Loading...
HomeMy WebLinkAbout2140 W 18th St - EngineeringClient: Golden West Spraybooth Project Engineer: Kevin ~liI ;r Order Number: 3053017 Reviewer initials: Product: Paint Spray Booth Model Number: ATDS Test Sample Number: 03-3666-A, 03- Date: 30 December 2[ 03 I Standard: NFPA 33, 2000 Ed 3666-B, and 03-3666-C, production units installed at West Port Shipbuilders in Port Angeles, WA Par. # Complies Comment CHAPTER 9 AUTOMATED ELECTROSTATIC SPRAY EQUIPMENT 9.1 to 9.5 N/A No such spray equipment used. CHAPTER 10 HAND-HELD ELECTROSTATIC SPRAY EQUIPMENT 10.1 to 10.5 N/A No such spray equipment used. CHAPTER 11 DRYING, CURING, OR FUSION PROCESS 1 1.1 N/A Genera{. No separate drying/curing apparatus, Drying is incorporated by heater in the listed air make-up unit, 1 1.2 YES Spray Enclosures Used for Ambient Air Drying. Spray booth can be used for ambient drying. Provides proper ventilation (same as when painting) and does not allow vapors to exceed 25% of the lower flammability limit. 11.3 YES Spray Enclosures Used for Drying et Elevated Temperatures. Because of heater in air make up unit the enclosure can be considered to be used for drying at elevated temperatures. 11.3.1.1 YES Interior surfaces are smoothed and easily cleaned. YES 11.3.1.2 Spray booth is provided with a high temperature limit switch that automatically shuts off the drying process if 200 °F (93 °C) is reached. (Note - UFC required a maximum of 160°F.) Temperature setting of the booth set to exceed 175°F (71 °C). 11.3.1.3 YES Control interlock is provided so that the spraying cannot be performed during the drying or curing process at elevated temperatures. 11.3.1.4 N/A No radiant drying apparatuses are used. 11.3.1.5 N/A No radiant drying, curing or fusion apparatus are used. 11.3.1.6 N/A No radiant drying, curing or fusion apparatus are used. 1 1.3.1,7 N/A Operations are not part of the manufacture's responsibility and are not part of the scope of this evaluation. Containers of flammable or combustible liquids are the end user responsibility. 1 1.3.1.8 N/A Operations are not part of the manufactures responsibility and are not part of the scope of this evaluation. Automobiles are not the product sprayed in this operation. Used to spray cabinets for yacht interiors. 1 1.3.2 N/A Heating is performed in the same room as the spray application. Spray application is interlocked with the heating cycle. Client: Golden West Spraybooth Project Engineer: Kavin Mllel ~,~,~ Order Number: 3053017 Reviewer Initials: Product: Paint Spray Booth Model Number: ATDSI~OP[: Test Sample Number: 03-3666-A, 03- Date: 30 December 2003 Standard: NFPA 33, 2000 Ed 3666-B, and 03-3666-C, production units installed at West Port Shipbuilders in Port Angeles, WA Par. # Complies Comment 1 1.4 N/A Flash-Off Areas. None provided 1 1.5 N/A Ventilation. Fusion apparatus are not used. 1 1.6 N/A Warning Signs. No drying, curing or fusion apparatus are used. CHAPTER 12 MISCELLANEOUS SPRAY OPERATIONS 1 2.1 N/A Vehicle Undercoating and Body Lining. Spray booth is not used for this application. 12.2 N/A Preparation Workstations. Spraybooth is not a preparation workstation. 1 2.3 N/A Limited Finishing Workstations. Not considered as a limited finishin~l workstation. CHAPTER 13 POWDER COATING 13.1 to 13.12 N/A Powder coating is not performed. CHAPTER 1¢ ORGANIC PEROXIDES AND PLURAL COMPONENT COATINGS 14.1 to 14.9 N/A No such coatings used. CHAPTER 15 STYRENE CROSS-LINKED COMPOSITES MANUFACTURING (GLASS FIBER REINFORCED PLASTICS) 1 5.1 to 1 5.7 N/A No such application is performed. CHAPTER 16 TRAINING 16.1 Yes All personnel employed are properly trained to use equipment and application. CHAPTER 17 REFERENCE PUBLICATIONS 1 7.1 -- Referencing NFPA Standards to be considered for particular portions of this standard. ETL SEMKO ~t~ Intertek Report No. 3053017-1 Issue Date: 12/30/2003 Attachment Three: Resolution of Discrepancies Clause No. I Discrepancy I Resolution None ETL SEMKO Intertek Report No. 3053017-1 Issue Date: 12/30/2003 Attachment Four: Testing The product was tested in accordance with the Standard for Spray Application Using Flammable or Combustible Materials; (NFPA 33: 2000). The following tests were performed: Note: Evaluated for construction only. No tests performed.