module.
Staging
Temperature control for the evaporator IS prOVided by the lllstaller through a field supplied
temperature controller. The field supplIed staglllg SIgnals are provided to the Microtech II
controller WhICh correspondmgly activates and deactIvates the scroll compressors. The
temperature controller IS reqUlred to close normally-open 24 volt contacts on a demand for
coolmg. These closure SIgnals are field WIred to the terminal stnp (TB2) m the condensmg
uml. Refer to the typical field wiring dIagram for details. The followmg control staging is
required:
CondenSing Unit Model
ACZ-01 OA thrau h 039A
ACZ-030B thrau h 110B
ACZ-120B throu h 155B
Number of
Capaclt Ste S
2
4
6
Number of ReqUIred
Contact Closure Si nals
2
4
6
Lead/lag is automatIC and switched based on operatlllg hours and compressor starts.
8
ACZ G10A through 155B
Product Manual ACZ-3
Building Automation System (BAS) Interface
The followmg BAS standard protocols are supported through McQuay's Protocol
SelectabIhtyTM option:
· BACnet/IP@
· BACnet MS/TP@
· BACnet Ethernet@
· LonTalk@
· MODBUS@
The following functlOns are generally aVaIlable depending on the applicatlOn and protocol
muse:
· Enable/disable operatlOn
· Select operatmg mode
· Set the network hmIt vanable
· Read all digItal and analog mputs and outputs
· Read operatmg mode and status
· Send a descnptlOn of each alarm when It occurs
Keypad/Display
A 4-hne by-20 character/lme hqmd crystal dIsplay and 6-key keypad IS mounted on the umt
controller Its layout IS shown below. .
Figure 2, Micro Tech J/TM Keypad
The four arrow buttons (UP, DOWN, LEFT, RIGHT) have three modes of use.
· Scroll between data screens as mdIcated by the arrows (default mode).
· Select a speCIfic data screen III a hIerarchIcal fashIOn usmg dynamIC labels on the nght SIde of the
display (thIS mode IS entered by pressmg the MENU button).
· Change field values in edit mode.
10
ACZ 010A through 1558
Product Manual ACZ-3
Product Specification
SpecificatIOns are aVailable m MSWord format. Contact the local McQuay sales office.
SECTION 15XXX
AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS
ACZ 010A-ACZ 155B
PART 1 - GENERAL
101 SUMMARY
SectIon lllcludes deSIgn, performance cntena, refngerants, controls, and mstallatlOn
reqUIrements for aIr-cooled scroll compressor condensmg umts
1 02 REFERENCES
Comply WIth applicable Standards/Codes of ARI 365-94, ANSI/ASHRAE 15, ETL, cETL,
NEC, and OSHA as adopted by the State
Umts shall meet the efficIency standards of ASHRAE Standard 90 1, October 2001.
1 03 SUB MITT ALS
A. SubmIt shop drawmgs and product data m accordance WIth the specIficatIOns.
B. SubmIttals shall mclude the followmg.
1. DImensIOned plan and elevatIOn VIew drawmgs, reqUIred clearances, and
locatIOn of all field connectIOns
2. Summary of all auxIlIary utIlIty reqUIrements, such as electncIty, water,
compressed air, etc Summary shall mdIcate qualIty and quantIty of each
reqUIred utIlIty
3 Smgle-lme schematIc drawmg of the power field hookup reqUIrements,
mdIcatmg all Items that are furnIshed.
4. SchematIc dIagram of control system mdIcatmg pomts for field
mterface/connectIon.
5 DIagram shall fully delmeate field and factory wmng.
6. InstallatIOn manuals.
1 04 QUALITY ASSURANCE
A QualIficatIOns EqUIpment manufacturer must speCIalIze m the manufacture of the
type of products specIfied and have five years expenence with sImIlar eqUIpment
and refrIgerant offered.
B Regulatory ReqUIrements: Comply WIth the codes and standards specIfied.
C Manufacturer's plant must be ISO RegIstered.
62
ACZ 010A through 1558
Product Manual ACZ-3
Equipment Protection
The unit IS protected ill two ways: (1) by alarms that shut the umt down and reqUlre manual
reset to restore umt operatlOn and (2) by hmlt alarms that reduce umt operatlOn III response
to some out-of-lill1lt condItIOn. Shut down alarms can activate a remote alarm sIgnal. Lmllt
alarms activate a sIgnal on the controller.
Shutdown Alarms
. HIgh condenser pressure
· Motor protectlOn system
· Phase voltage protectIOn (OptlOnal on ACZ-B only)
· OutsIde ambIent temperature
. Sensor failures
Limit Alarms
· Condenser pressure stage down, unloads umt at hIgh discharge pressures
· Low ambient lockout, shuts off unit at low ambIent temperatures
· Low evaporator pressure hold, holds stage # 1 untIl pressure rIses
· Low evaporator pressure unload, shuts off stage #2
Unit Enable Selection
· Enables umt operatlOn from eIther local keypad, dIgItal mput, or BAS
Unit Mode Selection
· Selects standard cooling, or test operatlOn mode
Digital Inputs
. Dmt off SWItch
· Remote start/stop
. Flow SWItch
Digital Outputs
· Shutdown alarm; field wIred, activates on an alarm condItlOn, off when alarm is
cleared
· Evaporator pump or air handler fan motor; field wIred, starts when umt IS set to
start
Condenser fan control
The MicroTech .IITM controller prOVIdes control of condenser fans. The controller stages
condenser fans based on dIscharge pressure.
Product Manual ACZ-3
9
ACZ 01 OA through 1558
1.05 DELIVERY AND HANDLING
A. Condensing UnIts shall be delivered to the Job site assembled and charged with a
holdmg charge of refngerant and full Oil charge by the manufacturer.
B Comply with the manufacturer's mstructlons for nggmg and handlmg eqUipment
1 06 WARRANTY
The refngeratlOn eqUipment manufacturer's guarantee shall be for a penod of one year from
date of eqUipment start-up but not more than 18 months from shipment. The guarantee shall
provIde for repair or replacement due to failure by matenal and workmanshIp that prove
defective wIthm the above penod, exciudmg refrigerant.
107 MAlNTENANCE
Mamtenance of the UnIts shall be the responsibility of the owner and performed III
accordance WIth the manufacturer's mstructlOns.
PART 2--PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. McQuay InternatIOnal
B (Approved Equal)
2.02 UNIT DESCRIPTION
Provide and Install as shown on the plans factory-assembled, air-cooled scroll compressor
condensmg umts III the SIze and quantity speCified. Each UnIt shall consist of hermetiC
tandem or tnple scroll compressor sets, air-cooled condenser sectIOn, control system and all
components necessary for controlled umt operatIOn when field piped and Wired to low SIde
eqUipment speCified elsewhere
2.03 DESIGN REQUIREMENTS
A. General: PrOVIde a complete scroll-compressor condensmg umt as speCIfied herem
and as shown on the drawmgs The UnIt shall be m accordance WIth the standards
referenced m sectIOn I 02 and any local codes m effect.
B Performance. Refer to the schedule of performance on the draWIngs. The UnIt shall
be capable of stable operatIOn to a mInImUm of SO percent of full load Without hot
gas bypass Performance shall be in accordance With ARI Standard 365-94.
C. Acoustics. Sound pressure levels for the UnIt shall not exceed the followlllg
speCified levels. The manufacturer shall proVIde the necessary sound treatment to
meet these levels If reqUired. Sound data shall be proVIded WIth the quotatIOn. Test
shall be in accordance With ARI Standard 370
Product Manual ACZ-3
63
ACZ 01 OA through 1558
Octave Band
63
125
250
500
1000
2000
4000
8000
dBA
2.04 CONDENSING UNIT COMPONENTS
A. Compressors' The compressors shall be sealed hermetIc scroll type Wlth crankcase
MINIMUM TWO COMPRESSORS
REQUIRED
OIl heater and suctIon stramer Compressor shall have a forced-feed lubncatIOn
system with a reversIble 011 pump and 011 charge The compressor motor shall be
refngerant gas cooled, hIgh torque, hermetIc mductlon type, two-pole, wIth Inherent
thermal protectIOn on all three phases and shall be mounted on RlS vIbratIOn
Isolator pads
B Condenser The condenser coIls shall consIst of 3/8 mch (lOmm) seamless copper
tubes mechalllcally bonded into plate-type fins The fins shall have full drawn
collars to completely cover the rubes. A subcoolmg coIl shall be an Integral part of
the mam condenser coIl Condenser fans shall be propeller type arranged for
vertIcal aIr dIscharge and mdlvldually dnven by dlrect-dnve fan motors. They shall
be eqUIpped WIth a heavy-gauge fan guard. Fan motors shall be TEAO, three-
phase, dIrect-drIve, 1140 rpm
D RefrIgerant CircUIt. Capped connectIOns shall be provIded for field connectIOn of
refngerant plpmg. Refngerant speCIalties shall be field supplIed and mstalled.
E Control System A centrally located weatherproof control panel shall contam the
field power connectIOn pomts, controlmterlock termmals, and control system
Power and startmg components shall mclude factory short CIrcUIt protection of fan
motors and control CIrcUIt, IndIVIdual contactors for each fan motor, solId-state
compressor three-phase motor overload protectIOn, Inherent fan motor overload
protectIOn and Ulllt power connectIOns for connectIOn to remote dIsconnect SWItch
Termmals shall also be provIded for power supply to the evaporator heater CIrcUIt.
Hmged access doors shall be tool-lockable. Barner panels or separate doors are
reqUIred to protect agamst accIdental contact WIth lIne voltage when accessmg the
control system
F An advanced DDC mIcroprocessor Ulllt controller WIth a 4-lme by 20-character
lIqUId crystal dIsplay provIdes the operatmg and protectIon functions. The
controller shall be capable ofrecelvmg a 4 to 20 mA SIgnal for temperarure reset
and be remotely enabled WIth a dIgItal Input. The controller shall take pre-emptIve
IImltmg actIon In case of hIgh dIscharge pressure or low evaporator pressure
The controller shall contam the following features as a mlmmum.
EqUIpment ProtectIOn
The umt shall be protected in two ways: (l) by alarms that shut the Ulllt down
and reqUIre manual reset to restore umt operatIOn and (2) by limIt alarms that
64
ACZ 010A through 1558
Product Manual ACZ-3
reduce Ulllt operatIOn m response to some out-of-lImIt conditIOn. Shut down
alarms shall activate an alarm signal.
Shutdown Alarms
.. Low evaporator pressure
.. High condenser pressure
.. Motor protectIOn system
o Phase voltage protectIOn (OptIOnal)
.. OutsIde ambient temperature
.. Sensor failures
LImit Alarms
.. Condenser pressure stage down, unloads at high discharge pressures
o Low ambient lockout, shuts off unit at low ambient temperatures
.. Low evaporator pressure hold, holds stage #1 untIl pressure rIses
o Low evaporator pressure unload, shuts off one compressor
Umt Enable SelectIOn
Enables UllIt operatIOn from eIther local keypad, digItal mput, or BAS
Umt Mode SelectIOn
Selects standard coolIng or test operatIOn mode
DIgItal Inputs
.. Umt off sWitch
.. Remote start/stop
o Motor protection
Digital Outputs
.. Shutdown alarm, field WIred, activates on an alarm conditIOn, off
when alarm IS cleared
Condenser fan control
The UllIt controller shall proVIde control of condenser fans based on
compressor dIscharge pressure.
BUlldlllg AutomatIon Svstem (BAS) Interface
The followmg BAS protocols shall be supported.
.. BACnet@
.. LONMARK@
.. MODBUS
2 05 OPTIONS AND ACCESSORIES
The followlllg optIOns are to be mcluded:
11<::,1 o~~ ~J 1-'............. l.:.. .....11..... n ,.uul vl:'.....u...Lvu L.... 1 S J:-I......f..........uL v[ [".Jl L..H...d
.. Low ambient head pressure control to oaF (-17 8aC)
co Non-fused disconnect sWitch WIth through-the-door handle
.. Alumlllum fins shall be pre-coated WIth a phenolIc epoxy coatmg With 1000 hour salt
spray ratlllg (ASTM B 117 -90
C!l\!lfH!l Mil Dz-ud.;uuv" .;(,.Is
:;:",,:, 6.1."H~TH ~....l,.......J .....pVi...) .....VU.L.u5 t"LV Y .I.du..l.o :888 I L.vu-J.. .;u.ll U.t!L""] J.~oJJ."tu.J.J.""""" (..L\..8T~11
D 117 98) u.ud .1.0,) ufJt'l:",d Lv bvLl.1 MJ."-' \"lUll u.J..1d lL.v \,tv11 fluu.l\"lv
J1-'J.HJ.5 Y.lD..."",L.vu .Luvlu.tv.l.u fvJ. .D.""ld .1A..1>.JLulluLJ.vu.
RttBB!!1 m JhtlU . i:.....AHllll.;;,LtlllJ f.:." fidel wul..JI..,lwll
Product Manual ACZ-3
ACZ 010A through 1558
65
.
..
· It.,,] ~"d "."d b~~ltlJ 5 YEAR COMPRESSOR PARTS WARRANTY PROVIDED
Ihgh Jl15lt OlrOMlc OMlHut pr0tBohall
PART 3 - EXECUTION
301 INSTALLATION
A. Install m stnct accordance wIth manufacturer's reqUIrements, shop drawmgs, and
contract documents.
B Adjust and level umt m alIgnment on supports.
C Coordmate electncal mstallatIOn WIth electncal contractor
D Coordinate controls WIth control contractor
E ProVIde all appurtenances reqUIred for a fully operatIOnal and functIOnal umt
302 START-UP
A Install proper charge of refngerant and 011.
B ProVIde testmg and startmg of machme, and mstruct the Owner m Its proper
operatIOn and mamtenance.
66
ACZ 010A through 1558
Product Manual ACZ-3