Loading...
HomeMy WebLinkAbout3207 Maple St - Engineering Permit Address (YlaA9\-e r-e Project description .Soar a,nraY roves Date the. permit was finaled Number of technical pages d� b ,.y,{p}E.3« Sy..M �hN. wl: cxN. ,..::s'wa't ydYn..nn ..M- ...sii• �d n. 7 M •S: y, v' i Y'+,' t +I. Wiss, Janney, Elstner Associates, Inc. W AR CHITEENGINEERS CTS 960 South Hamey Street MATERIALS SCIENTISTS Seattle, Washington 98108 206.622.1441 tel 1 206.622.0701 fax www.wje.com Via Email March 22, 2011 Silicon Energy 3506 124th Street NE Marysville, WA 98271 Re: Review of Design Load Testing and Rating WJE No. 2011.0096 To whom it may concern: At the request of Silicon Energy, Wiss, Janney, Elstner Associates, Inc. (WJE) has reviewed the mechanical load test results reported by Intertek, an Occupational Safety Health Administration (OSHA) Nationally Recognized Testing Laboratory (NRTL), for the Cascade PV Module assembly including the module and mounting system manufactured by Silicon Energy. The Cascade PV Module assembly is described in Cascade PV Module Manual Revision 3, and the Cascade System Installation Guide Revision 2. The PV Module assembly is approximately 51 -3/4 inches wide by 47 -1/2 inches long and consists of two layers of 1/8 inch thick tempered glass laminated together and attached to an 1/8 inch thick aluminum frame mounting foot. Silicon Energy has asked that we review the relevant mechanical load test results and report our findings in this letter. We have reviewed the relevant portions of the Intertek test report titled Listing Constructional Data Report issued June 23, 2009, and revised August 3, 2010. Load testing was conducted by Intertek in accordance with the test standard Flat -Plate Photovoltaic Modules and Panels UL 1703 dated March 15, 2002 (UL 1703) Section 41 Mechanical Loading Test. According to the test report, the design load for the Cascade PV Module assembly confirmed by the testing is 125 pounds per square foot (psf). The Silicon Energy PV Models covered by the test report include the following: SiE -150, SiE -155, SiE -160, SiE -165, SiE -170, SiE -175, SiE -180, SiE -185, SiE -190, SiE -195, and SiE -200. It is reported that these models are identical in every construction detail, and differ only in cell efficiency and electrical rating. Sincerely, WISS, JANNEY, ELSTNER ASSOCIATES, INC. p H A A A f ig no Martin, P.E. r> Project Manager •a 1 38664 \201110096 silicon energy consulting zm \comes ondence\letter.docx ��GisTER .s. P rgY g P9S/ 1, ONIAI 3- 2.2 -11 Headquarters Laboratories— Northbrook, Illinois Atlanta 1 Austin 1 Boston 1 Chicago 1 Cleveland I Dallas 1 Denver 1 Detroit 1 Honolulu 1 Houston Los Angeles 1 Minneapolis 1 New Haven !New York 1 Princeton 1 San Francisco 1 Seattle 1 Washington, DC p.....Aditmta.„4 PLAN NOTES 1. POWERSTRUT SHALL BE PS 200 CHANNEL, ZINC COATED STEEL SPACED AS SHOWN PER PLAN. 2. REFER TO GENERAL STRUCTURAL NOTES FOR ADDITIONAL REQUIREMENTS. PIPE RACKS BRACES BY OTHERS. INSTALL PER MANUF. 1 /S1.1 REQUIREMENTS. STEEL PS200 POWERSTRUT W/ 1 1/8" OVAL HOLES 2" OC. SPACE STRUT 4' -0" OC. POT 5213 PLAN G 4 S1.0 SCALE: 1/8• 1,_0. S R,‘ L r 4°N.AL Yr e -f� PROJECT: EPSTEIN WHARTON SOLAR DATE: 4/12/12 CARISSA FARKAS STRUCTURAL 3207 S MAPLE ST, PORT TOWNSEND PROJ. 1222 ENGINEERING, PLLC 2322 NE 103RD ST DESIGN: CF SEATTLE, WA 98125 206.683.3197 SHEET: S 1 .O SNAPRACK SYSTEM BY OTHERS ..N CONNECT EACH STRUT TO PIPE RAIL W/ 5/16 -18 OR 5/16 -20 GALVANIZED OR ZINC COATED U -BOLTS STRUT PER PLAN FOUNDATION BY OTHERS II I II III 41I -I 1 III III 111 III -III- III III III -I1 I II -III II i i i i i i M i _iii MEI HEi l H i i i( 1 i i iii ii �EEM .1 1 iii HEI 1 Iii iiI` I� HE11 i iii= I III i i i III I I II I I- 11 i=i 11 III III III III I I Ed II III I I f =f l f f l_I Tyr 1 f f i f l' I l l f f l l l f l I f l =ifi_l i r l l H Iiir=-HMH HrAiM it ii"EdiriMEHi iiialiEill= iii 1�� ii )i 111, III -III -1 1 el 11771117 11 X 11 1 I e i 1 IF 11 -1 I ei i i,- X 11 -i 1 IT 1 ,1,EtO v W:A.s Le74) m f, y Ai SECTION 1 A, SCALE: 1 /2" =1�_0" ~Q �i 45213 4.41 <z, Cyr gt -Ar) PROJECT: EPSTEIN WHARTON SOLAR DATE: 4/12/12 CARISSA PARKAS STRUCTURAL 3207 S MAPLE ST, PORT TOWNSEND PROJ. 1222 c f ri t ENGINEERING, PLLC 2322 NE 103RD ST DESIGN: CF SEATTLE, WA 98125 SHEET: S1. 206.683.3197 GENERAL STRUCTURAL NOTES (The following apply unless shown otherwise on the plans) CRITERIA 1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS, AND THE INTERNATIONAL BUILDING CODE (2009 EDITION). 2. DESIGN LOADING CRITERIA WIND Kzt =1.0, Iw =1.0, GCpi =0.18, 100 MPH, EXPOSURE "C" EARTHQUAKE SDC D, Ie =1.0, Ss =1.24, S1 =0.76, SDS =0.78, SD1 =0.43 SEE PLANS FOR ADDITIONAL LOADING CRITERIA 3. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION. 4. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE PLANS. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED TO PERFORM THE CONTRACTORS WORK. THE STRUCTURAL ENGINEER HAS NO OVERALL SUPERVISORY AUTHORITY OR ACTUAL AND /OR DIRECT RESPONSIBILITY FOR THE SPECIFIC WORKING CONDITIONS AT THE SITE AND /OR FOR ANY HAZARDS RESULTING FROM THE ACTIONS OF ANY TRADE CONTRACTOR. THE STRUCTURAL ENGINEER HAS NO DUTY TO INSPECT, SUPERVISE, NOTE, CORRECT, OR REPORT ANY HEALTH OR SAFETY DEFICIENCIES OF THE OWNER, CONTRACTORS, OR OTHER ENTITIES OR PERSONS AT THE PROJECT SITE. 6. CONTRACTOR INITIATED CHANGES SHALL BE SUBMITTED IN WRITING TO THE STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO FABRICATION OR CONSTRUCTION. 7. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED, SUBJECT TO REVIEW AND APPROVAL BY THE STRUCTURAL ENGINEER. N E PO T S 5 P`ma c W4 r. 1 GENERAL NOTES -0 t.., 4 S1.2 NOT TO SCALE (Hip' E r `'C,. 45213 �v 0 V ES G/?.1.Lr;G v S�pA ENS .4. 1Z+113 PROJECT: EPSTEIN WHARTON SOLAR DATE: 4/12/12 cfSe CARISSA PARKAS STRUCTURAL 3207 S MAPLE ST, PORT TOWNSEND PROJ. 1222 ENGINEERING, PLLC 2322 NE 103RD ST DESIGN: CF SEATTLE, WA 98125 206.683.3197 SHEET: S1.2 GENERAL STRUCTURAL NOTES, CONT. (The following apply unless shown otherwise on the plans) 8. ALL STRUCTURAL SYSTEMS WHICH ARE TO BE COMPOSED OF COMPONENTS TO BE FIELD ERECTED SHALL BE SUPERVISED BY THE SUPPLIER DURING MANUFACTURING, DELIVERY, HANDLING, STORAGE AND ERECTION IN ACCORDANCE WITH INSTRUCTIONS PREPARED BY THE SUPPLIER. STEEL 9. POWERSTRUT NOTED PER PLAN SHALL BE STRUCTURAL STEEL PER ASTM A 36. 10. STRUCTURAL STEEL AND CONNECTIONS EXPOSED TO WEATHER SHALL BE HOT DIPPED GALVANIZED AFTER FABRICATION. 1 My, A s 1 c v G,t,GC>, 45213 GENERAL NOTES, CONT. 'ON E.N S1.3 NOT TO SCALE e e S pi-113 PROJECT: EPSTEIN WHARTON SOLAR DATE:4/12/12 CARISSA FARKAS STRUCTURAL 3207 S MAPLE ST, PORT TOWNSEND PROJ. 1222 ENGINEERING, PLLC 2322 NE 103RD ST DESIGN: CF SEATTLE, WA 98125 206.683.3197 SHEET: S 1. 3 It t k s1III in en'e rq qm b M 3._,, 4 _t x.�y x "ova tt 'a rw�^ !r .vy. t ems Cascade Series PV Module and Installation System see the difference �`�C T\ Silicon Energy's mission is to manufacture quality PV systems specifically for the US market that .advance' r durability, longevity of performance and aesthetics. 4 The Cascade Series PV Module and Installation System t 7 a r I has some unique features that differentiate it from other PV systems presently on the market. 1 e PV Module Features: High efficiency crystalline silicon cells i 1 7 f Strong and durable fe Double -glass module construction allows light to 4• Y 4- ass between cells 1 l 1 Six bypass diodes per module provide improved 4 performance in partial shading s 1. t 4 Highest fire rating Class A "r 30 -year limited power warranty, 5 -year materials and workmanship °'mss.# m .w Installation Systems Features: Cascade design allows water, snow and ice easily flow off Increased air flow behind modules increases performance i J Mounting system conceals and protects wires r -K' 1 for a clean wireless look w: f Squirrel proof y �v� rt Installs on standard 4 -foot centers y'. ,,,,,,,I.,:, F specifically designed for the US market 6° Y P Y g •c: e w s Aesthetically pleasing modern appearance a w Customer colors available (architectural 4 r „0 'r 7'' +u,. bronze standard) Made in USA Washington Minnesota i Electrical Characteristics Measured at STC* SiE160 SiE165 SiE170 SiE175 SiE180 SiE185 SiE190 SiE195 SiE200 Rated Power (Pmax) Watts 160 165 170 175 180 185 190 195 200 Maximum Power Voltage (Vmp) 24.7 24.8 24.8 24.9 25.0 25.1 25.3 25.5 25.6 Maximum Power Current (Imp) 6.5 6.7 6.9 7.0 7.2 7.4 7.5 7.7 7.8 Open Circuit Voltage (Voc) 29.9 30.0 30.0 30.1 30.2 30.3 30.5 30.5 30.6 Short Circuit Current (Isc) 7.6 7.7 7.8 7.8 7.8 7.9 7.9 8.2 8.4 Maximum System Voltage (VDC) 600 Series Fuse Rating Amps (Amps -DC) 15 Temperature Coefficients Pmax: 0.566 /°C Voc: 0.389 /°C Isc: 0.109 /°C Standard Test Conditions (STC) at 1000w /m', AM 1.5 spectrum, 77 °F /25 °C cell temp. 1 4 8 cf i 1 3 3/4 2 1/2 1 H T 1-I 12 13/16 4 x -j j 1 r-- r 1/4 -20 Mounting Studs l h L L o 4 per Module j _IL ■�f 1L J 1 24 Li .11/4 L'H'' EJ- 1/4 -20 Module 1 1 46 1/8 I q f -I I I II 1--- Ground Studs 49 1/2 l I I L it Module Width 1 j O L 2 per Module _.k J II li i o l i 11 1 i i S ir i om m 21 3/4 i' 1 j 1 1 �I 'i 1! 1 I ∎li 1 1 1 i 1 1 li II !f,- 1 1 I 1/4 in. i 1 o 1 Powder Coated Aluminum i 1 1 Module Overlap i 1! I ii Mou Foot (Protects Wire) I I� i i I 1i l 24 ,I! 11 it i Ji Ii 1 �I Fastener Slots i j 1 II I' I �I "p 45 3/4 i1 11 11 1! 11 I 3 /8x11 /4 Module Connectors I 1I 1 Tyco SolarLok 11 I I 11 i 1 11 14AWG Solar Wire :L____ i, j L-_ 1 1 L 1� 1 �i Ii i II I e -1- 10 -32 Ground Stud 10 9/16 I II ii if Ii 1 515/8 1 H 3 3/4 48 c` 48 C1 a 8 H'----.1 1 7/8 in. Base of Mounting Foot H *Not to Scale, Units in Inches Complies to UL1703, specifications subject to change without notice. eCl,�us Mechanical Specifications and Ratings Weight (module mounts) 58 lbs. (^'65 lbs. ^'4.1 lbs. /ft Front: 0.125 in. high transmissivity tempered glass Cells 49 crystalline silicon cells wired in series (7 x 7) Construction Back: 0.125 in. tempered glass Diodes 6 bypass diodes per module Encapsulant: Advanced Encapsulant 0.09 in. aluminum alloy 5032 H32 Mounting Foot 0.125 in. powder coated aluminum alloy 5032 H32 Frame 1/4 -20 stainless steel studs with flange nuts Slope of Module 1.85° (minimum mounting surface angle 5 Temperature Range -40 to 194°F -40 to 90 °C) Fire Rating Class A Design Load 125 psf Connectors (Wire) Tyco SOLARLOK (14 AWG Solar Wire, Length 32 in.) 3506 124th Street NE s I 1 I C n Marysville, WA 98271 USA Tel: 360 618 -6500 Fax: 360 618 -6501 2 h r q Li- www.silicon- energy.com V8.2 (Rev 070111) i r s.. eri r qL m Cascade PV Module Manual 1 Ir 1 1 f 1 11 R N i 11 111 1 `,4,‘I-42:-4/ 1 i i lF f 1 1. I r 11 kE :I .4 1y tl' 1 6 :1: 1 .1 1 '3�� r �a -1 1� I 1 '1:' s ill., t h r d r a 1 pio 1 t l I I �+1 E I i q t r 1 9 v 1 1 ,1 f.,4 M1a-d '.i ll l t1 l r d l 1 ,i,' R f 1 1 t l c C i r� 'r .,]sreR �I e, tr t rte l�+ C I 1� s -1 a5 ter ,rt r' f I 1 S'r �yt >2 7 c t U 11 u s �e t d :.m+ ._,14 g f t I, R s 0 n e. x 1 t .teri r d t vI t E Ir l 1 hi` t. P irl i y f t k r ti v t k 1 it 1 4 r 1 t ills` 01 r 1 r 1 11 F P f it t r 4 i f {1, 1 -i r2 af {'tw Y i 1 A` .10,y4_44,..._..,,, p -.1: a f L aLt ue .t .rX� 'ice Y t t x o-f y o a t r1i ,,T 11 I, 4 v- Yv r r t .4 i �i n'17'"i'i't--',147-Wii3O iL st },4 "5. 2 a L 1 r f .r 1 1 Z 1 i n J 1t i rk lY a1 4 b I f. 3 tlt I f fly I nt c 434.4,' riFiIV q'. Y 1 p,<1 a 'xe' f i P 4i1 P ,,f t T 4,, (L:4 �-e- r f7' 1 rra1- +gaz t r fes Yk'V N d *r r 1 e 1 Q 7'' r k I. h j', i '',1:11'; i 1 d'� i A fl t x e dtl a t i ti s> t r +dFr t u, f ll f 1. a r L dt t t +SN ki Y. x D1 4N `41.10 i�1�� °f SS 1u l l(!_ l.' rt k' t r,_ 11;i '',I;1,,, r'-,, �t 1 I Ott .4 ti t a 5 o l rf'Y) N, F X, 1� 1 r r t i tt k 1 v x s ti n1 r L .1t� IX t t` d f a r a Y r 4 -7 7, ',.i.-,,,,.1-. r� d .YI fl 1. ri F ll 1. x. 4 .1 4. III 5 t 1. 1 "j pg .'41r. i *61419144 k fi t j 1�t t I 1.1,-, 1. lye. 11 t t p v. �'7t: l yl d I j i tint R 1 4 1 t t 12 P+ 4 il, .1p I� r r s, 1, 4,1 i ri.1 9Y s f f Py f i Itr 1.4 1b al c)��Jl x�?J k t R d§ h' t o I l -t tip I r-qp il q 7 i ll +"4 T i d tiPi 'V it Y 1. 11 +I f t, e� f y 1 a l I U a'ti 15`” -.1 of i I rl h 1t 111 1 t i 1 T 114 4 7 e L s'I`i n, f 1 f 1 t Ilk 1 1 t l''.1.4 (I 1a r Vfd ;4 y. 4 Sp' /1- 1 l u E it 13. 1 1 III 'S f {1 a +1�` us� y�,'�r t 4 It q .Yul I 114Y kk 1 9 I/P� 11 1 l'' 1 31 ill ^t t to 1..r rfl 1 a_I .,a 'tw t (r i llS f i i 1 r i w s s �i� ilea E 1 1 t} A I ..4 f I .P �p i, i 1 l o 3• +1 f" r 1 w i I t 9 i 1' 1 a �'1 f I 31. Y t t l r I n 1 s� 1 ��1 l i �4� I '11, s t f n I ,g t til rI .I 4 t I 'f l r i :.1 Y l; f, t i tIA I 1. ly 4 t f l t �10 1 writ i l ilt f 1 3 I h4 E i4i) 1 f wft� rill �M1r 44,4 i tt -fi 1'1 tt Etb, it ,1 i -,t 4I;Ir f r.; r i i I "xl t' 4 e +3 I 0 ai, t1 J y 1 1 1 t {��Fo a !fi k, 11 f �tf �t 1� 3tI�,r1�1 i:f,l -,ca, 4 Atli I 14-lie yitiu.t S-- This manual contains important safety, installation, operation, service, and maintenance information that you should understand in its entirety prior to installing, wiring, or using Silicon Energy PV modules. Do not connect or disconnect modules under load. Silicon Energy PV modules are designed to produce direct current (DC) electricity from light. Modules wired in series, parallel, or series parallel configurations can produce electrical shock great enough to cause damage to property, injury, or death by electrocution. Prior to installing, wiring, or using Silicon Energy PV modules you should: fully understand and practice electrical, building, and fire safety fully understand PV /solar electric systems have knowledge of, experience with, and follow all local and national building and electrical codes (see National Electric Code -NEC Article 690) Product Handling Only knowledgeable and trained professionals should install these modules. In some jurisdictions, licensed contractors may be required for installation. Multiple panels connected in series can produce high voltages which are potentially hazardous. Do not wire the modules during wet, damp or high wind conditions. Cascade PV modules are constructed with a tempered glass front and back. Although durable, it is glass. Handle with care. Do not set the module down in such a way that the exposed edges of glass are supporting any weight. Areas on the module most prone to damage are the exposed edges of glass and the leads. Pay particularly close attention to protecting these areas from damage while installing, servicing, or maintaining the module(s). Do not stand on, step on, or kneel on the module. Do not drop the module, drop objects onto the module, or set heavy loads on the module. Avoid any sharp impacts between objects and the module. Always treat the output wires of the modules as a potential source of electricity and electrical shock. Photovoltaic modules do not have to be connected to a circuit to generate DC current. Each installer should wear safety gear including eye, head, hand and fall protection. The modules are heavy and must be handled properly to avoid injury to persons and damage to product. It is recommended that two people lift and move modules due to their size and weight. Protect person and module from falls when installing above ground. Inspect modules for damage, particularly to the leads. Never install a damaged module. Use extreme caution when handling a module with a damaged lead. PLEASE NOTE, AS PER SECTION 48, UL 1703: PV module power is affected by both temperature and light: Colder temperatures can increase the voltage and power. Reflection of light from snow, water, or other surfaces can increase the current and power. Do not artificially concentrate light on the module(s). Under normal conditions, a PV module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions (STC). Accordingly, the values of I and V marked on this module should be multiplied by a factor of 1.25 when determining component voltage ratings, conductor ampacities, fuse sizes, and size of controls connected to the PV for output. Refer to Section 690 of the National Electric Code (NEC 690.8) for another additional multiplying factor of 1.25 (80% derating) which may be applicable. The electrical characteristics are within -10% of the indicated values of I V and Pmax under standard test conditions (irradiance of 100 mW /cm AM 1.5 spectrum, and a cell temperature of 25 °C 77 °F) 2 www.Silicon Energy.com Cascade PV Module Manual Rev. 3 1. Compliance Silicon Energy's Cascade PV Modules are built to comply with UL 1703, "Flat -Plate Photovoltaic Modules and Panels These modules contain no user serviceable parts. Please read the following warning statements before installing the modules: The installer is responsible for following all local and national building and electrical codes, including those which may supersede specifications contained in Silicon Energy manuals. Consult local building authority for all wind, snow and seismic requirements. Some jurisdictions may require an engineering certification. The installer is responsible for ensuring the following: the building /mounting structure can support all code required loading conditions waterproof integrity of the mounting surface; including the use of appropriate flashing when needed Silicon Energy Cascade Modules are appropriate for the specific installation environment and site conditions. Substitution of fasteners and wire connectors other than those supplied by Silicon Energy may void warranty. Use a minimum of 14 AWG USE -2 sunlight- resistant wire or PV wire and Tyco SOLARLOK Connectors for all wiring connections. Ground module(s) according to the instructions in the Grounding Requirements Section. Provide 15 amp max series fuse rating over current protection. This module carries a Class A fire rating. In order to maintain this rating, when mounted on a roof structure, the module must be mounted as specified, maintaining a minimum clearance of 1.5 inches. The roof surface must be made up of a fire resistant covering appropriate for the application and abiding by local authority guidelines. 2. Module Specifications The Cascade PV Module currently comes in one physical configuration (see Figure 1) with a series of electrical specifications (see Table 1). See the Silicon Energy Cascade Installation Guide for dimensions of the module when mounted with the custom Cascade Installation System. Referencing the component callouts in Figure 1, each module is comprised of: 1. 49 crystalline silicon cells and 6 diodes encapsulated in one high- strength, double -glass lamination. 2. An aluminum edge guard/ side frame is factory mounted along each of two sides of the module. 3. Each edge guard has two 1 4-20 Mounting Studs with two' /a -20 serrated flange nuts and 4. Each edge guard has one 1 4-20 Grounding Stud with one' /a -20 serrated flange nut. 5. A negative lead made up of 14 AWG USE -2 wire and exiting the module from a strain- relieved, sealed compartment. 6. A positive lead made up of 14 AWG USE -2 wire and exiting the module from a strain relieved, sealed compartment. 7. The negative lead is terminated with a Tyco SOLARLOK Connector (male housing). 8. The positive lead is terminated with a Tyco SOLARLOK Connector (female housing). 0 Qu w, 0 0 0 0 +o 4 ('l 162 1 45.75 [1205 I 47.43 Figure 1. Silicon Energy Cascade PV Module with dimensions (inch [mml) and component callouts 3 www.Silicon- Energy.com Cascade PV Module Manual Rev. 3 Silicon Energy produces a series of Cascade PV modules with the following electrical characteristics: Table 1. Electrical Specifications at Standard Test Conditions* Cascade PV Module Model SiE -150 -155 -160 -165 -170 -175 -180 -185 -190 -195 -200 Rated Power in Watts (Pmax) 150 155 160 165 170 175 180 185 190 195 200 Open Circuit Voltage (Voc) 29.7 29.8 29.9 30.0 30.0 30.1 30.2 30.3 30.5 30.5 30.6 Short Circuit Current (Isc) 7.4 7.5 7.6 7.7 7.8 7.8 7.8 7.9 7.9 8.2 8.4 Maximum Power Voltage (Vmp) 24.4 24.5 24.7 24.8 24.8 24.9 25 25.1 25.3 25.5 25.6 Maximum Power Current (Imp) 6.15 6.33 6.48 6.65 6.85 7.03 7.20 7.37 7.51 7.65 7.80 Maximum System Voltage (VDC) 600 600 600 600 600 600 600 600 600 600 600 Series Fuse Rating (Amps -DC) 15 15 15 15 15 15 15 15 15 15 15 Standard Test Conditions (STC): Irradiance of 1000W /m AM 1.5 spectrum, and a cell temperature of 25 °C 77 °F The electrical characteristics may vary within 10% of the indicated values 3. Module Installation The following general instructions are provided as the minimum required for safety. For detailed mounting instructions see the Silicon Energy Cascade System Installation Guide. 3.1. Electrical Installation Safety Solar modules and their interconnection cables pass direct current (DC) and can be a voltage source when exposed to light or under load. DC can arc across gaps and may cause injury or death if wiring is connected or disconnected when current is present. Modules must never be connected or disconnected under load. Before (dis)connecting modules, the circuit must be broken at another point using a rated device intended for that purpose (e.g. breaker). A short circuited module or array exposed to light will produce current that should be treated as a load. Fully cover all modules with an opaque material before connecting or disconnecting modules. 3.2. Electrical Installation Requirements All installations must comply with the National Electric Code (NEC) and all applicable local codes. Provide 15 amp maximum series fuse rating for over current protection. Secure all wires and protect from mechanical damage. For all installer supplied wiring, use a minimum USE -2 sunlight- resistant wire or PV wire with a maximum conductor temperature of at least 90C (wet) such as found in the Table 2. Table 2. Wire Specifications Gauge Mfr Part Max Conductor Purpose (AWG) Mfr Number Temperature Supplied by Module Output 14 Tyco 1986166 -Y 90C min (wet) SiE to Disconnect 14 Tyco 1986166 -Y 90C min (wet) Installer or SiE to Disconnect 12 Tyco 1986165 -Y 90C min (wet) Installer or SiE to Disconnect 10 Tyco 1986164 -Y 90C min (wet) Installer or SiE to Disconnect 6 Tyco 1986274 -Y 90C min (wet) Installer or SiE to Ground 14 to 6 N/A N/A 90C min (wet) Installer The module output leads are 14 AWG and come with factory installed connectors (see Table 3). When making the final connection of the array to the positive and negative disconnects, use only UL recognized solar connectors such as Tyco SOLARLOK connectors. The metallic crimp supplied within the connector may only be applied using the approved Tyco crimping tool. 4 www.Silicon Energy.com Cascade PV Module Manual Rev. 3 Table 3. Connector Specifications Crimp gauge Mfr Part Purpose (AWG) Mfr Description Number Supplied by Module Output, SOLARLOK Male Coupler, Negative 14 Tyco Female Contact, Minus Keyed 1394462 -2 SiE Module Output, SOLARLOK Female Coupler, Positive 14 Tyco Male Contact, Not Keyed 6- 1394461 -1 SiE 3.3. Grounding Requirements This module does not have a continuous frame. Therefore, for safety and to protect the system from lightning, both edge guards of the module must be grounded. Connect to earth ground using the center PEM studs and the flange nuts provided. When the module is properly installed with Silicon Energy's Cascade Installation System, the module will be grounded to the installation structure and no additional grounding of the module will be necessary. The ground conductors must be a minimum of 6AWG if installed in such a way that it is exposed to mechanical damage. Ground conductors which are protected from mechanical damage must be a minimum of 14AWG. 3.4. Mechanical Installation Requirements Modules must be fastened securely to installation systems intended for PV applications. Wind and snow loads not to exceed 125 psf. For module applications requiring greater strength Silicon Energy must be consulted to protect the module warranty and an engineer must be used to design the installation means. Engineering verification is recommended to ensure a structurally sound roof or mounting structure. When roof mounted, module and installation system must be over a fire resistant roof covering rated for the application. The Cascade PV Modules must be mounted with edge guards parallel to the fall line of the roof or mounting structure. They are designed to be rotated to have the positive lead on either side, but must not be mounted with the edge guards running perpendicular to the fall line. As always, good practice should be used when installing Silicon Energy Cascade PV Modules: Mount to maximize solar exposure and minimize or eliminate shading. Modules may be mounted at any angle from 0 to 90 however the Cascade Installation System does have minimum installation angles. See the Silicon Energy Cascade System Installation Guide for more details. When installing these modules the following should be considered: Avoid low angle installations to prevent buildup up dust, debris, snow and ice and to utilize the "frameless" feature of these modules to best advantage. Always maximize ventilation behind modules for cooling. A minimum clearance of 1.5 inches between mounting surface and modules is required to maintain fire rating. 5 www.Silicon- Energy.com Cascade PV Module Manual Rev. 3 Snap.. TM 7........„_„. GROUNDMOUNT FILE a CITY OF PORT ANGLES Construction Plans The Issuance of this permit based upon these plans, specifi- --.•.r.,, ions and other data shall not prevent the building official '-thereafter requiring the corner ;ion of errors in said specifpa6ons and other or from preventing being carried on thereunder when in \hie codes and ore lances of this jurisdiction. On y �c�__ kcd Ali 1l/40tz- te, 1 I t CODE COMPLIANT INSTALLATION MANUAL 1 2012 44. //z Table of Contents 1. INTRODUCTION 2 1.1 Overview of the Ground Mount System 2 1.2 Overview of this manual 3 1.3 Your responsibility as installer 3 1.4 Support 3 2. PREPARE FOR THE INSTALLATION 4 2.1 Introduction 4 2.2 Identify SnapNrack components 4 2.3 Obtain installer supplied tools and materials 5 2.4 Survey the site 6 2.5 Lay out system on the ground 6 3. INSTALL PIPE FRAME 8 3.1 Excavation of the footings 8 3.2 Set grade stakes for vertical pipe 9 3.3 Install pipe 10 3.4 Set concrete footings 10 3.5 Pipe couplers and fittings 11 4. INSTALL RAILS 12 4.1 Attach pipe clamps 12 5. INSTALL MODULES ON RAILS 13 5.1 Prepare clamping hardware 13 5.2 Set first module 14 5.3 Connect wiring 15 5.4 Connect grounding 15 5.5 Trim rails 15 6. FINAL CHECK 16 6.1 Structural inspection 16 6.2 Check all fasteners 16 6.3 Check wires 16 7. APPENDIX 17 7.1 Engineering Letter 17 2 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 1. Introduction 1.i Over view 4Ji Lilt Ground Mount System The SnapNrack Series 200 Ground Mount System, is a low profile, visually appealing, photovoltaic (PV) module installation system. This innovative suite of racking components simplifies the process of installing solar modules and shortens install times, which lowers installation costs. IN- F x SnapNrack systems, when installed in accordance with this manual, will be structurally adequate for the specific installation site and will meet the 2009 International Building Code, as well as local building codes. The SnapNrack installation system is a set of engineered components that can be assembled into a wide variety of PV mounting structures. It is designed to be installed by qualified solar installation technicians. With SnapNrack you will be able to solve virtually any PV module mounting challenge. 3 I 13 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 1.2 Overview of this Manual This manual describes the installation procedures for ground mounting with the use of 1.5 -inch Schedule 40 and Schedule 80 steel pipe for photovoltaic (PV) arrays. Review this entire manual before installing the SnapNrack system. Throughout this manual you will see highlighted notes which will provide you with different types of information: NOTICE indicates important information to help with the installation or to avoid potential damage to the structure or components. CAUTION indicates a potential for property damage, personal injury, or death. For questions call the SnapNrack technical support team. Find contact information at www. snapnrack.com. This manual is available in PDF form at www.snapnrack.com 1.3 Your Responsibiiity as lnstaile Comply with all applicable local or national building codes, including any that may supersede this manual. Make sure that the SnapNrack components and other products are appropriate for the particular installation and the installation environment. Use only SnapNrack supplied parts for the rail system. Ensure safe installation of all electrical aspects of the PV array. If it is raining, or if you anticipate any potentially dangerous conditions, do not proceed with the installation. 1..4 it rrt For help with your installation, contact the nearest SnapNrack engineering support office. You can find contact information for SnapNrack support by visiting www.snapnrack.com and clicking on Contact Us. 4 I I SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 2. Prepare for the Installation 2.1 Introauccion r t t The SnapNrack system is designed to be installed with a minimum number of footings resulting in a significant labor savings over traditional installation methods. The system !PPP integrates with ordinary 1 -1/2 inch Schedule 40 A or Schedule 80 galvanized pipes. This ground Ground Rail and Channel Nut mount solution includes everything needed to install modules on pipe with vertical posts zrusi up to 8 feet from grade. You will only need the pipe, pipe fittings, concrete and the basic construction skills to complete the installation. f This fully engineered system utilizes industrial grade SnapNrack support rails and module clamps. Top Mount End Clamp Assembly 2.2 Identify SnapNrack components Make sure you have all the necessary SnapNrack system components (see photos) needed to complete the installation. Mid Clamp Assembly (O Pipe Clamp Assembly Components Universal End Clamp 5 i 1 5 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 2.3 Obtain installer supplied tuu.:, and materials Make sure you have all the necessary additional hardware components, tools, and other material that are needed to complete the installation. These should include: Post hole digger Power Auger or Back Hoe for power assisted excavation for concrete Wheelbarrow and shovel Kee Klamp Double Swivel String line Line level or builder's level Framing square Tape measure ``a r Pipe cutter 2 pipe wrenches Mallet or large hammer Kee Klamp Single Swivel Drill Felt -tip marking pen Half -inch box /open end wrench ;eke 3/8 -inch ratchet wrench with half -inch socket and torque wrench Tools for attaching grounding hardware Reciprocating saw or chop saw with Kee Klamp Tee a nonferrous metal blade for trimming the rails Metal file for finishing trimmed rails 6 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 2.4 Survey the site Measure the installation area and develop an may out system on the ground accurate drawing identifying any obstacles such as buildings, ditches and trees. Using the information collected in the site survey, complete a system layout showing If plans are available, check to make sure array location and distances from key that the plans match the layout. features. Include any information necessary Review the shading pattern across the for the permitting process. installation area from nearby structures, The following definitions are used to describe trees, etc. It is wise to perform a shade array layout designs: analysis prior to the design as part of a Module length —the measurement standard site analysis. along the longer side of the module Identify any restricted access areas as frame required by the local jurisdiction usually Module width —the measurement referred to as offsets from other structures. along the shorter side of the module frame Module thickness —the measurement BEFORE YOU DIG ANY HOLES, of the thickness of the module contact all utilities in the area to locate any underground lines, Typically, most ground mounted arrays are pipes, and wiring. installed in a landscape configuration, with the long side of the PV modules horizontal and the rails running up the slope. This is Determine the design wind speed and different from roof mount installations which specific conditions for the site and reference typically are in a portrait configuration with the Rail Span Calculation table in section 7 to the long side of the module running up slope determine the maximum allowable rail span and the rails running horizontally. and footing spacing for this site. When laying out the array, be sure to leave If you are unsure about the local design space for the module clamps on the rails. wind speed, consult with the local building jurisdiction. Module mid damps (see photo on page 4) are installed between modules in a row and I7 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL require a half inch of space between the not overhang mounting rails by more than modules. 25% of total module frame length. Standard module end clamp s (see photo Verify that mounting rail spans are in on page 4) require 1.5 inches of extra rail to accordance with the Rail Span Calculations extend past the end of the module frame. table in the section 7 at the back of this If you are using universal end clamps (see manual. photo on page 4) the rail can be trimmed Verify that rail ends do not overhang by a flush with the module frame. The space distance greater than 30% of the acceptable between rows of modules is not critical, rail span specified in the same table. but it is a good practice to leave a small gap (1/8 inch) between rows of modules to Submit array plans to local permitting be installed so that the modules are not in jurisdiction and proceed with the layout only contact with each other. when all permits for the project have been granted by the authority having jurisdiction. Layout rails so that module frame ends do TYPICAL ARRAY OF 4 MODULES INSTALLED MODULE OVERHANG .:p NOT TO EXCEED 25% OF MODULE LENGT RAIL s SHOWN j to BEFORE RAIL END VERHANG MODULES NOT TO EXCEED ARE 30% OF ACCEPTABLE] INSTALLED RAIL SPAN Location of rail ends and module overhang (Landscape Orientation) 8 1 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 3. Install pipe frame 3.1 �.x‘aVldavti of the footings To speed up installation, it is recommended to use a 12 -inch Excavate core footings -12 inches in power auger to dig the footings. diameter and typically 36 to 60 inches deep. See engineering design tables in Section 7 of this manual for recommended peir depth. Before you dig any holes, make certain all utilities in the area have Footing size may vary depending on been clearly marked including job- specific conditions. All conditions should underground lines, pipes, and be reviewed by customer's site engineer. wiring. M AX RAI' GVERHAr1C, rRP� MAX RAIL LENGTH iRL, y ..0 SNAPNRACK GROUND MAX RAIL SPAN cR:0 (-RILI RAIL MODUIES` I1 SPAN (RS) AND MAX RAIL 1 y OVERHANG OR CANTILEVER RO) \,y' 1 6 MAX y' BRACE A. SEE TABLE I FOR CCNDFITONS WHEN ARRAY TILT ANGLE r THIS BRACE 15 REQUIRED._ MAO ae• ABOVE GRADE 4 Il i PIER DEPTH i 1.5" 501 40 GALVANIZE) EEL PIPE O I STS [1\ FOUNDATTIXV DE TAILS PIER DIAMETER AS SHOWN IN THE PIER DETAILS tS 915051EEUVE 1.4 5 ELM( WOW. K615 Y6RIOl P(S15 I ss <uSrzF w( HRI1(N mbR •llo011REWNP 11wFa na ''6E T ro ieoF m✓C 80 d Barr. OF VVOM0L RIPARO1O Pate CSCN.T)lE u'' MRS wawF SWAM r nEEaalev.Ema s� MAN ItIXMARGE Ott MIME MU 1oC I u 01 111 rte m9110c1E]�SO 3,1lBSm ID RIMPULOY 6NUE MIRMI vFO m1+rt1m a w nu u.c¢r FLANGE MOUNT L L DETAIL STANDARD PIER DETAIL STANDARD PIER DETAIL ON SLOPED GRADE I9 SnapNrackTu SERIES 200 GROUND MOUNT INSTALLATION MANUAL 3.2 Excavation of Grade Bea A grade beam may be used in place of the pier foundations. Grade beam shall be a minimum of 12" wide, 18" deep and shall run the width of the array a minimum of 12" beyond each vertical post. (2) #4 Bars L Shall be used at BOTH the top and bottom e of the grade beam, one on each side of the r vertical pipe. These shall have a minimum of 3" clear of concrete cover and shall conform to the attached specifications. Concrete Digging holes with power auger shall conform to the attached concrete specifications. Using the Grade Beam option at locations with a design wind speed of 120 Paost MPH or higher require a site specific analysis. f nstail pipe and set concrete Determine the proper angle for the module► array and calculate the length of the vertical posts. Do not exceed 8 feet of vertical post length from grade for rear post. Supports vertical pipes at the proper height and angle Install vertical pipes in concrete footings until the concrete piers (or grade beams) are itro set. Use a string line to insure alignment of posts. Pour concrete into the footings. Tamp the concrete to ensure contact with the vertical pipe support. Remove the support bracing the concrete sets. Concrete requires 28 days to reach full strength or rated PSI. Engineering Tables in this Manual require a 2,500 PSI rating on the fully cured concrete. Check pipe frame levels 10 I 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 1.4 Bracing Options `4, 7. There are two bracing options for SnapNrack y t Series 200 Ground Mount System. See figures f on next page for illustration of these options. 1 It Standard Install Using Braces A, C and D 4 V II", V Braced Option Using Braces A, E and F rte The Engineering Tables in Section 7 of this Manual list site conditions that determine the necessary bracing. Tee installed 1 5 o +ne coin^° ^Yr Vertical posts can now be assembled and rest on the support bracing. Using two pipe wrenches and 3/16 -inch hex wrench, the pipe and support legs can be assembled. a Align the end of the channel using a string at line. Tighten all the pipe connections and �Q cross brace hardware and re -check alignment of the vertical pipe supports. The pipe v''. should be assembled with Kee Klamp style pipe couplers or equivalent. The couplers and connectors should be installed to the Swivel installed manufacturer's specifications. KEE KLAMP OR THREADED PIPE EQUIVALENT COUPLERS PIPE TEES s 1.5" SCHED 40 1.5" SCHED 40 STEEL PIPE STEEL PIPE FOR ��A'� F OR BRACING MEMBERS HORIZONTAL MEMBERS NOTE: KEE KLAMP OR TORQUE ALL KEE EQUIVALENT i KLAMP OR EQUIVALENT SINGLE SOCKET 1.5" SCHED 40 STEEL PIPE SET SCREWS TO 29 SWIVELS FOR VERTICAL MEMBERS FT-LBS TORQUE 11 SnapNrackrM SERIES 200 GROUND MOUNT INSTALLATION MANUAL GROUND RAIL i� HORIZONTAL PIPE a of POST t y" BRACE F NOTE: BOTTOM CLAMP OF BRACE A SHOULD I y ALWAYS BE CLOSEST TO V TOP OF FOUNDATION BRACE A WI BRACE E d h a a f_ a a -a a a.. s... 11 i l F OR B J III BRACE U BRACE O: SEE NDTE ON REQUIRE/EMS BRACE D: WHEN BRACE C IS BRACE C: SEE TABLE FOR REQUIRED, BTACE D IS ALSO REQUIRED CONDITIONS W FEN THIS MAX PIPE SPAN PG IF: (-_BRACE ISREQUTRED AND SITE SOS VALUE IXCEEDS 1 MINIMUM FREQUENCY. MAX PIPE OVERHANG PS /4 FRONT (SHORT) HOST HEIGHT ALTERNATE BRACE IX ®S 36° ORIENTATION AS SHOW,' 12 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 4. Install rails 41 Attach Aran rlam+,S Snap in SnapNrack pipe -to -rail clamp insert and attach rails to pipe frame as shown in the detail diagram. Inserts are designed to snap in and out of rail channels. This enables you to quickly assemble systems without having to slide inserts from the end of the rail. ___I x X Always cut rails to the required 9 1- length. Never use a rail splice to r•-' -`i join two shorter rails in a ground i P' mount installation. l g" X 2.5" SS HEX BOLT WITH SS SPLIT LOCK WASHER (OR FLANGE BOLT) SNAPNRACK MID CLAMP SNAPNRACK CHANNEL 1 NUT 5/16 18 SNAPNRACK UNIVERSAL END CLAMP SNAPNRACK UNIVERSAL END CLAMP WEDGE SNAPNRACK GROUND RAIL a" X 1.5" SS HEX BOLT SNAPNRACK SPLICE INSERT WITH SS FLAT WASHER AND PULL STRAP ,i 1 SNAPNRACK PIPE CLAMP 1 -1 /2IN 1.5" SCI 4' STEEL PIPE 1, jg" X 1" SS HEX BOLTS WITH SS SPLIT LOCK WAS HERS Detail of pipe -to -rail connection 13 1 SnapNrack'^^ SERIES 200 GROUND MOUNT INSTALLATION MANUAL 5. Install modules on rails r i irrepare ciarnping hat Preassemble module clamping hardware. •1 Each standard end damp assembly and mid r clamp consists of a module clamp, a channel r p nut, and a 5/16 -inch bolt and split lock washer. The end clamp size and bolt length are specific to the thickness of the module if you Aligning first row of modules are using the standard end clamp. Make sure you have the right size of each of these components for the modules being installed. To speed the installation, measure out the I ocation of mid clamps and end clamps on re A rails with a tape measure. Snap in clamps on all the rails so the clamps ..R will be ready when you place the modules. r i `f,....... L Place the first module, taking care to line the First row of modules installed module up to the rails. The rest of the installation will go more smoothly if you take the time i to get the first module lined up properly. r Tighten the two end clamps on the first module and snap in the next two clamps, which will typically be mid clamps, to prepare to receive the next module. Three rows of modules installed 14 I SnapNrack SERIES 200 GROUND MOUNT INSTALLATION MANUAL Place all the bottom modules first and requires the WEEB -PMC washer, only on align them with a string line or laser. We the mid clamps. recommend you leave a 1/8 -inch gap between the rows of modules to allow for 5.5 Trim rails thermal expansion and to help dissipate heat. If you are using standard end clamps, trim rail Proceed to the next row and work your ends to leave about 1.5 inches of extra rail way up. When you place the last module in the row, secure it with end clamps to finish the row and repeat the process for the next row of modules. .3 .W;finect wiring Connect module leads and train the wires into the rail channels as the modules are being installed. This will ensure a clean installation with no dangling wires. Use module lead clips as necessary to insure Grounding with lay in style lugs that module leads are secured to module frames until they drop into the rail channel. B You can also use the SnapNrack channel cover to help retain wires. 5.4 Connect °rounding WEEB PMC grounding washer Install grounding hardware per PV module manufacturer's specifications and NEC code requirements. It is often convenient to install grounding hardware as modules are being installed but this will vary with the type of PV modules used The Wiley Electronics WEEB is an acceptable grounding method. The SnapNrack rail WEEB on mid clamp 115 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL extending past the end of the module frame. If you are using universal end clamps, the rail can be trimmed flush with the module frame. File off any sharp edges from the rail ends y with a hand file and clean up metal shavings. Install the rubber rail end covers. Careful array layout planning will enable you to cut rails to the correct length before they are installed and eliminate the need for trimming. Check all bolts 6. Final check 5.1 Structural inspection Grab module frames and gently push up and down in various locations around the array to ensure that nothing moves. A r nrl. all fasteners Check all bolts with the torque wrench to ensure that all 5/16 -inch hardware is Check under the array for loose wires. tightened to correct torque: Silver Hardware 10 -16 ft -lbs. It is a good practice to look for areas Black Hardware 7 9 ft-lbs. where the PV wires or cables could potentially get damaged due to Check wires contact with the module frames, Check under the array to ensure all wires are rails or other sharp metal objects. attached properly with module clips along This is a common cause for ground the module frames and trained into the cable fault in PV installations. channels in the rails and that all channel covering is snug. 16 1 SnapNrackrM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 7. Appendix e ia.y Letter T HYLOR Central Coast: 684 Clarion Court San Luis Obispo, Califomia 93401 805.547.2000 800.617.2235'fax 0SYHIN Southern California: 1276 E. Colorado Blvd, Suite 201 Pasadena, California 91106 toNSIILTIIiG ENGIOEERS. INC 626.793.7438 626.793.7439 fax STRUCTURAL CALCULATIONS, SPECIFICATIONS, AND SUMMARY PREPARED FOR: SYSTEM: SnapNrack Series 200 PV Mounting System DESIGNER: SnapNrack 775 Fiero Lane Suite 200 San Luis Obispo, CA 93401 PROJECT ENGINEERS: Matthew Gilliss, P.E., LEED AP Amy Ransom Nathan White, P.E., S.E., LEED APB° +c Michelle McCovey -Good P.E. OFESS R I C 65495 o o E XP. C_� O sqr civet. �P a Subiect to Annual Review Re- issuance. Valid Through December 31, 2012 or Lic. Exp Date, whichever is sooner. 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 1 fi Y [OR Central Coast Southern California 684 Clarion Court 1276 E. Colorado Blvd. San Luis Obispo, CA 93401 Suite 201 805)547.2000 Pasadena, CA 91106 805 547.2001 fax (626)793.7438 (800)579.3881 (626)793.7439 fax SUMMARY LETTER Date: January 1, 2012 To: SnapNrack Attn: Greg McPheeters From: Matthew Gilliss, P.E., LEEP AP Taylor Syfan Consulting Engineers Project: SnapNrack Series 200 PV Mounting System T &S Job No.: 10500 Subject: Summary Letter for Series 200 INTRODUCTION This Project Summary Letter is in reference to the Structural Calculation Packet for the SnapNrack Series 200 Mounting System, dated January 2012. The calculations have been performed in accordance with the 2010 California Building Code (CBC), the governing structural code in California, which is based on the 2009 International Building Code (IBC). The 2009 IBC references the 2005 Minimum Design Loads for Buildings and Other Structures, including Supplement No. 1, No. 2, and Errata, by the American Society of Civil Engineers (ASCE), referred to as the ASCE 7 -5. The racking system has been designed to withstand code prescribed forces due to the racking system's own weight, the weight of the solar panels, snow loads, seismic loads, and wind forces. RAIL SPANS In terms of variable conditions for the racking system, the follow pages contain charts that can be used to determine maximum spans and spacings based on the solar array's overall size and tilt angle. This chart is a summary of the following pages which include the calculations for each component under each condition. 18 1 SnapNrack" SERIES 200 GROUND MOUNT INSTALLATION MANUAL HYLO R Central Coast Southern California 6 84 Clarion Court 1276 E. Colorado Blvd. San Luls Obispo, CA 93401 Suite 201 y (805)547.2000 Pasadena, CA 91106 (805)547.2001 fax (626)793.7438 (800)579.3881 (626)793.7439 fax rs1Vuas SUMMARY LETTER SITE- SPECIFIC ANALYSIS Each possible racking configuration labeled in the following chart has been analyzed and is summarized within this chart. Because there are many different possible configurations, (2) two of the common cases have been provided in this report as example calculations. Site specific racking configurations with calculations producing the overall results shown in the following charts can be provided upon request. A site specific analysis may be required if it is found that the location of the solar panel installation or configuration corresponds to any of the following criteria (but not limited to): The total pitch of the solar panel (solar panel pitch) is greater than 45 degrees above the horizontal. Special note should be taken to measure the solar panel pitch from the horizontal and NOT the grade to be installed on. See note at the end of this section. A topographic factor applies to the location. Topographic factors apply, for general purposes, when the structure is on the upper half of a hill, or on a mesa or bluff, or is near a large body of water or other flat surfaces such as salt flats, that exceed 5,000 ft. For complete descriptions of topographic factors, please refer to ASCE 7 -05 Section 6.5.7. The site ground snow load is greater than 50 psf. The site design wind speed is greater than 120 MPH (3 second gust speed). A combination of loads and /or site conditions applies that is not addressed in the attached rail span and foundation charts. Verify all conditions with the local building official or a registered professional engineer. If one of more of these factors applies to the project location, please contact Taylor Syfan, and we will be able to analyze the site conditions and recommend a custom engineered configuration for each specific site. 1 19 SnapNrackrm SERIES 200 GROUND MOUNT INSTALLATION MANUAL TOY1_511 Cent ral Coast Southern California 684 Clarion Court 1276 E. Colorado Blvd. San Luis Obispo, CA 93401 Suite 201 (805)547.2000 Pasadena, CA 91106 0._ 2 (805)547.2001 fax (626)793.7438 I S (800)579.3881 (626)793.7439 fax tiiisi i74 E'17'7F5 .i'C SUMMARY LETTER It is also to be noted that the provided summary charts assume the site is flat (i.e. the array is NOT installed on a hillside). For sites with a slope, the listed foundation depths will be required to be increased as per the soils engineer or, if the project does not involve a soils engineer, SnapNrack's drawing 5200 -D03. SUMMARY CHARTS AND TOPGRAPHIC FACTORS The attached pages of this summary contain common array configurations with varying wind speeds. These charts can be used as a quick reference for looking up array configurations and foundation requirements based on the site conditions, but it must be noted that for any site location where a topographic factor is to be applied (e.g. hills, bluffs, water) the configurations given may not be adequate for the given site. A registered professional engineer should evaluate the exact topographic conditions for this specific site prior to construction. (Taylor Syfan may be retained for this evaluation, however they or another registered professional engineer should evaluate the site). UNIVERSAL END CLAMP SnapNrack has also developed a "Universal End Clamp" which is used to connect individual solar panels to the rails (see SnapNrack's 5200 drawings). These have been developed and tested by SnapNrack, and they are adequate to resist the maximum uplift and shear forces generated by code prescribed wind forces when installed as specified. The testing results may be presented upon request. FOUNDATION OPTIONS Pier Foundations: Piers shall be 12" in diameter and shall be the depth required in the following charts based on wind speed, panel tilt, and snow Toad. Concrete shall conform to the attached concrete Specifications. Grade Beam Option: A grade beam may be used in place of the pier foundations. See SnapNracks drawing S200 D04 for grade beam configuration; Grade beam shall 20 SnapNrackTu SERIES 200 GROUND MOUNT INSTALLATION MANUAL TRY LO F l Central Coast Southern California 1 684 Clarion Court 1276 E. Colorado Blvd. 1^ San Luis Obispo, CA 93401 Suite 201 AN 263, 91106 (2),S (805)547.2001 (805)547.2000 fax (6 (626)79)793.744 38 (800)579,3881 (626)793.7439 fax SUMMARY LETTER be a minimum of 12" wide, 18" deep and shall run the width of the array a minimum of 12" beyond each vertical post. (2) #4 Bars shall be used at BOTH the top and bottom of the grade beam, one on each side of the vertical pipe. These shall have a minimum of 3" clear of concrete cover and shall conform to the attached Specifications and be adjusted for local conditions. Concrete shall conform to the attached concrete Specifications. Using the Grade Beam option at locations with a design wind speed of 120 MPH or higher require a site specific analysis. SITE SPECIFIC ENGINEERING The results in this packet are structurally adequate for all configurations shown. For certain projects, site specific engineering may be recommended to help determine a very efficient custom installation cost. Taylor Syfan may be contacted to provide a site specific analysis in order to optimize the racking and foundation design which may lead to substantial cost savings on certain projects that may have unique site conditions and /or scale. REFERENCES AND LIMITATIONS Please note that all sizes, material specifications, and weights have been provided and approved by SnapNrack. Please see SnapNrack's plans for limits on the bolt parameters. Torque all 5/16" diameter hardware as specified in SnapNrack's plans (10 -16 ft -lbs for Silver Stainless Steel and 7 -9 ft -lbs for black Stainless Steel). Torque bolts sufficiently to prevent loosening, but do not damage bolts or threaded parts. Periodic inspection of connections is required. SnapNrack has also provided estimated soil values used to calculate the size and depths of the footings (soil type 4 or better, per IBC Table 1806.2). It is the responsibility of SnapNrack's customer, otherwise known as the contractor or professional solar installer, to verify with a soils engineer or the building inspector that the site specific soil conditions match or exceed the estimated values given within this report. It is also the responsibility 21 1 SnapNrackT^^ SERIES 200 GROUND MOUNT INSTALLATION MANUAL Central Coast Southern California THY1.011 684 Clarion Court 1276 E. Colorado Blvd. San Luis Obispo, CA 93401 Suite 201 805)547.2000 805)547.2001 fax 626)7926)793.4 91106 (63.7438 (800)579.3881 (626)793.7439 fax SUMMARY LETTER of SnapNrack's customer to verify the site specific design forces (wind speed, ground snow load, etc.) before using the charts contained in this packet. Installation of Series 200 is to be conducted in accordance with SnapNrack's drawings S200 D01 thru D05 (all drawings are REV F). Construction of any and all structures is under the jurisdiction of the local building official and building enforcement agency, which shall review and approve all projects prior to commencement of construction. Please feel free to contact me with any questions or concerns. Thank you. Sincerely, Matthew B. Gilliss Project Engineer Taylor Syfan Consulting Engineers 22 1 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 1 IL O 1t Central Coast: 684 Clarion Court Southern California: 1276 E. Colorado Blvd. rr San Luis Obispo, CA 93401 Suite 201 yrAN (805)547.2000 Pasadena, CA 91106 (805)547.2001 fax (626)793.7438 (800)579.3881 (626)793.7439 fax STRUCTURAL SPECIFICATIONS GENERAL 1. Do not scale drawings. Contractor shall use dimensions on architectural plans to lay out array, foundations and other elements. If dimensional questions occur, REC Solar, Inc. SnapNrack (REC) must be consulted. 2. All construction and materials shall comply with and be installed in accordance with all the requirements of all legally constituted public authorities havirjg jurisdiction, including all county and local ordinances, and the Safety Orders of the State Industrial Accident Commission, OSHA. 3. The Contractor shall be responsible for shoring and providing bracing during construction and /or erection to support all loads to which the structure may be subjected. 4. The Engineer will not be responsible for and will not have control or charge of construction means, methods, techniques, sequences, or procedures, or for safety precautions and programs in connection with the construction delineated by these plan$. It should be understood that the contractor or his/her agent(s) shall supervise and direct all work and shall be solely and completely responsible for all construction means, methods, techniques, sequences, procedures, and conditions on the job site, including safety of all persons and property during the entire period of construction. Periodic observations by Taylor Syfan Consulting Engineers Incorporated (or "Taylor Syfan" typ.) personnel or representatives are not intended to include Verification of dimensions or review the adequacy of the contractors safety measures on or near the construction site. 5. No deviations are allowed from the structural details without the written approval of the Engineer. Approval by Building Enforcement Agency, Inspector, Special Inspector, or any other party does not constitute authority to deviate from plans or specifications. All plan changes or addenda are subject to approval of the Building Enforcement Agency. The processing of changes, assembly of permit documents, and acquisition of permits is the responsibility of the Contractor. 6. Special Inspectors shall obtain Building Enforcement Agency clearance prior to any work commencement. Copies of the inspection repprt(s) to be filed by the special inspector(s) shall be given to the Engineer. The Contractor is responsible for scheduling, coordination, and expenses involved in any and all inspections. 7. Taylor Syfan's drawings are prepared to convey only the specific structural aspects of each detail. Non structural information, including but not limited to fenestrations, fire resistance, insulation, finishes, waterproofing, drainage and flashing may not be included on the structural plans. Taylor Syfan is not responsible for non structural information. The Contractor shall obtain the non structural information for each detail from REC and Others. 8. The Building Inspector shall inspect and apprgqve all construction for conformance to the construction documents and building code. Additionally, structural observation by Taylor Syfan or another structural engineer is recommended to verify general conformance. 9. All construction projects require inspection and maintenance following completion. Operation, inspection, and maintenance are the sole responsibility of the Owner. The Engineer shall have no responsibility for any failures due to deviance from or neglect of the proper installation procedures presented in this installation packet. Ensure that workers, equipment and other loading are not applied to the PV modules or racking throughout the lire of the structure. SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL T V O Central Coast: Southern California: t[ 1 684 Clarion Court 1276 E. Colorado Blvd. y[iN San Luis Obispo, CA 93401 Suite 201 805)547.2000 Pasadena, CA 91106 805)547.2001 fax (626)793.7438 (800)579.3881 (626)793.7439 fax STRUCTURAL SPECIFICATIONS 10. The drawings, calculations, notes and specifications contained herein and provided herewith are the exclusive property of Taylor Syfan, Copyright 2012. The use of these calculations and specifications shall be restricted to the original plans, provided by REC, for which they were prepared and publication thereof is expressly limited to such use. Reproduction or publication by any method, in whole or in part, is prohibited without written permission of Taylor Syfan. Title to these drawings, calculations, notes and specifications shall remain with Taylor Syfan without prejudice. FOUNDATIONS CONCRETE 1. The Building Inspector shall inspect and approve all grading and excavations prior to placement of forms, reinforcing steel or concrete. 2. Refer to the structural drawings details for foundation embedments, however, foundations shall in no case be embedded less than 12" into approved competent soil. Where frost depths exceed designed foundation depths, the frost depth will govern design depths for foundations. 3. Concrete shall have a minimum strength of 2,500 psi at 28 days, Type II cement, and maximum slump of 5 Special Inspection is not required by the Engineer except that it may be specifically required by the Building Enforcement Agency. 4. Reinforcing steel shall be to ASTM A615, deformed, clean and free of rust. Bars shall be 60 grade minimum (unless specified otherwise). 5. Aggregates shall be per ASTM C33. Maximum size 1 for footings and 1" for all other work. 6. Concrete durability, quality, mixing, placing and curing, shall conform to ACI standards and specifications. Mix design must be adjusted for local soil and exposure conditions. 7. Conform with ACI 301 and 318 requirements. 8. Reinforcing clearances for foundations shall bg 3" min. when against earth and 2" min. when against a formed surface or top of footing. 9. Removal of forms (formwork) supporting vertical surfaces shall be after 2 days min. 10. Minimum lengths for lap splices shall be 48 bar diameters. STRUCTURAL STEEL 1. Pipe sections shall conform to ASTM A53 Grade "B 2. Install cold- formed metal framing according to RISC and to manufacturer's written instructions unless more stringent requirements are indicated. 3. Steel members exposed to weather, soil, or moisture shall be galvanized or have similar corrosion protection. Steel embedded in concrete shall Nave the same cover requirements as for reinforcing steel (rebar), unless the embedded steel is galvanized or has similar corrosion protection. Finishing requirements for exposed steel are by others. 24 1 I SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL D Central Coast: Southern California: THYI.OR Clarion Court 1276 E. Colorado Blvd. San Luis Obispo, CA 93401 Suite 201 (805)547.2000 Pasadena, 91106 (6 (805)547.2001 fax (626)79)793.744 38 (800)579.3881 (626)793.7439 fax Series 200 Brace Locations .1 ..,g i 1 hr...., f NOTE 1 i II .N1111111LJ B ON REWIRE ENES �.'Ivi (4, FOR BRACED .,h BRACE D: 0015 BRACE C 15 MACF C: SEE TABUS. NOR REQUIRED, BRACE 511 ALSO REQUIRED CONDITIONS' WHEN TRS MAX PIPE SPAN PS 1 IF: BRACE IS REQUIRED AND S111 505 VALUE 111005 1 IBNIP:UN FREQUENCY. MAX PIPE OVERHANG P114 FRONT (S ROST HETGNI ALTERNATE BRACE FxCFEDS 31 ORIE111AEI0h A5 SHOWN BRACE C D Brace D is located between the front (short) vertical posts Brace C is located between the back (tall) vertical posts As 4 �0 GR OUND RAIL HORIZONTAL PIPE 4 IP, POST BRACE F BRACE A SHOEIID E: BOTTOM CLAMP ALWAYS BE FOUNDATION TO TOP OF FOUNDATION •I, r BRACE A V"� BRACE E BRACE A, E, F 25 p acto g--6 ce.S co ve. Lo A )0 Load_ s 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 0 LL U) U) U) d u U) U) U) 4) LL U) U) u) 0 u U) CO Q 0 006 W W W U) 0 otf W W W 0 o S LL Lo CS 0 W 1 0 LAW 0 cc co W Z O m O m O m 8 m O 'A O 0 O 'O O 'O N N N N 7 K O W W c, 7 x O W W c 7 W W W c, 7 W W a C 0a Z?.}, c ya c y }Z M cc 3 re 3 re N R 15 to o c O v rn a, 0 Y e� U a, V O c.) w d V .L+ a1 J J J J 0, d= v v CO E a, CO C CO 1 d= v CD I's i fl. t6 Q of co _a Z A Z is Z is Z co Q c o cn C N vFiv CO C d t vciM u2 C O t M fi w V c''.. Z V W U) CL u) W co n w �a c m F. d N u) a y N to a d N CO a d N CO fn a N W U) T- ft N r' 7 O. CL W W O ca H Q rco 1.- 0 a 0 o W D 00o W O ^0 2 Q o o in 2 a in i fl 2 Q 0 a, r... in 2 c.V 0 co io .c y ao <OU,tn 2_, 0. ao u ,u) o N 0 0 .2 co d a o d Q O N d D. O N d a 0 U x v x� x� x LL, c c co io M co co im L 2 Bo io in 1 8 2 0 I v i i c cn m U 1 m U I CO 0 I m 0 O Co a W W, to 1.1.1 u W N 7 a a a a H 0 a a v T W W W W E N 1- p Q Q w j QQQ W QQQ W QQQ c 1a ❑zzz a ❑zzz a zzz a zz z aE- Q❑ N N N to R co O J r' V J e= t OJ J 2 U J e- V U Z 0 i Z Z O ffs Z i 0 1 0- 0 Q o c O N o N'° CT N 0 Z(N m z L" ZCO i ZCO L d Q. w Z N Cn o. aa N C Q N C C' c4,0- `2 C t2 V h z V'' V V a1 3 w 0 r ,4) t (t zz d V ZzZ ro a x zzz d a zzz a O o. m Z w I o o❑ l m om T uj 0 W W c, la 0 W v N H> O W E W 14 LU E a E R R o CO a o, o t a n I. a N a a QQQ co a a p m en zzz c zzz Z co zzz z co zzz i-0 Z t!) Z to u) 0 O 7 w 5 0 a c d c, Z a C, Z d c, C z fl Z W -C d Z(/) r m to .c m to .c y to 0 CJ 0 -I 0 CJ 1J Z 4- is W C3 (0 V' i W i o i i w h a R i N c co c d v c d c d v" J E 2 n3 Nu) 2 as N m E.,„ co co NN `o H E in 0 T- 0 c 0 c N C v a, O t6 M lC t r la L a., E V) co U) u) co 0 U) O t j C p t ,....<0 v d V V V O y 'O COW u) W u) CO CO fn L v N d co N a 0 a 0 X 0 X 0 d m C x x v E al a 1 t a t e E L 1 1 1 2 s i i i R C c Co 0) CO Cl) 0) C Cn d 7 t O o. a y O d C y d d a, y d a, 3) a, a, a) O E c c c c 000 _,0 a u O Cq a O L O Lo L O to 0 a, y O w P. o t-°- c- 1- 0 0 E- o c° a- v r M M M e- M a k 1 29 SnapNrack SERIES 200 GROUND MOUNT INSTALLATION MANUAL LL t CC W W CA Z N 411111111111111141 N ‘4,:-.:4 CI 0 0 11\1Ik"" W M U) 0 W \V.-4 O 0 N N ce 2! a z c H O (n P w oo sa r H H 0 O (n LLJ H Q d K K c.D oQWO Z_ z w m 0 x x H W O W W s a ›.W OU k 0 O(na(7cn w 0 0 0 0 0 0 2 t 0 0 0 0 0 0 T, N N N N N N o g a (n (n (n (n (n (n W W W W W W T om_ W W W W W W ea -E (n (n (n (n (n (n ine owm NNNNNN r i i ,--I ,-1 1--1 -L ,-I o b =i 0 00000 4t °te N N N N N N a =or. O I N on in uC d -8 O 00000 °y 0 0 0 0 0 0 O 0 0 0 0 0 LA Ln Ln Lfl LJl Lfl tin 2 01 01 01 01 rn on (n (n (n (n (n (n O i vn t 30 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL f f w 1 W EMilill ii r X04 3 Ill o m ^wa` Q III Ww g ym W o y�a n IX iiiiii H N u. w CC ILI o z „g W II g s a O Q W li 0 z W I all? y? l� w r__ P. c Vi \„=go Wpm s N o 4, o N 5 w 1s:o;:PTA: oos mbU ..1 20 ��g 0 6;1'' m u U W W .o 1 z 8 i ...1 a cece tu en Q a Q x� 6o Wo f f I CC *;m< w a _::::,.;:t L,P. 5' w Z as cc rm Z w w Q n El i 0_ r F Q VI lw/l U W i Q 144 Q c� in z 0 a a d O W z x 0 D o° Q H 1— 0 W ZDF DK Z ,-'-'m V (U LL C7 Oww� p. Z Z w crl- z0r a s z cu wpa ZazOa¢¢¢ 0 U U1wto DVIwLLQ£EF 1 31 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL 2' §1,C u E I '‘',9..a' (0) EX 1- el l E g E Mi 411, 2 R b 1- tir 5 o §!!e WO z gn2 F O t- t O -qi tn LU 411 ..E_. 2 2 )$E| w Cd e: e /i/§ p q 2 2 t a G; k ig z Y z o IN °i w 0 0 0 Q!£) 0 l c& ire IC E R o \mw mL (k& j 2 ,o 2; m m 2 .2.. o 7 K i ';:--1- g y I z 1.7 21': 22 2 xt ,,t' b g j 2 7 r& w a 0 vt 32 1 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL u_ il w pp A w F F Go �j OZ 22,4 a �1 8 mz00 0 a W Z wo c N F u T,F3 k ga aojW8 ow O w¢ <p J HHO1-n1=81 H z uw u+n+ a Oil °u w wNF.F� °C9F.w00 -w CI O _D >aH �i ce zW W u10 ce W M CL 0 0 N tn W N 3s »Q m E6L MMNIMMIMMIIME WEE E\ \L1. CD N CD wgZ R. o 0 Pk W 6 a (n a ut tn z a w W u W w w S 2 a a u u f f U' 6 25-r 2 a F0t a o f5m Idil INN w S or aft. 5:z,e •s liami iao.E. qii ag o V Z c vic I 33 CO �2r� ru� gea, 4 ,k2s7 Lty(b-z,d 1 SnapNrackrM SERIES 200 GROUND MOUNT INSTALLATION MANUAL u_ g AV -''''''''4 Mml .11 igr", a. 8 m W�'o Q ioo Q s W4 MI Allow m l— k::::..,.: tt CO r�i��i N xru I/\ �oLL_ LLI tribizi‘ (i) AL\ PPrOK e u-, Iii rS b O N c, I I=I c, at I w cc cc x I oa I N Q a h O i L Z Di N g w 0 o J a o. I"- to w a *L. .k ,pauV 13 6 Q U z g 3 G Lc w W3 o W U w Z U. q ai!Ing m. �Li z w J sse .t�3:•4 g 0 w O z o /j o 0 0 Q U w z s i Al z Z 2 w s rr d P H g j S,F Z Z h li F 0 "t° �M cc Q zQ Q¢ �n�� vi0 ,5---1 wH 0_ u) w 0 cc QL cc u_ w' £W -J�xxx UU t',5 n. Z co O g* v 1 35 SnapNrackTM SERIES 200 GROUND MOUNT INSTALLATION MANUAL SnapNrackTM 10 year Limited Product Warranty and 5 year Limited Finish Warranty Limited Warranties: SnapNrack, Inc., "SnapNrack environment for which it was not designed. As used warrants to the original end -user of the Product "Pur- herein, the term "chalking" refers to the powdery residue chaser at the original installation site "Site that the formed by the breakdown of the anodized finish, and SnapNrackTM PV module mounting system (the "Prod- excludes any foreign residue deposited on the finish by uct shall be free from defects in materials and work- the surrounding atmosphere, including, but not limited to manship for a period of ten (10) years (the "Limited soot, dust, plaster, cement, etc. The Limited Finish War Product Warranty"), and the Product's anodized finish ranty is void if normal maintenance and cleaning practic- shall be free from visible peeling, cracking or chalking es are not followed by Purchaser as specified by AAMA under normal atmospheric conditions for a period of five 609 610 -02 entitled "Cleaning and Maintenance for (5) years (the "Limited Finish Warranty") (collectively, Architecturally Finished Aluminum," a copy of which is the "Limited Warranties The Limited Warranties shall available from SnapNrack or from www.aamanet.org. commence on the earlier of (a) the date the installation of the Product as part of the original solar electric system SNAPNRACK MAKES NO WARRANTIES, EXPRESS OR IM- (the "System is complete, or (b) thirty (30) days after PLIED, OTHER THAN THE LIMITED WARRANTIES MADE SnapNrack ships the Product to the authorized distribu- HEREIN. SNAPNRACK EXPRESSLY DISCLAIMES ALL tor or retailer. If, within the warranty period the Product OTHER WARRANTIES, INCLUDING IMPLIED WARRAN- is determined by SnapNrack to be defective, based on TIES OF MERCHANTABILITY OR FITNESS FOR A PARTIC- reasonable evidence of a defect provided by Purchaser, ULAR PURPOSE OR USE, TO THE FULLEST EXTENT PER SnapNrack will, at its sole option, (a) repair the Product MITTED BY LAW. TO THE EXTENT THAT ANY SUCH IM- or replace it with an equivalent product, or (b) take back PLIED WARRANTIES CANNOT BE FULLY DISCLAIMED AS the Product and refund the purchase price to the Pur- A MATTER OF LAW, THEY ARE LIMITED IN DURATION TO chaser. TEN (10) YEARS FROM THE DATE OF ORIGINAL PUR- CHASE. Conditions, Limitations and Exclusions: SnapNrack is not responsible for, and Purchaser hereby agrees to TO THE FULLEST EXTENT PERMITTED BY LAW, SNAP bear, the costs of any on -site labor and any costs asso- NRACK DISCLAIMS ANY LIABILITY WHATSOEVER FOR ciated with the installation, removal, reinstallation, ship- ANY SPECIAL, INCIDENTAL, CONSEQUENTIAL OR PUNI- ping or transportation of the Product or any components TIVE DAMAGES ARISING FROM THE USE OF THE PROD thereof for replacement or service. (Note: the foregoing UCT, OR FOR OTHER LOSS OR INJURY RESULTING FROM may not be applicable to consumer sales in certain juris- ANY CAUSE OF WHATSOEVER ARISING OUT OF OR RE- dictions.) SnapNrack may, at its sole discretion, use LATED TO THE PRODUCT, INCLUDING BUT NOT LIMITED new, remanufactured or refurbished parts or products TO DAMAGE OR INJURY TO PERSONS OR PROPERTY, when repairing or replacing your Product under this war- DAMAGES FOR LOST SERVICES, COST OF SUBSTITUTE ranty. Any exchanged or replaced parts or products will SERVICES, LOST PROFITS OR SAVINGS, AND EXPENSES become the property of SnapNrack. This warranty is ARISING OUT OF THIRD PARTY CLAIMS. extended only to the original end -user purchaser and is not transferable, provided that as long as the System SNAPNRACK'S MAXIMUM LIABILITY UNDER ANY THEORY has not been physically moved or altered, any subse- OF LIABILITY, WHETHER EXPRESS, IMPLIED OR STATU- quent owner of the System shall have the same Limited TORY, OR FOR ANY MANUFACTURING OR DESIGN DE- Warranty rights as the original Purchaser. FECTS, IS LIMITED TO THE ORIGINAL PURCHASE PRICE OF THE PRODUCT. The Limited Warranties do not apply to Products installed (a) outside the U.S.A. or Canada, or (b) in corrosive at- To the fullest extent permitted by law, Purchaser's re- mospheric conditions, including, but not limited to chem- medies for breach of warranty, or for manufacturing or ical fumes, salt spray, acidic rain or surface tempera- design defects, shall be only as stated herein. Snap tures which exceed 200 degrees Fahrenheit. The Limited Nrack's Limited Warranty covers only the Product, and Warranties do not cover damage to the Product's ano- not related items such as PV modules, roof flashings and dized finish caused by moisture, condensation, or other specialized clamps. Manufacturers of such related items contamination resulting from improper storage, packing typically provide written warranties of their own. or handling. The Limited Warranties do not cover dam- age to the Product that occurs during shipment or prior Warranty Procedure: Purchaser should contact the to or during installation. The Limited Warranties shall be distributor or retailer where the Product was purchased, void if the Product is not installed in accordance with or if unable to do so, contact SnapNrack, Inc at: (805) SnapNrack's written installation instructions for the 540 -6999, info @snapnrack.com or SnapNrack, Inc., 775 Product, or if the Product has been modified, repaired, or Fiero Lane, Suite 200, San Luis Obispo, CA 93401. reworked in a manner not previously authorized by SnapNrack in writing, or if the Product is installed in an SnapNrack Warranty (October 2010) 36 CITY OF PORT ANGELES DEPARTMENT OF PUBLIC WORKS . . . . . INSPECTION REPORT. . . . . . REQUEST: Date (0 -:3 i-OS- Time 7 Aoc"-- Received by IJ.e....f/ I S E (phone, person) Location of Work to be inspected ::; ZO 7 M" IJ I ~ '5 +-. j) .' Name of person requesting inspection eV/....., ~ C. Address of person requesting inspection c.u.-, () ~r) II 'f g Phone No. t{ I 7 -..( 8<f9 t Type of Inspection (circle appropriate one): Permit No. Sewer Foundation Framing Chimney Plumbing Final Sewer Excav. Oth0 +e 7 INSPECTION NOTES: Inspected: Date 10 -r ,-0') Time 3: 50 PM Remarks: /!.et'la..ce 51'! 5""v(~~ /(~ -P.r.e"'<. ( By De,,-,,,-:<; E . IV\. "'-I "vi -+r, iYLe .-f-e r . RESTORATION REQUiRED...... YES IX- NO f~we-r~s-r 0 '" ~ , {:. )- \f) v ~ ~ ~ ~ N ~ SURFACE RESTORATION: L(Y..C:; - 2:><- ZO' SURFACE TYPE: 0 Unimproved DGravel gfAsphalt 0 PCC 0 Other Work Order # go 3<.( "-07 g IXf COMPLETE 34105 -I ,I '2-0; o INCOMPLETE I I J2/7/0SiF u o Repaired by City o Repaired by Permittee o No Damage Found ~ S i-vpe-l ~,.... --:.II:.__.......oo....u\ CTDCE:T CIIDCDII\ITCf\.lnI:I\IT In^Tt:\