HomeMy WebLinkAbout2000_Masonry Shear TestsGENERAL TESTING LABORATORIES, INC.
18970 Third Avenue NE P.O. Box 1586
Poulsbo, Washington 98370
(360) 779-9196 Toll Free (888) 898-8378 Fax (360) 779-4320
May 4, 2000
Clallam County Historical Society
926 W 8`" Street
Port Angeles, WA 98362
Attn: June Robertson
Re: Masonry Testing on Museum
General Testing Project No. B9224
Dear Ms. Robertson:
General Testing was asked to perform In -Place Masonry Shear tests in different locations (see
ATR Engineering Layouts) on the future Museum in Port Angeles.
This required carefully removing the head joint without disturbing adjoining bed joints in
testing areas. Steel loading blocks were then fabricated to fit the size of the end of the brick to be
tested, and calibration of the hydraulic ram to be used was then done (see calibration sheets). This was
all performed on May 2, 2000. On May 3, 2000, actual testing took place and all test results are
included.
We understand that a minimum of 30 PSI was required, and all tests exceeded the minimum.
If we can be of any more help on this project or if you have any questions please do not hesitate
to give us a call.
Sincerely,
WobArnot
Technical Director
Cc: Art Rack ATR Engineers/Charlie Smith Lindburg Smith Architects
BA/be
Quality Assurance for Northwest Construction
GENERAL TESTING LABORATORIES, INC.
18970 Third Avenue NE P.O. Box 1586
Poulsbo, Washington 98370
(360) 779-9196 Toll Free (888) 898-8378 Fax (360) 779-4320
IN -PLACE MASONRY SHEAR TEST
UBC STAND 21-6
Client: Clallam County Historical Society Date: May 3, 2000
Project: Clallam County Museum
Inspectors: Stephen Blaney, Jim Comnick
Project No.: B 9224
Gauge Readin
Test No.
Location**
Heise
Marshall
Hydraulic
Pounds
Force
Mortar Area
(sq. in.
P S I
1
41
2700
--
2480
64
39
2
#2-Below slate board
--
10,000
9574
64
150*
3
#2-Above slate board
--
5400
5144
64
80
4
#3
--
7800
7455
80
93
5
##4
--
6200
5915
64
92
6
#5
--
6500
6012
80
75
7
46
--
9300
8900
80
111
8
#7
2600
--
2384
64
37
9
#8
3000
--
2769
64
43
10
#9-Above slate board
--
5300
5048
80
63
11
#9-Below slate board
--
6400
6107
80
76
12
#10
--
5100
4855
80
61
*No Failure
**See locations as per ATR Engineering drawing
Field Supervisor
Quality Assurance for Northwest Construction
0
W
E
0
s
w
a,00R I WALL LAYOUT
wwww
kL
bt SPt-1
L-L z u 0
gZo�N►g
)> coan co m
m
2 (D Z m
f o - %i 0
z�m A
D p "'
i� ��
c0n—
co Z
p"i es7— 7;t>� cv*tG S
m
T rRc n�P�
g� A-C-rupvK w -S. -> 6k.
C Z
r
V.00f-
out
m ermw i Rij
RLL- )0 P*-7
I
LL_ 172,5P
LJ V V U ReArD jlsj�
I-Lo W
'``fAI_ n-= Z WMI LAYWT
N�
�� .
L� �wf
��LnOCtq+-rb �STv�Y A44c.CS
�a ¢ pc�c�s
CALIBRATION OF HEISE GAUGE
ON THE HYDRAULIC PISTON INSTRUMENT PANEL
FOR SPX 5 TON NO. C51C MODEL B RAM
Heise
Gauge
Pounds
Force
100
86
200
178
300
270
400
362
500
453
600
545
700
637
800
729
900
821
1000
912
1100
1004
1200
1096
1300
1188
1400
1279
1500
1371
1600
1423
1700
1520
1800
1616
1900
1711
2000
1808
2100
1904
2200
2000
2300
2097
2400
2193
2500
2288
2600
2384
2700
2480
Heise
Gauge
Pounds
Force
2800
2576
2900
2672
3000
2769
3100
2865
3200
2961
3300
3057
3400
3154
3500
3250
3600
3347
3700
3443
3800
3539
3900
3635
4000
3731
4100
3827
4200
3923
4300
4020
4400
4116
4500
4212
4600
4308
4700
4404
4800
4501
4900
4596
5000
4693
CALIBRATION OF THE MARSH HYDRAULIC GAUGE
ON THE HYDRAULIC PISTON INSTRUMENT PANEL
FOR SPX 5 TON NO. C51C MODEL B RAM
Marsh Hydraulic
Gauge Reading
Pounds
Force
200
137
400
330
600
523
800
715
1000
908
1200
1100
1400
1292
1600
1485
1800
1678
2000
1870
2200
2063
2400
2256
2600
2448
2800
2641
3000
2833
3200
3026
3400
3219
3600
3411
3800
3603
4000
3796
4200
3989
4400
4182
4600
4374
4800
4566
5000
4759
5200
4951
5400
5144
Marsh Hydraulic
Gauge Reading
Pounds
Force
5600
5337
5800
5530
6000
5722
6200
5915
6400
6107
6600
6300
6800
6493
7000
6685
7200
6878
7400
7070
7600
7263
7800
7455
8000
7648
8200
7841
8400
8033
8600
8226
8800
8418
9000
8611
9200
8803
9400
8996
9600
9189
9800
9381
10,000
9574