Loading...
HomeMy WebLinkAbout2370ORDINANCE NO. A 77 70 AN ORDINANCE of the City of Port angeles regulating the use of electric current and amending Section 1 of Ordinance 2327 and Sections 14.12.100, 14.12.110, and 14.12.120 of Ordinance 2325 and of the Port Angeles Municipal Code. BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF PORT ANGELES as follows: Section 1. Section 1 of Ordinance 2327 and Section 14.12.100 of Ordinance 2325 and of the Port Angeles Municipal Code are hereby amended to read as follows: 14.12.100 Regulatory Provisions. A. 1. Woodworking Plants. The production areas of saw mills and commercial and industrial woodworking plants shall be wired in rigid metal conduit, intermediate metal conduit, M.I. cable, MC cable, or, if not subject to mechanical injury or vibration, E.M.T. with compression ring fittings. 2. The following premises shall be wired with rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, liquid -tight flexible metal conduit, or MI cable: (a) Portions of dairies, laundries, car washes and other locations which are subject to continuous moisture. See Section 300 -6 of the NEC. (b) Portions of docks, piers and wharfs which are subject to continuous moisture. (c) Premises designated elsewhere in this Chapter. 3. The following premises shall be wired with metal raceways, busways, MC, MI cable, or rigid nonmetallic conduit encased in not less than two (2) inches of concrete: (a) All institutional, educational and health care occupancies as defined in Articles 517 and 518 of the NEC. Exception No. 1: For signal and control circuits, open cable wiring approved for the purpose shall be -1- permitted for Class 2 signal and control circuits as defined in Article 725 of the National Electrical Code for other than the following circuits and /or systems: nurse call systems, fire alarm systems actuated at manual stations, electric water flow alarm devices in connection with sprinkler systems, automatic fire or smoke or products of combustion devices, alarms required for systems used in the piping of nonflammable medical gases, and communications systems used for issuing instructions during emergency conditions. Exception No. 2: Open cable wiring approved for the purpose of NFPA Bulletin No. 71 shall be permitted for Central Station Protective Systems installed and operator- manned and supervised in accordance with the latest adopted edition of the National Fire Protection Association Bulletin No. 71 in other than hospitals and nursing homes. Exception No. 3: Single -story boarding homes having direct grade entrance and egress, and alcohol treatment facilities (other than detoxification facilities) licensed for less than 10 residents by the Department of Social and Health Services. Exception No. 4: Unlicensed health care facilities except in patient care areas. (b) All premises in Fire Zone #1 as defined in Section 14.24.010(A) PAMC. 4. The following premises shall be wired with metal raceways, busways, cable trays, SNM, TC, MC, MI cable, or rigid nonmetallic conduit encased in not less than two (2) inches of concrete: (a) Industrial plants. Industrial plants, except that open conductors of No. 4/0 or larger size may be installed on insulators not less than 20 feet above floor or working sur- face level in accordance with Article 320 of the National Elec- trical Code. -2- • Exception No. 1: For signal and control cir- cuits, other than those defined as Class 1 circuits per National Electrical Code, Sections 725 -3(a) and 725 -4, open cable wiring approved for the purpose shall be permitted for Class 2 signal and control circuits installed in accordance with Article 725 of the National Electrical Code. Exception No. 2: Open cable wiring approved for the purpose (NFPA Bulletin No. 71) shall be permitted for Central Station Protective Systems installed and operator- manned and supervised in accordance with the latest adopted edition of the National Fire Protection Association Bulletin No. 71. Exception No. 3: Rigid nonmetallic conduit may be installed in areas outlined in National Electrical Code Section 300 -6. (b) Multifamily Occupancy Buildings. Feeder and Sub - feeders in such buildings (i.e., apartment buildings, hotels, motels and dormitories) of two or more stories, not including basement, shall be wired in a raceway(s). (c) High Rise Buildings. 5. Within buildings, all mains, sub - feeders, circuits exceeding 300 volts between conductors, and circuits exceeding 150 volts to ground shall be installed in approved raceways. 6. Rigid Non - Metallic conduit installed underground for services shall have rigid conduit steel ells. 7. All wiring in unused spaces underneath buildings shall be installed in rigid metal conduit, electrical metallic tubing, flexible metal conduit or other approved raceways, except where provided in Articles 336 and 339 of the NEC for dwelling occupancies. 8. On an addition or rewire of an existing commercial facility, all wiring that is newly installed, rerouted, or in any other way modified, as determined by the Electrical Inspector, will meet the requirements of this Chapter. -3- • • 9. When 65% of the existing electrical facilities have been or are expected to be modified, as determined by the Electrical Inspector, the entire electrical wiring facilities of the commercial establishment's service shall meet the require- ments of this Chapter. 10. An exception shall be granted by the Electrical Inspector to this section not not to the NEC or WAC, in the event that the commercial facility is determined to an historic site or qualified for historic preservation, as determined by the State Historical Preservation Officer. 11. On rewires or additions to non - commercial facili- ties for which all permissions and permits have been obtained for conversion to a commercial use, the same criteria will apply as if the facility were originally of commercial use. 12. All dwellings under 1,000 square feet shall be served with not less than a 125 amp service. All dwellings equal to or over 1,000 square feet shall be served with not less than a 200 amp service. 13. The following types of building occupancies, as defined in the Uniform Building Code as adopted by Ordinance No. 2318 as now or hereafter amended, shall be wired with metallic raceways, busways, MC cable, MI cable, or rigid non - metallic conduit encased in not less than two (2) inches of concrete: (a) Group A, Group E, Group H, Group I. (b) Group B, Divisions 1, 3 and 4. (c) Group B, Division 2, using type V -N construc- tion and over 3,000 square feet in area. B. The connections for electric meters shall be so located that meters will be readily accessible at all times. Meters shall not be permitted inside buildings or within carports or porches without special approval of the Office of the Electrical Inspector. -4- • C. For all motors, other than portable motors, located in industrial or manufacturing establishments, such as mills, ware- houses, foundries, mercantile and similar establishments, such as grocery stores and butcher shops, factories and machine shops, the wiring method employed shall be only rigid conduit. Elec- trical metal tubing or flexible metal conduit may be used, pro- vided that it is not exposed to mechanical injury, or as per- mitted in Section 400.4 of the National Electrical Code. D. All kitchens, bathrooms, toilet rooms, laundry rooms and similar locations containing plumbing fixtures, shall have a separate wall switch for lighting fixtures. No pull chains shall be permitted. E. Concealing work during construction prohibited - removal authorized. It shall be unlawful for any owner, contrac- tor, or other person to do or to permit to be done any work of any kind whatsoever which will cover or conceal in any way elec- trical wiring or equipment until the same has passed inspection. Electrical Inspector shall have the authority to remove, or order the removal of, any construction which makes it impossible to make a careful inspection of any electrical equipment. Section 2. Section 14.12.110 of Ordinance 2325 and of the Port Angeles Municipal Code are each amended to read as follows: 14.12.110 Wiring and Circuit Specifications - New Work. The following specifications shall apply for all new wiring and circuit installations governed by this Chapter: A. All new service panels shall have at least four full sized spaces for future circuits, after wiring is complete. B. Except for large load center installations, all service equipment, including switches, gutters and subfeed switches, shall be mounted no more than 6 feet to center of breakers or fuses, nor less than 3 feet from the floor or permanent working platform. -5- C. Underground water pipes shall not be laid in the same trench with an electrical service wire unless: 1. A minimum horizontal separation of 3 feet is maintained at all points along the line; or 2. All electrical wires are enclosed within a rigid metal conduit, or Schedule 80 rigid non - metallic conduit. D. Where water service pipes cross electrical service wires, a minimum vertical separation of 1 foot shall be main- tained. E. Underground service conductors used in a direct burial installation shall be of 200 amp minimum capacity. F. Service ampacity in multi - family residences shall have a minimum rating of 100 amps per apartment. G. The smallest wire sizes permitted are: 1. In commercial installations, No. 12 American Wire Gauge copper; except for control wiring and voltages of 24 or less. 2. In residential installations, No. 14 American Wire Gauge copper. 3. In all installations, no aluminum wire smaller than No. 8 American Wire Gauge may be used. H. Where more than one electric meter is used on a building, all meters must be identified by plainly showing the apartment number or occupancy on each meter base. I. The equipment grounding conductor and bond conductor shall be copper only. Aluminum shall be prohibited. J. Residential occupancies, ground fault circuit interrupters. In addition to complying with Article 210 -8, National Electrical Code, Ground Fault Circuit Interrupters, shall be on separate circuits in each bathroom. K. Workmanship. All electrical wiring and equipment shall be installed in a neat, workmanlike manner. Where applic- able, non - metallic sheath cables shall follow the lines of the -6- building and be fastened to building structures. Unnecessary, or unnecessarily complicated wiring shall be avoided. See National Electrical Code, Article 110. Section 3. Section 14.12.120 of Ordinance 2325 and of the Port Angeles Municipal Code are each amended to read as follows: 14.12.120 - Installers' License and Other Requirements. A. Any person engaging in electrical work in the City shall have a valid and current license to do so issued by the State, provided that no license or certification shall be required for: 1. Persons doing electrical work on their own resi- dences, or farm, or place of business, or on other property owned by the person; or 2. Regularly employed, competent, electrical mainten- ance employees doing electrical work on the property of the em- ployer; or 3. Electrical work specifically exempted under Chap- ter 19.28 RCW. B. Before a licensed electrical contractor receives an electrical permit, the bond required by RCW 19.28.120 shall be conditioned that the principal will comply with the provisions of this Chapter. Section 3 Severability. If any provision of this Ordinance or its application to any person or circumstance is held invalid, the remainder of the Ordinance or the application of the provision to other persons or circumstances is not affected. Section 4 Effective Date. This Ordinance shall take effect as provided by law. • • PASSED by the City Council of the City of Port Angeles at a regular meeting of said Council held on the iltAvday of (Fk)OPPiyyJ).E f , 1985. APPRO D AS TO FORM: Craig D. K utson, City Attorney PUBLISHED: -8- MAYOR