Loading...
HomeMy WebLinkAbout2757ORDINANCE NO. 2757 AN ORDINANCE of the City of Port Angeles, Washington, adopting the current editions of the Uniform Building Code, Uniform Fire Code, National Electrical Code and other related codes, increasing permit fees, and amending Ordinances 2552 and 2561 and Chapters 14.01, 14.03 and 14.21 of the Port Angeles Municipal Code. THE CITY COUNCIL OF THE CITY OF PORT ANGELES DOES HEREBY ORDAIN as follows: Section 1. Ordinance 2552 and Chapter 14.01 PAMC are hereby amended by amending PAMC 14.01.010 to read as follows: 14.01.010 Construction Codes Defined. Building construction within the City of Port Angeles shall be governed by the following listed codes, laws, and ordinances, as adopted and amended in Title 14 PAMC, which shall be collectively known as the construction codes of the City of Port Angeles: A. The Uniform Building Code; B. The Uniform Mechanical Code; C. The Uniform Fire Code; D. The Uniform Plumbing Code; E. The Washington State Rcgulationo for Barricr Frcc Facilitics Ventilation and Indoor Air Quality Code; F. The Washington State Energy Code; G. The Uniform Sign Code; H. The Uniform Code for the Abatement of Dangerous Buildings; I. The National Electrical Code and the State Electrical Laws; J. The Washington State Historic Building Code; K. Stand -Alone Construction Ordinances, as adopted by the Port Angeles City Council and as approved by the Washington State Building Code Council when required by State law. Section 2. Ordinances 2552 and 2561 and Chapter 14.03 PAMC are amended by amending PAMC 14.03.010, .020 and .040 to read as follows: 14.03.010 Uniform Codes Adopted. Pursuant to Chapters 19.27 and 19.27A RCW and Title 51 WAC, the following Codes are adopted subject to the amendments set forth in Ch. 51 16 WAC and Title 14 PAMC 14.03.030: A. The Uniform Building Code, including Appendix, Chapter 1, except subsection 110(b), Appendix Chapters 7, 10, 25, 29, 31, 32, and 49, 1991 Edition and Uniform Building Code Standards, 1991 Edition, published by the International Conference of Building Officials, as amended by the Washington State Building Code Council and published as Chapters 51 -20 and 51 -21 Washington Administrative Code; B. The Uniform Mechanical Code, 194$91 Edition, including Appcndix B, Chapter 22, Fuel Gas Piping, Appendix B, published by the International Conference of Building Officials and the Interna- tional Association of Plumbing and Mechanical Officials, as amended by the Washington State Building Code Council and published as Chapter 51 -22 Washington Administrative Code; C. The Uniform Fire Code, 1991 Edition and Uniform Fire Code Standards, 194$91 Edition, as specifically adopted in Chapter 14.21 PAMC published by the International Conference of Buildinq Officials and the Western Fire Chiefs Association, as amended by the Washington State Building Code Council and published as Chapters 51 -24 and 51 -25 Washington Administrative Code, except as amended in Chapter 14.21 PAMC; D. The Uniform Plumbing Code, 1991 Edition including Appcndix C, and Uniform Plumbing Code Standards, 194$91 Edition, published by the International Association of Plumbing and Mechanical Officials, as amended by the Washington State Buildinq Code Council and filed as Chapter 51 -26 Washington Administrative Code; E. The Washington State Regulations for Barricr Free Codc Council and codified at Chaptcr 51 10 WAC, establishing standards for making buildings and facilities accessible to and for in RCW 70.92.100 through 70.92.160 Ventilation and Indoor Air Quality Code, as adopted by the Washington State Building Code Council and filed as Chapter 51 -13 Washington Administrative Code; F. The Washington State Energy Code, 1991 Second Edition, as adopted and amended by the Washington State Building Code Council and filed as Chapter 51 -11 Washington Administrative CodeT and as codificd in Chaptcr 51 12 WAC, and thc Northwest Energy Code, 1987 edition, as promulgated by thc Bonneville Power Administration, togcthcr with thc conversion standard equivalent codc amendments to thc model energy code, December 24, 1986, all as presently existing or as subsequently amended, provided that: (1) The Northwest Energy Code shall apply to all new conditioning and electrical lighting; all non electrically space heated residential and nonresidential construction except that new residential Z. shall be designed to achicvc cncrgy U3C cfficicncy cquivalcnt to cncrgy u3c achicvcd in typical buildings constructcd with: (a) Ceilings insulatcd to a level of R 30 (R valuc includes insulation only); (b) Walls insulatcd to a level of R 19 (R value includcs insulation only), or constructcd with two -by four members, R 13 insulation batts, R 3.2 shoathing, and othcr normal assembly componcnts; (c) Below gradc walls, insulated on thc interior cidc, to a lcvcl of R 19 (R value includes insulation only), or if insulatcd on thc exterior side, to a level of R -10; (d) Floors over unheated space insulated to a lcvcl of R 19 (R value includcs insulation only); (c) Slab on gradc floors insulatcd to a level of R 10 at thc perimeter; (f) Heat pumps with a minimum heating season performance factor (HSPF) of 6.8 or with all othcr cncrgy sources with a minimum annual fucl utilization efficiency (AFUE) of seventy cight percent; (g) Doublc glazed windows with values not more than U 0.65 whcn tested per AAMA standard #1503.1 -88; and, (h) A maximum glazing area of twenty one percent of thc floor arca or, for purposcs of dctcrmining of fiftccn percent of thc floor area; (3) The conversion standard cquivalcnt code amendments Shall apply to any buildings constructcd pursuant to a building permit issued on or aftcr the the initial construction wcre not required to comply with thc Northwest Energy Codc, whcn such buildings Mating or conditioning and lighting.; G. The Uniform Sign Code, 19&891 Edition, published by the International Conference of Building Officials; H. The Uniform Code for the Abatement of Dangerous Buildings, 194491 Edition, published by the International Conference of Building Officials. I. The Washington State Historic Building Code, First Edition, published by the Washington State Building Code Council as Chapter 51 -19 Washington Administrative Code. In case of conflict among the codes enumerated in subsections A through D of this Section, the earlier named Code shall govern over those following. 14.03.020 Amendments to Uniform Codes. Pursuant to RCW 19.27.040, RCW 19.27.060(3) and (4), and PAMC 14.04.020, the following amendments to the Uniform Building Code, Uniform Plumbing Code, and Uniform Sign Code are adopted: A. Uniform Building Code, Chapter 5, Table 5 -C is amended by adding the following footnote: (�9) Type V -N construction prohibited in CBD - Central Business District. B. Uniform Building Code, Section 3802(b) is amended by adding the following: 5. In all buildings where the floor area exceeds 6,250 square feet on all floors; however, the area and height increases specified in Section 506(C) and 507 (for sprinklers) shall be permitted. For the purpose of this sub - section, portions of buildings separated from the rest of the building, in accordance with Section 505(e), with openings allowed by the Uniform Building Code protected by the installation of approved magnetic hold -open devices which are activated by smoke detection devices installed on both sides of said openings, may be considered as separate buildings. C. Uniform Building Code, Appendix Chapter 32, Section 32123201, is amended to require that all cedar shingles be removed prior to any reroof. D. Uniform Plumbing Code, Appendix C, is amended to add Footnote 1415 as follows: Required restroom facilities shall be maintained open and operable during business hours where businesses are being conducted and in other buildings when being used by employees, occupants, or the public. Such public restrooms shall be readily identifiable. E. Uniform Sign Code, Chapter 3, Section 301, is amended by adding the following: Provided, that presently existing signs not in conformity with this code, as amended, may be maintained in their present condition unless hazardous, but may not be altered or reconstructed unless in conformity with this code. F. Uniform Sign Code, Chapter 3, Section 303: Delete #3, signs less than 6' above grade. G. Uniform Sign Code, Chapter 4, delete Table 4 -B. In lieu thereof, Chapter 45, Section 4505(b) of the Uniform Building Code, 194491 Edition, shall apply to projection of signs. 14.03.040 Fees. The fees set forth in the codes adopted in PAMC 14.03.020 shall apply in all instances except for the following: A. The permit fee for the installation of a modular or mobile home shall be $150200. B. The mechanical permit fee for installation of a solid - fuel burning appliance shall be $4575. C. Sign permit fees shall be according to the schedule set forth in this subsection. 1. Sign Permit Fee Schedule Type of Sign Sign Size 25 50 50 99 Over 100 sq.ft. 3a. ft. sic.. ft. Fee Wall or marquees, - cicctricover 25 sq.ft. $25 $30 $35 $ 75 Wall or marquees, cicctric 30 40 50 Freestanding and projecting 40 50 70 over 25 sq.ft. $100 Freestanding, projecting, cicctric,Al1 signs less than 25 sq.ft. 15 - $ 25 All othcr cicctric, 1c33 than 24 sq.ft. 10 All non cicctric, lest than 25 sq.ft. 10 Supergraphic on building (any size) $ 25 2. If the work authorized under a sign permit has not been completed within 180 calendar days after the date of issuance of the permit, the permit shall expire and any subsequent work shall require a renewal of the permit and payment of renewal fees, at one -half the original fee. All fees are nonrefundable. 3. Any person, firm, or corporation who shall erect, re- erect, construct, alter, or maintain a sign without a permit first having been obtained, except as provided by the Port Angeles Municipal Code, shall as a penalty pay double the amount required by the Sign Permit Fee Schedule. D. Surcharges enacted pursuant to Chapter 19.27 RCW and remitted to the State Treasurer shall be $4.50 for each building permit, plus $2 for each additional residential unit. E. The inspection fee for call -back plumbing inspections shall be $10. F. A surcharge shall be added to the building permit fee for new single - family residential construction and each ground floor unit in new multi - family residential construction to cover the cost of radon testing equipment as mandated by the State of Washington in the amount of $30.00 per ground floor unit to be charged for permit applications submitted between July 1, 1992, and June 30, 1995. Section 3. Ordinance 2552 is hereby amended by amending PAMC 14.050.010, .020, .050, .070, .080, .120, .130, .160, .170, and .180 and adding PAMC 14.05.190 to read as follows: 14.05.010 Purpose and Scope. This Chapter is intended to regulate the installation, alteration, extension, and repair of electrical wiring, materials, appliances, apparatus, devices, and equipment in the City of Port Angeles. This Chapter does not apply to electrical equipment or central stations or sub stations or control of electrical cncrgy for light, power, telephone, or telegraph, or to electrical -construction governed by Chaptcr 19.29 RCW and Chaptcr 296 -44 WAC. This Chapter shall apply to all electrical conductors and equipment installed, used, rented, offered for sale or distributed for use in the City. 14.05.020 Adoption of Electrical Code. The 1987 Edition of thc National Electrical Code (NFPA 70 1987) and the State of Washington Electrical Laws as set forth in Chapter 19.28 RCW and Chapters 296 -46 and 296 -401 WAC, as adopted by the Washington State Department of Labor and Industries, are hereby adopted by reference subject to the amendments set forth herein and subject to the City of Port Angeles utility customer service policies, provided that if any specific requirement contained in said amendments or customer service policies is less restrictive than the specific requirement contained in the State of Washington Electrical Laws, such specific requirement of the State of Washington Electrical Laws shall govern. 14.05.050 Electrical Permit Required. Before any electrical work covered by this Chapter may be installed, altered, or repaired, an electrical permit shall be secured from the Office of the Electrical Inspector. follows: A. Electrical permits will not ordinarily be required for minor repair work such as repairing flush and snap switches, replacing fuses, changing lamp sockets and receptacles, taping bare joints, and repairing drop cords. B. Electrical permits shall not bc required for the C. Upon approval of the electrical permit and payment of permit will bc issued to thc applicant. 14.05.070 Electrical Permit to the Owner. An electrical permit to perform electrical work in or on the owner's residence or structure may be issued to the owner, provided the following conditions are satisfied: 1. The electrical work shall be done by the owner of the property. 2. If requested, the owner shall provide documcn tation (c.g., copy of decd and driver's license) and sign an affidavit stating that he or she is the owner of the property and that he or she will be doing the electrical work. electrical work, thc Inspector may require that thc portion of the altered, or repaired by a licensed and bonded contractor. industrial projccts, as defined in—WAG--2-9G 46 -140, shall submit locations, building service location, and padmount transformer locations, if applicable), riser diagram (one line diagram), connected load breakdown, number of phases, voltage, and building 14.05.120 Temporary U3c of Electric CurrcntService. Permission must be obtained from the Inspector for the temporary use of electric current during the construction or alteration of any building. Such temporary service may be allowed for up to one hundred eighty (180) days. No person shall connect his service with that of any other person, or in any way supply any other person, premises, property, or service with electricity through his service, except as approved by the Inspector. 14.05.130 Unlawful Wiring. A. It shall be unlawful for any person in any way to alter any electrical wiring, or to permit such electrical wiring to be altered unless done in conformity with the provisions of this Chapter. this Chaptcr for such conductor, motor, or apparatus, or to install of safety of thc same. C. Whcn an installation consisting of Edison base type plus fuses is considered to be over fused, thc Inspector shall, Typc "6" (tamper resisting) fuscs or circuit breakers. UB. Master metering of multiple dwelling units is prohibited. Sub - metering of buildings, existing master metered facilities, or multiple dwelling units is prohibited for the resale of electricity, or for the apportioning of costs between separate dwelling units, tenants, or owners. 14.12.160 Wiring Methods. A. Wiring methods for institutional, educational, health care facilities, and places of assembly of one hundred or more persons shall be wired as set forth in Article 518 of the 1987 Edition of the National Electrical Code; the wiring methods in Section 518 -4, Exception 1, shall not be permitted. For determin- ing the occupant load of places of assembly, the methods in NFPA 101, Life Safety Code, shall be used. B. All new or remodeled commercial or industrial buildings that exceed a total of 5,000 square feet shall be wired in an approved raceway. All buildings in the Downtown, Fire Zone 1 as defined in Chapter 14.24 PAMC, and any open space mall -type structures without fire wall separation, industrial zoned property, piers, docks, wharfs, structures over water, and any fccdcr to a panclpermanent structures at the Clallam County fairgrounds, shall be wired in an approved raceway. C. In multi- family occupancy buildings (i.e., apartment houses, hotels, motels, and dormitories), nonmetallic sheathed cable, with grounding conductor, may be used as the wiring method for branch circuits in such wood frame occupancies of not more than three (3) stories, not including a basement which is used for storage. D. All mains and circuits exceeding 300 volts between conductors, and circuits exceeding 150 volts to ground, shall be installed in approved raceways. E. The fault duty rating of all service equipment shall exceed the available fault current. The minimum fault duty rating required on service equipment for non - dwelling installations shall be at least 20,000 AIC. F. Wood used for support or other purposes in electrical installations, in contact with the earth or subject to moisture, shall be commercially pressure treated and labeled for earth contact. G. Electric meters shall not be permitted inside buildings or within carports or porches without written approval of the Inspector. H. Where more than one electric meter is used, a permanent label shall be attached on each meter base showing the apartment or unit number. I. For industrial and heavy commercial buildings using cable trays, metal clad cables will be acceptable for service and feeder conductors when approved by the Inspector. J. The smallest size cable permitted for commercial use is No. 12 AWG copper for power conductors. K. In Residential Occupancies, 20 amp branch circuits will be limited to 20 outlets and /or lighting devices and 15 amp circuits will be limited to 15 devices. L. Bathroom reccptacic3 shall not be on the same circuit ML. In Fire Zone #1, non - metallic conduit will be allowed for exterior use only. NM. On current transformer metering, a lockable main disconnect switch(es) shall be required. The switch(es) shall be located on the outside of the building or in a mechanical room when approved by the Inspector. 14.05.170 Wiring Specifications. A. In single - family units, 1,000 square feet gross floor area or more, a 200 amp service shall be installed. B. On multiple occupancies with service latcrals, a minimum of Six (6) meter minimum groupings arc required. All single electric meters shall be between four and one -half (4.5) feet and six (6) feet from finished grade to the center of the meter glass. C. Breakers are required at all meters in "meter pack" installations not having a main breaker ahead of the meter. D. Insulation in attics or crawl spaces shall not conceal junction, pull, or outlet boxes. E. Removal of panels, pipe, and unused wire and electrical equipment that has been abandoned is required to complete an electrical installation. F. Underground water and sewer pipes shall not be laid in the same trench with an electrical service wire unless: 1. A minimum horizontal separation of three (3) feet is maintained at all points along the line; or 2. All electrical wires are enclosed within an approved raceway and a minimum horizontal separation of one (1) foot shall be maintained. Where water service pipes cross electrical service wires, a minimum vertical separation of one (1) foot shall be maintained. G. The panel ampacity in multi - family dwellings shall have a minimum rating of 100 amps. H. The service equipment grounding electrode conductor and bond conductor shall be copper only. Aluminum shall be prohibited. 14.05.180 Inspection and Permit Fees. The fees for electrical inspections shall be as stated herein; provided that said fees shall not exceed those established in RCW 19.28.210. For the purpose of calculating said fees, amperage shall be based on the larger of the conductor ampacity or the over current device. A. The fee for inspection of the installation, alteration, extension, and repair of electrical wiring, materials, appliances, apparatus, devices, and equipment of the following service(s), or feeder(s), is: AMPERAGE 0 - 100 AMP 125 - 200 A 201 - 400 AMP 401 - 600 AMP 601 - 1000 AMP 1001 - over AMP Temporary service RESIDENTIAL SERVICES COLUMN A $ 4440 4450 §§65 �-9 444 4430 COMMERCIAL/ INDUSTRIAL SERVICES COLUMN B $ 4450 6-97 0 440120 144160 448200 220* *50% of above ADDITIONAL FEEDERS COLUMN C $ 4-915 4520 4530 340 4550 55 * 50% of Column B * One (1) percent of the cost of the electrical work 1. There shall be no additional fee for inspection of branch circuits when included in the service /feeder permit. 2. The residential service fee specified in Column A shall be paid for a single - family residential service, for a multi- family residential service (per service, up to but not exceeding a four- plex), and for each service, or the first feeder, when the service is not being installed, decreased /increased, or altered. 3. The commercial and industrial service fee specified in Column B shall be paid for each service, er -the first feeder, or other electrical work, when the service is not being installed, increased, or altered; for secondaries of transformers that have a capacity greater than 600 VA; for each service or feeder that is over 600 volts; and for a multi- family residence larger than a four -plex. 4. The additional feeders fee specified in Column C shall be paid for inspections with a service or feeder in Column A or B at the same time and on the same permit. B. The following fees shall apply to the electrical inspection of each of the following units and additional units inspected at the same time and same location: Single /First Additional Units Unit (Maximum of 5) Column A Column B 1. Mobile home, modular home or commercial service (200 AMP Max.) 2. Mobile home feeder 3. Each lot for a recreational vehicle 4. Berth at a marina or dock 5. Motors, 10 HP or larger 6. Signs *4§30 *493 00 4425 4425 4425 25 * 5 -510 §10 -510 §10 7. Hot tub (permanent) 4 -925 * Total fee for inspection of one service and one feeder when they are inspected at the same time is $3940. C. For new circuits, circuit extensions, and circuit alterations where the service or feeder is not modified, the permit fee shall be $4930 for up to and including four circuits inspected at the same time on the same premises under a single permit, plus $1 for each additional circuit over four circuits. D. Low voltage systems. The fee for inspection of residential burglar or fire alarm systems, and other Class 2, low voltage systems, shall be $4930 for one to four circuits (zones) plus $1 for each additional circuit (zone). For commercial or industrial Class 2, low voltage system installations, the minimum fee shall be $4930 for the control panel plus $1 for each circuit (zone) inspected at the same time. E. The fee for emergency, standby, and resource recovery generators up to 50 KVA i3 $20. The fcc for a gcncrator installation largcr than 50 KVA, or that is the main sourcc of powcr, is that for the applicable service size listed in subsection A of this Section. F. Block Permit. A firm, corporation, or other entity which has a regularly employed electrical maintenance staff, which is exempted from the requirement to have an electrician certificate of competency by RCW 19.28.610, may choose to purchase a monthly electrical work permit for work done by in -house electrical personnel rather than a work permit for each installation or alteration in accordance with this Section. Work done by contractors shall not be included in this block permit. The Inspector shall determine the maximum number of hours allowed on the block permit. This will entitle the purchaser to inspections for a period determined by the Inspector. Fees will be determined on an individual basis by the Inspector,- based on the estimated inspection time required. G. Fees for carnival electrical inspections. The fee shall be $4-960 for the first ten rides, concessions, or generators, and $45 each for all additional rides, concessions, and generators. H. Trip fees. A fee of $4930 in addition to the applicable inspection fee shall be paid before approval of the installation each and every time the following services are required: 1. Requests to inspect existing installations. After the first half -hour an additional $20 fee shall be provided for each one -half hour of inspection time. 2. Trips to inspect when the permit applicant has given notice to the Inspector that the work is ready for inspection when it is not. 3. An additional inspection trip is necessary because the permit applicant has given an erroneous or incomplete address, or the premise is not accessible. 4. More than one additional inspection trip per permit to inspect corrections required by the Inspector as a result of carelessness or neglect, or for improperly responding to a correction notice. 5. Each trip necessary to remove a non - compliance citation from the job site, posted because unlicensed electrical contractors or uncertified electricians or trainees were working on the jobsite. 6. When corrections have not been made in the prescribed time, unless an extension of time has been requested and granted. 7. When a final inspection has not been requested and the occupant has occupied the building. Furnishings indicate occupancy. I. A fee of two times the regular permit fee shall be charged for work that was started without a permit. This provision shall not apply to emergency work, when at the satisfaction of the Inspector such work was urgently necessary, making it impractical to obtain a permit prior to commencing the work. A permit must be obtained within forty -eight (48) hours after the start of such work. J. On jobs requiring partial or progress inspections, "one" inspection of one -half hour duration is allowed per $2-930 of fee. K. The fee for a plan review shall be $3 -2-40 an hour with a one -hour minimum charge. L. The fee for storm, fire, or other accident damage repairs shall be 50% of a new service of like ampacity, with a minimum charge of $20 (repair only, not new construction due to accidental damage). M. Special permit. For very small jobs requiring an electrical permit as determined by the Inspector and requiring no corrections. The fee for this permit will be $3415. Work requiring a cover inspection or additional inspections shall not qualify. 14.05.190 Electric Signs. Electric signs shall be UL listed and include awning signs, channel letter signs, directional signs, ordinary box signs, recessed signs and trailer mounted signs. A. UL listed electric signs may be repainted or refaced without being reinspected by UL. B. Any electric sign that is altered electrically or mechanically shall be relisted by UL as a "Rebuilt Electric Sign ". C. Electric signs that have been disconnected for more than one year shall be relisted by UL. This does not apply to cord connected signs. Section 4. Ordinance 2552 is hereby amended by amending PAMC 14.21.010, .030, and .050 to read as follows: 14.21.010 Adoption of Uniform Fire Code, Appendices and Standards. There is adopted by the City Council for the purpose of prescribing regulations governing conditions hazardous to life and property from fire or explosion, that certain code known as Uniform Fire Code, including Appendices I -A, II -B, C, F, III -A, B, C, IV -B, V -A, and VI -A, and the Uniform Fire Code Standards, 19881991 Edition published by the International Conference of Building Officials and the Western Fire Chiefs Association, as amended by the Washington State Building Code Council and published as Chapter 51 -24 and 51 -25 WAC; provided that Sections 10.202, 10.203, 10.204, 10.205, and 10.206 shall not be deleted and, notwithstanding any wording in said Code, participants in religious ceremonies shall not be precluded from carrying hand -held candles; and provided further, that Article 78, Fireworks, and Article 80, Hazardous Matcrial3, arcis deleted in thcirits entirety. 14.21.030 Above - Ground Storage of Flammable Liquids. A. The limits referred to in Section 79.501 of the Uniform Fire Code, in which storage of flammable or combustible liquid in outside above - ground tanks is prohibited, are established in all zones except in the ACD, CBD, CSDC1, and CSDC2 zones, where the maximum quantity shall be 24,000 gallons, and the M -2 zone adjacent to the Port Angeles harbor. B. The limits referred to in Section 79.1401 of the Uniform Fire Code, in which new bulk plants for flammable or combustible liquids are prohibited, are established as follows: In all zone classifications except that part of M -2 which lies west of Cedar Street as prescribed in Ordinance 1709 and subsequent ordinances amending the same. 14.21.050 Storage of Explosives. The limits referred to in Section 77.106(b)107(a) of the Uniform Fire Code, in which storage of explosives and blasting agents is prohibited, are established as follows: In all zone classifications except that part of the M -2 zone which lies west of Cedar Street as prescribed in Ordinance 1709 and subsequent ordinances amending the same. Section 5. This Ordinance shall be effective five days after the date of publication by summary. PASSED by the City Council of the City of Port Angeles at a regular meeting of said Council held on the 6th day of April , 1993. Alte i /le 1 MA 4IOR ATTEST: Becky J.( p . n, Citty Clerk AP •ROVED AS TO FORM: 41164,— nutson, city Attorne PUBLISHED April 11, 1993 (By Summary) 92.13 Summaries of Ordinances Adopted by the Port Angeles City Council on April 6, 1993 Ordinance No. 2756 This Ordinance of the City of Port Angeles makes housekeeping amendments to the Port Angeles Municipal Code and amends Ordinances 1709, 2736, and 2732. The amendments include changing the number of the chapter in the Code where the Risk Management Ordinance will be located, reinserting the subsection that added juvenile detention facilities as conditional uses in the Light Industrial District, and clarifying that the recently adopted developer reimbursement charge will not be applied to developments occurring after the original developer has been fully reimbursed for the infrastructure improvements. Ordinance No. 2757 This Ordinance of the City of Port Angeles adopts the current editions of the Uniform Building Code, Uniform Fire Code, National Electrical Code and other related codes, increases permit fees, and amends Ordinances 2552 and 2561 and Chapters 14.01, 14.03 and 14.21 of the Port Angeles Municipal Code. The full texts of the Ordinances are available at City Hall in the City Clerk's office or will be mailed upon request. Office hours are Monday through Friday from 8:00 a.m. to 5:00 p.m. These Ordinances shall take effect five days after the date of publication of these summaries. Publish: April 11. 1993 Becky J. Upton City Clerk