Loading...
HomeMy WebLinkAbout5.591 Original Contract v~ - 5.SqJ .' . NET ENERGY METERING CONNECTION AGREEMENT for CUSTOMER FUEL CELL, SOLAR, WIND, or HYDROPOWER ELECTRIC GENERATING FACILITIES of NOT MORE THAN 25 KILOWATTS This Net Energy Metering Connection Agreement is executed in duplicate this ;),,1 \"ft day of t; c.-tab.ef , 200 L between D D~ .tl-l1 WI" 11 '" (hereinafter referred to as "Customer"), and the City of Port Angeles, Electric tIhty, a MUnIcIpal CorporatIOn of the State of Washington (hereinafter referred to as the City). Both parties, who may be herein further referred to collectively as "Parties" and individually as "Party", agree as follows: 1. CUSTOMER ELECTRIC GENERATING FACILITY 1.1 Customer has elected, in accordance with RCW 80.60 et seq., to operate either a net energy metering fuel cell, solar, wind or hydropower electric generating facility, with a generating capacity of not more than twenty-five kilowatts, in parallel with the City's transmission and distribution facilities. This generating facility is intended to offset either part or all of the Customer's electrical requirements. 1.2 Customer's Application for Net Metered Electrical Generation, including the location of the electrical generating installation and details on the electrical generating unites) is hereby incorporated into this agreement as Appendix A. 1.3 The installation is identified by the City with the following designators: Transformer No. 7.5' · { h (feeder and phase) J If Sf 5 I ~ e... p if se , Customer Utility Account No. 1').4 '^ 00 OOt 1.4 A separate agreement shall be entered into for each Customer's electrical service location(s). 1.5 The electrical generating system used by the Customer shall be located on the Customer's premises. It shall include all equipment necessary to meet applicable safety, power quality, and connection requirements established by the National Electrical Code (Articles 690 and 705), National Electrical Safety Code, the Institute of Electrical and Electronics Engineers, Underwriters Laboratories, and the City's Connection Standards, as set forth in Appendix B, which is attached hereto. 1.6 The City shall have the sole authority to determine which connection requirements set forth herein are applicable to Customer's proposed installation. 2. PAYMENT FOR NET ENERGY 2.1 The City shall measure the net electricity produced or consumed by the Customer during each billing period, in accordance with normal metering practices. 2.2 If the electricity supplied by the City exceeds the electricity generated by the Customer and fed back to the City during the billing period, or any portion thereof, then the Customer shall be billed for the net electricity supplied by the City together with the appropriate customer charge paid by other customers of the City in the same rate class. 1201_01 wpd{5/3/01} Page 1 of 5 c' r' . NET ENERGY METERING CONNECTION AGREEMENT 2.3 If the electricity generated by the Customer and distributed back to the City during the billing period, or any portion thereof, exceeds the electricity supplied by the City, then the Customer shall be: a) billed for the appropriate customer service charge as other customers of the City in the same rate class; and b) credited for the net excess kilowatt-hours generated during the billing period, with this kilowatt-hour credit appearing on Customer's bill for the following billing period. 2.4 At the beginning of each calendar year, any remaining unused kilowatt-hour credit accumulated by the Customer during the previous year shall be granted to the City without any compensation to the Customer. 2.5 Customer shall pay any amount owing for electric service provided by the City in accordance with applicable rates and policies. Nothing in this Section 2 shall limit City's rights under applicable Rate Schedules, Customer Service Policies, and General Provisions. 3. INTERRUPTION OR REDUCTION OF DELIVERIES 3.1 The City may require Customer to interrupt or reduce deliveries as follows: a) when necessary in order to construct, install, maintain, repair, replace, remove, investigate, or inspect any of its equipment or part of its system; or b) if it determines that curtailment, interruption, or reduction is necessary because of emergencies, force or compliance with prudent electrical practices. 3.2 Whenever possible, the City shall give Customer reasonable notice of the possibility that interruption or reduction of deliveries may be required. 3.3 Notwithstanding any other provision of this Agreement, if at any time the City determines that either: a) the facility may endanger City personnel, or b) the continued operation of Customer's facility may endanger the integrity of the City's electric system, The City shall have the right to disconnect Customer's facility from the City's electric system. Customer's facility shall remain disconnected until such time as the City is satisfied that the condition(s) referenced in (a) or (b) of this section 3.3 have been corrected. 4. CONNECTION 4.1 Customer shall deliver the excess energy to the City at the City's meter. 4.2 Customer shall pay for designing, installing, inspecting, operating, and maintaining the electric generating facility in accordance with all applicable laws and regulations and shall comply with the City's Connection Standards set forth in Appendix B, which is attached hereto. 4.3 Customer shall pay for the City's standard watt-hour meter electrical hook-up, ifnot already present. 4.4 Customer shall not commence parallel operation of the generating facility until written approval of the connection facilities has been given by the City. Such approval shall not be unreasonably withheld. The City shall have the right to have representatives present at the initial testing of Customer's protective apparatus. 1201_01 wpd{5/3/01} Page 2 of 5 .' NET ENERGY METERING CONNECTION AGREEMENT 5. MAINTENANCE AND PERMITS 5.1 Customer shall: a) maintain the electric generating facility and connection facilities in a safe and prudent manner and in conformance with all applicable laws and regulations, including, but not limited to, the City's Connection Standards, Appendix B, and b) have the system inspected by a qualified technician after 5, 8, 10 years of operation and every two years thereafter, the latest inspection and test report to be available for review by the City on request. c) obtain any governmental authorizations and permits required for the construction and operation of the electric generating facility and connection facilities. Permit requirements, for this project, include: o Electrical permit o Building permit o Clearing and grading permit o SEP A o Joint Aquatic Resources Permit. 5.2 Customer shall reimburse the City for any and all losses, damages, claims, penalties, or liability it incurs as a result of Customer's failure to obtain or maintain any governmental authorizations and permits required for construction and operation of Customer's generating facility or failure to maintain Customer's facility as required in (a) of this Section 5. 6. ACCESS TO PREMISES The City may enter Customer's premises or property to: a) inspect, with prior notice, at all reasonable hours, Customer's protective devices; read meter; and b) disconnect at the City's meter or transformer, without notice, the connection facilities if, in the City's opinion, a hazardous condition exists and such immediate action is necessary to protect persons, or the City's facilities, or property of others from damage or interference caused by Customer's electric generating facilities, or lack of properly operating protective devices or inability to inspect the same. 7. INDEMNITY AND LIABILITY 7.1 The Customer assumes the risk of all damages, loss, cost and expense and agrees to indemnify the City, its successors and assigns, and its respective directors, offiyers, employees and agents, from and against any and all claims, losses, costs, liabilities, damages and expenses including, but not limited to, reasonable attorney fees, resulting from or in connection with performance of the agreement or which may occur or be sustained by the City on account of any claim or action brought against the City for any reason including but not limited to loss to the electrical system ofthe Customer, caused by or arising out of an electrical disturbance. 7.2 Such indemnity, protection, and hold harmless includes any demand, claim, suit or judgement for damages, death or bodily injury to all persons, including officers, employees or agents, and subcontractors of either Party hereto including payment made under or in connection with any Worker's Compensation Law or under any plan for employees' disability and death benefits or property loss which may be caused or 1201_01 wpd{5/3/01} Page 3 of 5 ! .' NET ENERGY METERING CONNECTION AGREEMENT contributed to by the connection, maintenance, operation, use, presence, or removal of Customer's equipment. The only exception will be liability occasioned by the sole negligence or willful misconduct of the City or its employees acting within the scope of their employment and liability occasioned by a partial negligence of the City or its employees acting within the scope of their employment to the extent that such partial liability is fixed by a court of competent jurisdiction. 7.3 The provisions of Section 7 shall not be construed to relieve any insurer of its obligations to pay any insurance claims in accordance with the provisions of any insurance policy. 7.4 The City shall have no liability, ownership interest, control or responsibility for the Customer's Electric Generating Facility or its connection with the City's electric system, regardless of what the City knows or should know about the Customer's Electric Generating Facility or its connection. 7.5 Customer recognizes that it is waiving immunity under Washington Industrial Insurance law, Title 51 RCW, and further agrees that this indemnification clause has been mutually negotiated. This indemnification shall extend to and include attorney's fees and the costs of establishing the right of indemnification hereunder in favor of the City. 8. INDEPENDENT CONTRACTORS The Parties hereto are independent contractors and shall not be deemed to be partners, joint venturers, employees, franchisees or franchisers, servants or agents of each other for any purpose whatsoever under or in connection with this Agreement. 9. GOVERNING LAW This Agreement shall be interpreted, governed, and constructed under the laws of the State of Washington as if executed and to be performed wholly within the State of Washington. Venue of any action arising hereunder or related to this agreement shall lie in Clallam County, Washington. 10. AMENDMENTS, MODIFICATIONS OR WAIVER Any amendments or modifications to this Agreement shall be in writing and agreed to by both Parties. The failure of any Party at any time or times to require performance of any provision hereof shall in no manner affect the right at a later time to enforce the same. No waiver by any Party of the breach of any term or covenant contained in this Agreement, whether by conduct or otherwise, shall be deemed to be construed as a further or continuing waiver of any such breach or waiver of the breach of any other term or covenant unless such waiver is in writing. 11. APPENDICES The Agreement includes the following appendices attached and incorporated by reference: Appendix A: Customer's Application for Net Metered Electrical Generation to City of Port Angeles. Appendix B: City's Connection Standards for Customer Electric Generating Facilities of25 Kilowatts or Less. 1201_01 wpd{5/3/01} Page 4 of 5 J . NET ENERGY METERING CONNECTION AGREEMENT 12. NOTICES All written notices shall be directed as follows: City of Port Angeles: Electrical Engineering Manager 321 East 5th Street P.O. Box 1150 Port Angeles, W A 98362 Customer: DOUj/q,S A-h f)'ltH111 Name 15/1 w. /O'f11 Sf. Address POf\t tPt~e!-eSJ WJJ. 1'63b3-/2D J City, State & Ziif Customer notices to the City, pursuant to this Section 13, shall refer to the Service Address set forth in Appendix A. 14. TERM OF AGREEMENT This Agreement shall be in effect when signed by the Customer and the City and shall remain in effect thereafter month to month unless terminated by either Party on thirty (30) days' prior written notice in accordance with Section 13. 15. SIGNATURES IN WITNESS WHEREOF, the Parties hereto have caused two originals of this Agreement to be executed by their duly authorized representatives. This Agreement is effective as of the last date set forth below. Si~~ ~ Doualo_~ A-h t11~ 11V1 ~e CITY OF PORT ANGELES: ~-/r/~ JAM cS L tI",;f.Pe"1'f Print name CUSTOMER: Title EJ.,Et:iIfIC ENt:INe-5~/A/t:. dllJA/""'GII?. Title 16/1-~/OI , Date I~ /J/ /0/ Date/ / 1201_01 wpd{5/3/01} Page 5 of 5 I ' APPENDIX A Application for Net Metered Electrical Generation Thank you for your interest in establishing a renewable energy or fuel cell connection with City of Port Angeles, Electric Utility. Please note generation systems must meet certain requirements to be considered. . The project must be not morea than 25 kilowatts (kW) in size. . Generation must be fueled by solar, wind, hydropower or be a fuel cell. . Owner provides power conditioning, connection, and safety equipment. . Projects will be considered on a first come first served basis. Please complete Customer and Installer Information and the appropriate section for the type of generation proposed to be installed. In addition, include a one-line diagram and description of protection equipment. Please allow at least ten working days for processing your application. Questions may be directed to Electrical Engineering Manager, at telephone number (360) 417-4702. Customer Information Owner Name: Mailing Address: City, State & Zip: Email Address: Service Address: DOLl~ 11 #1t001 A5 II W. 10 tit -st. P.rt II'ljef~ WA 4~WlQ"'1? @ -/:en t'w4W/. '1 ~3 63 CDVI1 (If different than Mailing Address) Daytime Telephone: war/::. (tOoUi'S,,..,) '-!t7-/3Sj Electric Utility Account No.: (1410D 001 Expected System Operational Date: (0 /2.f I~ I hlJJ,t1e 'f~7- <096,6 Installer Information (If dIfferent from Customer InformatIOn) Installer Name: ~ Al1V11fln'1 4~J Bob (jl{dje/I (8065 K/ed-r/c) Mailing Address: City, State & Zip: Email Address: Daytime Telephone: Drawings Attached: o one line, 0 manufacturers literature, 0 design drawings. 1201_02 wpd{4/20/01} 10f3 , ' Fuel Cell Information Fuel Cell Manufacturer: Fuel Cell Model Number: Fuel Cell's Rated Power Output (kW): Inverter Manufacturer: Inverter Model Number: Inverter's Power Rating (kW): (AC continuous) (AC continuous) . Describe the protection equipment to be used and the physical location of the installation: Drawings Attached: D one line, D manufacturers literature, D design drawings. Photovoltaic Solar System Information PV Module Manufacturer: It.stY'b{JO Wer- PV Module Model Number: A P I 'J.. 01, PVPowerRatingperModule: I~O DC Watts Inverter Manufacturer: Tf't:ll.e- El1jil1eeY','~ Inverter Model Number: pp - 5 w S-S'i~ I s I Inverter's Power Rating (kW): 5.5" k w Number of Modules: g Total Output: q6a DC Watts (AC continuous) Describe the protection equipment to be used and the hysical location of the installation: ~ e..... "8-1 wi#! i 11 Ver't--e.Y' is rn tt'te. Yll ,/I S h ~ mtJ4tft dn ' e d'J4t'ilje t=/ec:tY'Ol1jc. a.utD ~f-{c.. au.'f; - is/qt( ll1~ pf'tJ1e.c::h'trn A UfD 111~ tho A c tMtf~fer roe/a. y Al.,to hta-h'c off a Cfyeu l.Y rej l.t.{,,1 /rvl t~;::~~c tl;~~~~~ ~t1~~; Drawines Attached: D one line, J8( manufacturers literature, D design drawings. 1201_02 wpd{4/20/01} 20f3 .l 3 ~ Wind System Information Wind Turbine Manufacturer: Sou+n We5 f W;~JjJOUIe'f" , Wind Turbine Model Number: Ai,.. l{03 }.1QY'lt/i!.. Wind Turbine Tower Height: -0- feet Wind Turbine Rated Power Output (kW): .'i kw (Peak at 12 mph wind speed, or specify) AC Source ( check one): ~ Inverter 0 Synchronous Generator 0 Induction Generator Inverter Manufacturer (if using): .see. ptlje :A Inverter Model Number: Rotor Diameter: q feet ('I'") <.ct"""" (AC continuous) (AC continuous) Inverter's Power Rating (kW): System Rated Output (kW): Describe the protection equipment to be used and the physical location of the installation: s~ j1Q!1e '" Drawings Attached: o one line, pq manufacturers literature, 0 design drawings. Small Hydro Power Information Turbine Manufacturer: Turbine Model Number: Turbine Power Output (kW): AC Source (check one): 0 Inverter 0 Synchronous Generator Inverter Manufacturer (if using): Inverter Model Number: Inverter's Power Rating (kW): System Rated Output (kW): (AC continuous) o Induction Generator (AC continuous) (AC continuous) Describe the protection equipment to be used and the physical location of the installation: Drawings Attached: o one line, 0 manufacturers literature, 0 design drawings. 1201_02 wpd{4/20/01} 30f3 ( .. . ~ APPENDIX B CONNECTION STANDARDS for CUSTOMER ELECTRIC GENERATING FACILITIES of not more than 25 KILOWATTS A. General This Appendix sets forth the requirements and conditions for interconnected non-utility- owned electric generation where such generation may be connected for parallel operation with the service of City of Port Angeles, Electric Utility (the City). For purposes of this Appendix, the interconnecting entity shall be designated Customer. B. Connection Requirements 1. Customer shall conform to all applicable National Electric Code (NEe) requirements [NEC Articles 690 and 705] and bUilding codes, and shall obtain electrical permit(s) for the equipment installation. 2. Customer shall have a dedicated lockable disconnect device between sources of alternating-current, (Le. between inverter(s) or other power conditioning unit(s)) and the City's distribution system.~ The lockable disconnect must be accessible tolhe City at all times and only the City's lock may be used on it. 3. Customer's over current device at the service panel shall be marked to indicate power source and connection to the City's distribution system. 4. Customer's power production control system shall comply with NEC Articles 690 and 705, Institute of Electrical and Electronics Engineers (IEEE) Standard P929 minimum specifications, and standards for parallel operation with the City. In particular, the: a. Power output control system shall automatically disconnect from the City's source upon loss of the City's voltage and not reconnect until the City's voltage has been restored by the City. b. Power output control system shall automatically disconnect from the City's source if Customer's voltage fluctuates beyond plus or minus 10 percent. c. Power output control system shall automatically disconnect from the City's if Customer's and the City's frequency fluctuates plus or minus 2 cycles per second (Hertz). d. Inverter output distortion shall meet IEEE Standard 519. C. Safety All safety and operating procedures for joint use equipment shall be in compliance with the Occupational Safety and Health Administration (OSHA) Standard 29, CFR 1910.269, the NEC, WAC rules, the Washington Industrial Safety and Health Administration (WISHA) Standard, the City Service Requirements, and equipment manufacturer's safety and operating manuals. 1201_03 wpd{4/20/01} Trace Sinewave Multifunction Inverters The Trace smewave mverters provIde smewave output wIth hIgh effIcIency, hIgh surge and low Idle current. WIth three mIcro-processors and bI-dIrectIOnal power topology, It IS over 90% effIcient through most of ItS load range. peakmg at 96% efficIency The "soft start" system allows the mverter to run heavIer loads wIth Improved relIabIlIty. The SW mverters can be programmed to perform automatIc generator start and stop, automatIc load sensmg and generator support, and mcludes protectIVe cIrcUItry whIch guards agamst downtIme IndIcators show over-current, over-temperature, short cIrcUIt, and low and hIgh battery voltage condItIOns All Trace SW mverters mclude a bUIlt-m, fully automatIc, three- stage battery charger, desIgned for maXImum chargmg and mmunum generator tIme and fuel 2 year warranty, ETL lIsted to UL standards. SW Senes dimensIOns are: 15" X 22.5" X 9" The PS Series is a hIgh-effIcIency mverter lIke the SW senes wIthout some of the "bells and whIstles" and at a lower pnce Factory pre-set mverter and charger functIOns make thIS senes super-simple to operate Settmg adJustment and field momtormg can be accomplIshed with the optIOnal Smewave Remote Control (SWRC) or Smewave Communications Adapter (SWCA). The PS senes transfer relay IS rated at 50 Amps and IS UL listed. PS Senes dImensions are 15.25" x 22.5" x 6.5" SW SERIES AND PS SERIES INVERTERS Trace Model Batter Volts AC Volts/Hz Continuous Charge Watts Amps 150 120 60 75 130 65 Inventory ID 30-303-027 30-303-028 30-303-029 30-303-030 30-303-047 30-303-050 I 1111111111111111 . .. ~ ~/{d 1 Ji_ .., ',:.~-::a~ .. - .. SW & PS SERIES ACCESSORIES a Trace Model Description Inventory ID Price SWRC Remote Control for SW or PS with 25' cable 30-304 -031 $295 SWRC/50 Remote Control for SW or PS With 50' cable 30-304-032 $329 RC8/10 Remote Control for PS With 10" cable 30-304-046 $38 RC8/25 Remote Control for PS With 25" cable 30-304-047 $55 RC8/50 Remote Control for PS with 50" cable 30-304-028 $69 PSCB CondUit Box for PS serIes 30-304-041 $94 SWCB CondUit Box for SW serIes 30-304-043 $94 SWI Stackmg Cable for SW 01 PS 30-304-030 $45 SWI/PAR Smewave Parallel Stackmg Interface 30-303-032 $345 SWI/PARlE Smewave Parallel Stackmg Interface - export "E' & "W" models 30-300-038 $345 SWODE Outdoor Enclosure 30-304-0 I 0 $371 SWCA SW and PS CommUnicatIOns Adapter 30-303-031 $175 SW-D Display SW serIes mverter (non-operatIOnal) 30-304-044 $175 ~ ''''>,.~ lry, , 43"- ~ 4_-"~.'$':~::~_''ffl<__ "'" " " ~ , " ;y' ,,,, ^ ><, ~ ~ ~ " - A ,<?<,. \ I,~; ;>; . . . . . ,>'~ . , , ,t . . . I~ ~ /, <; ~ :,,~ // ~> >> ; .~<< f;< %, Trace Power Panels "' '" ;">J'~ *" 'Y.:-";V . , ;~ ,. '"'2 The Power Panel System from Trace Engmeermg IS a preassembled, integrated "balance of system" panel with a range of mverter capacitIes, charge controls, t DC input voltages and AC output configuratIOns. The Trace Power Panel ;0$# includes all National Electric Code reqUIred components, wirmg and safety circuitry and is ETL Listed to UL standards. The inverter(s) and all AC and DC safety equipment are mounted on a powdercoated steel backplate. Simply mount the power panel on a wall, connect your batterIes, AC and DC inputs, and AC loads and the system is operatIOnal. Input terminals for generator and PP-SW4024/D utility power are easy to access. All of the systems are on the same size back- plate. They differ in mverter power output, waveform and battery voltage. Dual inverter umts have 120/240 VAC output. Charge control(s) and battery cables are not mcluded. Order them below. A smgle charge control can ~egulate a PV array of up to 1.4 kW @ 12 volts, 2.8 kW @ 24 volts and 5.6 kW @ 48 volts. POWER PANELS Model # ~uantity of Inverter Continuous Inf.ut Waveform Output Battery Inventory Price Power Panels are nverters Power Vol age Charger ID for indoor use only. PP-DRI512/S I DRI512 IS kW 12 VDC Modified SlOe 120 VAC 70 Amp 30-306-0 IS $1979 Because of their large PP-DRI512/D 2 DRI512 3 kW 12 VDC Modified Sine 120/240 VAC 140 Amp 30-306-003 $3637 size. they will be PP-DRI524/S I DRI524 15kW 24 VDC Modified Sine 120 VAC 35 Amp 30-306-006 $1879 shipped by truck. PP-DRI524/D 2 DRI524 3 kW 24 VDC Modified SlOe 120/240 VAC 70 Amp 30-306-008 $3529 freight collect. They PP-DR2412/S I DR2412 24kW 12 VDC Modified SlOe 120 VAC 120 Amp 30-306-018 $2295 come in a wood crate. PP-DR24I 2/D 2 DR2412 48kW 12 VDC Modified Sine 120/240 VAC 240 Amp 30-306-004 $4337 or an optional plastic PP-DR2424/S I DR2424 24kW 24 VDC Modified Sine 120 VAC 70 Amp 30-306-019 $2295 shipping box. Please PP-DR2424/D 2 DR2424 48kW 24 VDC Modified SlOe 120/240 VAC 140 Amp 30-306-009 $4337 call for accurate I PP-DR3624/S I DR3624 36kW 24 VDC Modified SlOe 120 VAC 70 Amp 30-306-007 $2529 delivery time PP-DR3624/D 2 DR3624 72kW 24.VDC Modified Sine 120/240 VAC 140 Amp 30-306-0 10 $4795 PP-SW2512/S I SW2512 25 kW 12 VDC SlOe 120 VAC ISO Amp 30-306-002 $4089 PP-SW2512/D 2 SW2512 5kW 12 VDC SlOe 120/240 VAC 300 Amp 30-306-031 $7237 PP-SW4024/S 1 SW4024 4 kW 24 VDC Sine 120 VAC 120 Amp 30-306-034 $4995 Power Panels are PP-SW4024/D 2 SW4024 8kW 24 VDC SlOe 120/240 VAC 240 Amp 30-306-033 $8995 custom made with PP-SW4048/S I SW4048 4kW 48 VDC SlOe 120 VAC 60 Amp 30-306-012 $4995 your choice of options. PP-SW4048/D 2 SW4048 8kW 48 VDC SlOe 120/240 VAC 120 Amp 30-306-035 $9137 Please allow 4 to 6 -4 I1'P-SW5548/S I SW5548 55 kW 48 VDC SlOe 120 VAC 70 Amp 30-306-013 $5695 weeks for delivery .1 -"'''JA8/D 2 SW5548 II kW 48 VDC SlOe 120/240 VAC 140 Amp 30-306-037 $9995 on non-stock units. POWER PANEL OPTIONS Model # Description Inventory ID Price PPO-C40 C40 DC charge or load controller lOstalled, lOcludes prewlred 60 amp DC breaker 30-306-026 $258 PPO-DVM/C40 Digital meter with LCD display lOstalled on the front of the C40 30-306-030 $99 PPO-CD IS IS amp DC load breaker prewlred and installed in the DC disconnect 30-306-027 $59 PPO-CD20 20 amp DC load breaker prewlred and lOstalled 10 the DC disconnect 30-306-028 $59 PPO-CD60 60 amp DC load breaker prewired and installed 10 the DC disconnect 30-306-029 $59 PPO-BC5-2/0 5 foot 2/0 AWe battery cable pair With flng termlOals (battery side only) and fleXible condUit 30-306-024 $83 PPO-BCIQ-2/0 10 foot 2/0 AWe battery cable pair With flng terminals (battery side only) and fleXible conduit 30-306-00 I $132 PPO-BC5-4/0 5 foot 4/0 AWe battery cable pair with ring termlOals (battery side only) and fleXible condUlt 30-306-025 $115 PPO-BCIQ-4/0 10 foot 4/0 AWe battery cable pair With flng termlOals (battery side only) and fleXible conduit 30-306-022 $182 PPO-BCI5-4/0 15 foot 4/0 AWe battery cable pair With flng termmals (battery side only) and fleXible condUit 30-306-023 $220 PPO-SB Heavy-duty plastic shippmg container, excellent as a battery box (ID 24"H X 46"L X 42"W) 30-304-025 $359 30 J~al U)~J ". iJA.. c: ;1/1 ~~ -------------------------, r -. r-- T81 0 D~TILlTY 0 LNO. 0 METER -f~-~ AC IN I I I <:~ .-" AC IN 2 0 = ----, T <: : t.- NO: w Q( w NEU IN I I III ..... III <: => <: L.. I Z W z NEU IN 2 0 ll. Z c.. I I @ MA~~ NEU OUT : [@] [5 I "V~TER I[ I PAlNllEl I AC OuT I ~ - - ..., o MAIN 0 60 AMP 0 0 CLASS T I I 0 0 t H 60 A 01 10 30 A f-- 0 TB2 ELECTRIC AUX RELAYS 00 IOAHP 1200VAC FURNACE H60 B 01 r030 B f- RESISTIVE 00 - 10 I 0 RYIO NO C H 30 A 01 0 Leg ELECTRIC 0 0 0 I STOVE H 30 B 0 I 10 I 0 I COM 0 ~ J r I .. 0 NON CRITICALr- -j 15 A 0 I 10 I I .. I < RYI\ NO HOT TUB ..J I ... [ NC H 20 B 0 I 10 I ........ '" NON CRITICALf- .. .~ '" 60AoI r030A I ELECTRIC I < ..J 0 ..J HOT \JATER ;c Z ::> RY9 NO I 60 B 0 I 10 30 B HEATER < I ~ LG I COM I W 0 -;; 0 f- RY7 NO 0 ~ L NC I ~ I I W ~ . r-;; I I > ::c < I -; RYB I Z NO I I ~ [ Nt: S~IEL 0 .......... 0 ~ . H;:: 0 $ 0 300 AMP @ @ Q) 0 r REMOTE 0.-+-- CLASS T T220 A 01 I STACKING 0 ! ~TTERY DEEP \JELL 11/ I 15 00 I PUMP <240V) r BAT TEMP DISCONNECT 00 I I -. 0 0 20 A 01 BAT .. +1 TABLE SA\J r 00 :- I I I - 0 BAT - I I ] SHOP PO'w'ER r 00 0 0 I 0 : DC GND AC GND : COMPUTER. 15 A 01 /~ L___:~~-------~-------J -= OUTLETS. SECURITY . REFRIGERA TOR 20 A 01 ~ PELLET STOVE I GAS HEAT F'AN GARAGE DOORS oC] 0000 0000 a- - <: => Z Z .....=> a Q( a Cl o c:::J c::J a aU U ..... ~20V /Arc ~ ~H/ASfE SVSrE x x~ z" ~..... >- 6 o:U s:t: ~ ~ t; U ww..... a L.. G~~lO rcOlN][NlfECrfElO W~rH ~L:J -, <t 0:<: Zz '" ~~ !::9 G[E[N]fE~/ArO[R [B3/ACCKU~ "'w ELECTRIC START 120VAC GENERA TOR SCSVIN$3.OVG PUBLIC PO\JER r I I I I 1M 7. SPECIFICA TIONS 7.1 Technical Specifications Rotor Diameter: Weight: Start up wind speed: Rated Power: Regulator Set Range: Recommended Fuse Size: Yaw Wire Size: Pole Dimensions: Minimum Battery Bank: ,h 'i, I " " ;, jl I: J i I, r I I I' /. :\ I I 1 I i I' i II I: .!l 46 inches (1. 17 meters) 13 lb. (6kg) 7 mph (3.0 m/s) 400 watts at 28 mph (12.5 m/s) 12v 13.8v - 17.8v preset to 14 1v 24v 27.6v - 35.6v preset to 28 2v 36v 41.4v - 53.4v preset to 42.3v 48v 55.2v - 71.2v preset to 56 4v 12v - 100 amps slow-blow 24v - 50 amps slow-blow 36v - 35 amps slow-blow 48v - 25 amps slow-blow #10 A WG (American Wire Gage) stranded. 1 % Schedule 40 pipe (outside diameter 1.875 inch, 48mm) 400 amp hours (12v) 200 amp hours (24v) AIR marine Power Curve 900.00 800.00 700.00 600.00 ~ 500.00 C'G 400.00 3: 300.00 200.00 100.00 0.00 o ---- - ~ ~--- - / ) / I i/ ./ ~ " -\. . ~ ~ ~ H-I-~-t I " ii, ,111 , L I :' '1 5 10 15 20 25 30 35 40 45 50 55 60 Wndspeed at Sea Level (Miles Per Hour) 26