HomeMy WebLinkAbout509 S Lincoln St - Building16 January, 1998
Jay Ketchum
Dive Shop
509 S Lincoln
Port Angeles, WA. 98362
Subject: Response to City of Port Angeles Building Official
Dear Mr Ketchum,
Gene H. Unger
Consulting Engineer
Cavil Structural Management
1401 West 7th Street
Port Angeles, Washington 98363
Office Fax (360) 452 -2098
In response to the City of Port Angeles building official letter dated 13
January, 1998, I am recommend several things happen It is important to bring
this building back to a safe condition for the customers of the businesses housed
in the structure This can be done by the following
The roof structure needs to be supported with temporary walls parallel to
the existing East -West walls within six feet on each side
The front wall needs to be braced or scaffolding erected to allow
pedestrians the use of the sidewalk and protection from possible front wall
movement.
Once this is done the building will be safe to occupy on a temporary basis
The concern then is the fact that the following items need to happen to bring the
building back to permanent use
•The unreinforced masonry walls and footings need to be removed and
replaced with new foundations and concrete masonry walls up to grade with new
support beams for the roof structure This includes interior and exterior walls It
is important to recognize that the bringing of this walls up to grade is very
important. This will make the roof work to project the structure-underneath from
moisture
•The front four to twenty feet of floor of the building needs to be replaced
along with the front wall The front portion of the building will be brought up to
level when this work in done
•The front sidewalk needs to be replaced with one that slopes towards the
street as the original one did
•The roof drainage system needs to be replaced and connected to the city
storm sewer system
•The addition in back of the pet store needs an entire new roof system from
the block walls up
97034R4.DOC
PE.
•The water service lines to each of the building section needs to be rebuilt so
that it is isolated from the structural support system Individual meters need to be
installed to each unit.
The roof structure needs to be evaluated for minor repairs where roof leaks
have compromised some of the members.
These are the items I feel are necessary to bring this building into safety
compliance Anything less will leave the building in a questionable state which 1
would not want to be responsible for Thank you for using Gene Unger
Consulting Engineer on this project.
Sincerely,
Gene H Unger, P E.
incl., Copy of City of Port Angeles Building Official Letter
cc: Lou Haehnlen, City Building Official.
1
97034R4.DOC 2
M ranREs 3- /7--
1
321 East Fifth Street, PO Box 1150
PUBLIC WORKS Port Angeles, Washington 98362 1150
UTILITIES
January 13 1998
Mr J Ketchum
509 S Lincoln
Port Angeles, WA 98362
RE. Structural stability of entire building located at 509 S Lincoln.
On December 12, 1997 your Structural Engineer requested the Building Department to
accompany him on an inspection of the above mentioned building, upon completion of the
inspection, the Building Department had concerns regarding the structural stability as well as the
Life, Safety issues such as the ability to exit the building due to the settling of the front wall. At
that time the Building Department sent you a letter requested you to vacate the entire building by
January 1 1998
It is apparent that you are having problems vacating, therefore the Building Department is
requesting that you direct your Engineer to provide a method of stabilizing the front wall, and
supporting the roof at the interior dividing walls. If you do not respond within five working days as
to your intent the Building Department will post the structure UNSAFE and there will be no one
allowed inside the building. This notice includes the Dive Shop Collection Agency and the Paint_
Store.
In the event we have snow or seismic movement the your Engineer needs to check the structure
for movement or failure.
or
o Haehnlen
Sr Building Inspector
Since
r_
CITY OF PORT ANGELES
cc: Gene Under Structural Engineer
Gary Colley Attorney
Phone (360) 417 -4805 TTY Phone (360) 417 -4645
Fax (360) 417 -4609 pubworks @ci.port- angeles.wa.us
CITY OF PORT ANGELES
tIGHT DEPARTMENT
ELECTRICAL PERMIT
N~
17864
/--3r 23
Port Angeles, Washlngtonmm._m............_.._m..mm...m......mmm, 19.___.m
In accordance with the City Ordinance to regulate the installation, extension, or repair of elec-
trical equipment in, on, or about any building or other structure in the City of Port Angeles, per-
mission is hereby granted to do El!ectrical work as listed below.
j~OY k c:i' ~ ;
~=.~:o~~~~Bi~i~::~:~~~~;=:=~~=:::=:
/ /;/ (~ /;;J:/?
Light Outlets..............._.n................_n... Service, volts .-....---3-~7h-.........h..... Type ot Wiring:
Receptacle Outlets..........n..n............... No. wires .........................00.00..__:0000 Armored Cable ..._..._00..___..'............
JY{)(Q
Size wires....".7)fo';;..>~,_..
Main fuse n_.nn.n............................
--S
Enclosure ._._00_00000000..000000................
Dryer, KW n.n.._.un.........._............______
Range, KW..__.n_...
W'ater Heater:
K~ "--'/?2--"/3/T
Heat: KW h.__n.._ 00_.....00_ n_h' .......... ._
Type of wiring:
Entrance Cable nhu..._.............___...
l\:otors: size, volts and phase:
Rigid Conduit
MetalUc TUbing ..u.........nn..n
Current transtormers:
No. & Size............_____nn__nn..
Ser. NO..nh......._n......_.__..._......_nn.....
Ser. No. nn.nnhn.....h_........................
Ser. No. .nn__n.hn..._._._....................h.
Non-Metallic ._..._..._...................____
Knob & Tubenn..nn........................
Rigid C<nlduit ___"______"",___,____",,...
MetalUc TUbing ......._..._.........._....
Raceway _._............................_._...._
Circuits, Light.__.............____.__._._____........
Utllity,________,___,____,,___,.________._________.,
Heat ...............-..-..-..--.....................
Range ........._........_____...................._.
Water Heater _........000000................
Motor ..........._....nn..nh....._........_.._.
Dryer _nn_un....................n__n_...nh...._
Furnace .. ....._............._...,~___........._......
Total Loa~~~~______~= ~_ :'" NO;;--='"Jf=y'-- Total ----------------------.------------
Remarks: _____._m._m__nn"'nnmnn~.~mm..___n__n_____.._n_.m__...m.m......m.m...mmmm_____.____m.mm.m
nhm.h_hm.m.___._mm___m._.__m.m___mhn._n__nmmh__mm_m_m._hm'm_.__.hmm.m._".mmmmm.mm..mm.-nm%'
Permit F;e Treas. Receipt 11_ c.P (, / ( f. /, . > "
//100 I!~ r/r It/U</"u::?/(a-
$m..m..m....mmmm.________ NO.m....m.__............... By n_____-'__.__.:__.C.__...___n__________m___mn'-'..2____n__ ""'"----,,
/ .
NOTICE-Current must not be turned on until Certificate of Inspection has been issued. It work is to be eon-
cealed due notice must be given the Inspector so that work may be inspected betore concealment.
NOTIFY THE INSPECTOR BY PERMIT NUMBER WHEN READY FOR INSPECTION
ELECTRICAL PERMIT
N~ 17864
Address._..___.____.__..___.._...................._.........................._......__...._....._..._...__..__................_.....__......_..Date..._....______..__._._........_......_......_........_
Owner..................._......_....__________._..._.._.___._...._.._...__._................_...__............____.__._....._._.Tenant........................_........_......___......_.......___....___.
'\
WiringContractor._.._.....______........._._........___..__.______.___._..................____...____.._____.._..___.._____._..._..._____.BY____.____________________h._.__......_...__..................
NOTICE-Current must not be turned on until Certificate of Inspection has been issued. It' work is to be con.
cealed due notice .must be given the Inspector so that work may be inspected betore concealment.
1M Olympic Printers, Inc.
CERTI F:,llGAt~~~;;@;F~:;o~~u P ANCY
t!'" d~\t\f;. \,.j.\Q~'~""'}.\;.ft'~1;;~11'';-",':::''~^ c. ,.... .....\9-
,,:;t<' ,.\,--"City 'Of~PoftfAlfeles ..t'~
"- t "I' - "I~'('~\.),~ Iii:.... ''''':~'~' g, , ~41 .'t" ~\~,
,~ ~ t 'l\.' ~"H'l,{ -, ,-,"'-' \ ,. ~
' Building"'\DiViSiOJf~ I:', ,'" \;t,.
. I ' \ 1-~<
I .;', " ,}.~".tr;,,-. ~\>
~his ~~rf!#?~~\)'(' 'i~~?:~~i~f!!~/~ the req.uiro/!!.~J,y{%[Secti~n'f~p9 of the
Uniforml!ffj?4i ,'JI,j/e cenifil~g,JlrirdJ:z,t!htU!,!,e~qj!JI~a~4)ls stiit,cture was
in com iiimae'~wjth' the ;Wlrt~i..' ~:: ~,j~iit:~~ 1Jiih't'GiifA!6.Iliiilif m'ildin
,'. ~ ,.t\' 'l':';'{, ,\~, - l.."',"I:lr',7;~'f:r! ~ \~1 G~~"\'~;;<....~,I;J~,,'l>- ~.LI"l g
i; :' ;, "j cr. constnl ' ";Ror'the"" ' \\}
..- ~ ,"~, ' l' :'.
~~
~
Use Classification Off' ii:;
'v '
Group B :1 ,"""," ,ITypeofConstruction "','", ""n'~'''''.'''j ".....' ,,"'j'" 0.'.'.... )~
I'"' ~'(:5, 'il1.'~':~,~ ,)"~.>"",,....I tfi 'I~"<~" ..,\"~ ,," ~ I ,~\, ~!,,~ 'i:~), 1 .
Owner ofBusinessIResiden~;J.a:Jifain County Republdlcan': _ ~ddressP. O. <Bbx,~:'8Q@ Port
"{_. ",~y~< 4~( ,ll "'Part . ,t,i.~~tJ,i}h7tI~:~;.~.:.(h",%;t'<.::'i\.:".71/'{\\"'fe,,~~'i;I'i~rl"~jJ/~l ~;~
", :es WA.
CSD
Angeles, WA
362
- .
B V'f\/
ROUTING SLIP
Certificate of Occupancy
$47.00 Certificate/Inspection Fee
DATE '":Pee>e..m Dell'"'
--'
Brief description of proposed business:
New Business ............................ (
Transfer of Business location. . . . . . . . . . . . . . .. ( ~
Change of Ownership . . . . . . . . . . . . . . . . . . . . .. (
New BUilding ..... . . . . . . . . . . . . . . . . . . . . . . .. (
Remodel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. (
Temporary Business ...... . . . . . . . . . . . . . . . .. (
Change of Use. . . . . . . . . . . . . . . . . . . . . . . . . . .. (
legal Description: lot $ ir q
Current Use of Property:
Zoning Classification of Property:
Block 1.l.(()
{/ /4-el+-lLlr
r!--Sn
Will THERE BE ANY OF THE FOllOWING?
YES NO
Construction changes
Electrical changes. . . . . .
Mechanical (heating, cooling, stoves) . . . . . .
Plumbing changes .....
New or relocated signs
New septic tanks
New sewer service .. ..
Admission charged to patrons
Is this a home occupation?
Excavation of filling of lots .....
Work done In City right-of-way
Is there sufficient off-street parking?
New dnveway openings
A grading plan for site drainage
(parking lots, downspouts, etc )
Are the eXlsllng streets paved? ......
Are there eXisting Sidewalks?
Is there curb and gutter?
Other
I hereby apply for a Certificate of Occupancy and acknowl-
edge that I have read this application and state that the
information I have supplied is correct to the best of my
knowledge.
REJECTED
Building Section
Public Works Department
Planning Department
Fire Department
City Clerk
P.B.I.A.
) zlrr /00
KDtJ
L-\ IZ//<tJOD
. /
Subdivision -FA
THE FOllOWING Will BE REQUIRED:
PERMITS
1) BUilding
2) Plumbing
3) Electncal
4) Mechanical
5) Sewer
6) Sidewalk Installation
7) Driveway Installation
8) Curb Installation
9) Sidewalk obstruction
10) Water meter Installation
11) Fire
12) Occupancy
13) Sign
14) Shoreline
15) Home occupallon
16) Conditional use
17) Other
BUSINESS LICENSE
1) Taxi
2) Peddlers
3) 2nd Hand Dealer
4) Pawn Broker
5) Dance
6) Hotel - Motel
7) Fireworks
8) Ambulance
9) Tattoo shop
10) Other
Date: .j)...J2e.., ,t:{ I 7.....000
Signed: LlJ--4 ~ f&-l~
Comments / Conditions
0" :s i -k- 0.::
.J; -\'1 bb( <:L, etL./
if
4
f t,4
Of T tiJ 12.-
0 hi ft■C- 1.11 Wt.:wt t4
!Jew) 112.t`GD 3. kti wow
o 1.,ck
Lotse.,egek
1 /11,09°)
.70c. (-IAA. Q1_414,000
p,&- 1-A ce
e, I 6-0%
1-As
5i G to
L.
_11.6 K.:V
e ROOS e. Y\ OVA t 7iNi r i.
NA. t ci
1
4
\A/ LA__ I D ec-rloovc,
etohk-
'6 we LAIL
ki Gtt.%
WtSila RtAlk,
'it N k -f■ -'2— i 7
El
VAe‘a, ith
Avw Ilecp*
oe..n
A*AL u)N car.
l2-
l'• COLS WC
cot_914 5 La GC ■e%
3.
igsp,u_ iiPs 2 omocelk._
4-
r
CfCct-)A3
14etu 9010 2.<4.
15 14 -S
fk it.r1 ko i.c.tvg
To
0
.ar•
co
..r
-i
oieeeikaavbralesaisienamurriaccAras
Ziii144*S*414.1iikistro*..,: .0. ivima tiattor.isevrier.4,0
o rufw1
S
111.1sClo.
47
Ns.
rfivf AC
N
IA) 0
I.
.2 lr
IT
fro 0 •es
,2 7;
'p
E. 3 I•4
1
goilsausliiila.
Bo!. oil
A 1 r
Aoc
r
■it
I 4 2 —31 itc 1 X 3
4
Ea2)01
P'1 5 (75
R 1 aw
‘e4 4
P !;•/(1 k
'v(14 I 011 .P4 f te ev
1_ a t t 42 A a
4,444
T L v it
e 6 z 57-1)
I
/0
fn -4 P
o
ii6?fl 1f4
ife froA
f
io 4 i4 /i 4
....•pfnip
vol ,k1
14 14
t
A 14
00 u'
000
mm m
in tn
mm m
-I -I
(41
kire-tr tot.
7 4•6
st9 O ,t_te i d- )1
,e
I
Ce
oe
s
P w
7
c
As
Tes 01
EX I '4 77:- 0'4 /4 14-4
1 7C-e:s Fair
leer e 4 s A
h 6 _C-0 e
,/i" (0.
0
W■ce/,
fAA!f, /Lt _4f_i4
r et f-
/7 A4. e 1 78
If 1;677.
r.e ki II eir; cectc Ited
s.e 'rr-4 4 €40..de
,/.2-P
A
)T
f(iT
y k
Awe- e <raser w
AP-et:1e hoe 4 lie.Tico-w Se.A D
-'t
al/
1767
s e l/ 3 t o
1
(.00#.1 -rnee AS Z_
v/ 8 &»tt Ree-A--e.weatf.e5-
11. ?fr:
eY tt Fines 6).-6 Oti VCCA.77-
1-
K A
t n
141/,' Pit' 2
L e;..„) .f 04
;t r
1/ h 1 ilecl( O /4/4`151.70jr
n) 1
2/4-e, c, _7) atirr )0A
a o It,
11 8 II s'
4SM.
k OM.-
0
L ",1 /1 .0
7 /tht '96'
717 I .17
VI VI US
XII
UI IA all
000
'flee
Cl
el V
CV C4 CI
1
,,e1 6 a,
re--€ ,Vs; A5
Oack
/ii
Pi f
e-C-
17 1 711
etitg 073
t/86
Rd (-5) e (3)E F39t
/6r a_ fry? e_ 4 c-110 ot)
472-14 4
1 er G-
p 6 -,17
-7}k
C e e
e z
A
(gles,P.
.3-ie: o 4. 4..__
1 k .7-7 S' I' i f
(Z 4 7,/
i
ifie. ..i r/:.& )5•.*4:7: IfY We Or ..eg' 0, r eiiiif P2.-
-bd. 4
ff 0
+-I tA el 1 i
i
0---ato,_d,
wi d o it 11 .__.i.1.776 I cid:a,
if% VI
111 MI WI
MI Ili 141
CA U1 In
000
In 0
Cl
C4 et
et et et
(4
C4 C4 C4
y e.1 psi
A
G
7 /14ov 18
.q go 73
&let de 1,t/
f I 0
g e (1?_;.
01^
v y/ 1-4 444
2- /f ere.' r`e
r
k14 yee.:44
j4 4L,
Jo, fit 4 6 7 1-- the_
4
e-r1.4 AY-14_04 14/44l• lt;tive,
7
4
Ar
1 CA-•••14 COI Z
6a-14 C. -V
fee. b
4 /e(sC
rave, ;Ir
4
7Y)0 /reel ect c„ hi,V w1
3
U J 7 C40-t/,. B
Tie, 7 3-
—3
-4
QL
Xt
b lock
fr-
,Ert t)9 P ege-••
leg/ .Werit
/6 "0,
2_.)e- P. G,
1.• ftag ixrDie
e$te
vi
1 i
e a
I
•3
r ere,k t
Se
Vi T sets! 4,
Th i
744
1 /4 X'-e7
i 1i, W e
—S JQ
it
pee cAe_, h.ol;
1 4 .5e_ .n V.147 fe. eltr, 0
,E.)cesti
t-res-o-
r 'f
/7 Are v
e
Teeick gt, RA!
M ie-kl.?.. fir c! its
gS
0 10 4
p se--
tte
76-
{A/
1..
III ILI IL
1141 Ml 41
X
tot
000
'fl
C4
et 4 .4
C4 CI C4
j ,Aei
#7: V,
F r'.07-z-t pv 4 1 .90c.o't
if .---/pf..(4.441
•-t
/I
d e.
(v- •003 Z
Ag A/0 tb frg a
9,007_s. )41
r /AP iot:r f
2.0 7 ,4
ee)
sio I Av e- kdA
1^. c
W 4
4. 1
4. t
0 t6o o i
hs
1
i
e/ i
C-41 I tit 144 S4 rog. t
4.1 at
j,i 1 (-Co f
e oet=-.(v7
i" k
6,
1
IA it 71 6 a
„---te -7 71
r
t
1.oT/ 000_4/
9
P
a M
ra /f. e7c 4l. ii'
I. r
sgx
Ca
fu-44t rt
/D Q ..c .0
e we
C,
G itc 10 r-- to
2H"
J c% u, K, r
9 r.t. by
paarrny new
AZ, d, 9
9' So ?_3
11 side e-fL co f it
-(r.e+1 .o.ve-.
i.o
2 Es p8
1 2Tr-
J
v 9%'
Ez. Bb
ad .4'ft
7
i!
Papbw 9
=F
aTrfS 00
J,1'? 3 d of De af
frM a' s a T Awasw J 4 f4 :2 u o a
y� ')-I "-9 y
0
N N N
N N N
AAA
AN
0 0 0
'Ix
us to in
mmm
mmm
-I 1 H
iA N N
4
).9_
"c" 4 eq .1
o d 4 :9 /P
j4 rt 147
t
S i ,se 2/
4 a- a...4 0 /iv .4 P i 0 0 1-1.40rner
a. i eolvi'v as lo/ ...1" yovatj --7 1 -.-AL- '4'35'
I I i
Al I.1 a.
kcq- l-i? ioA
irvia _4541 w vt■g:
7/ P /3
'»l"
-4- 'DO 0
f A
4 s0- 0. 110,M cf41• 1 1
tL ‘?.if
M /2 ix ti
0 tOt 4 a q 57/
4. y wt. a2 d
J 0 /?A' 0 4 ea.. a_p- i41
4
y 40 ,i) 144 /D
yi•%••/1 42 a
/P //k z
yora- a
00_14' 0) A 2157 a 451 kyr rp 0
1 41 49
r
4 November 1997
Jay Ketchum
Dive Shop
509 S Lincoln
Port Angeles WA. 98362
Subject. Condition Inspection of Building Update
Dear Mr Ketchum
97034R2.DOC
Gene H. Unger
Consulting Engineer
Civil Structural Management
1401 West 7th Street
Port Angeles, Washington 98363
Office Fax (360) 452 2098
I am pleased to have joined the re- inspection of your facility on 17 October
1997 I met Tom Bennett, P E of Pacific Engineering and a Geologist who
accompanied him to conduct a complete inspection of the potential water leek in
your section of the building
The time from 10 30 A.M until 1 00 P M was spent investigating two holes in
the concrete floor within the dive shop The first hole was under the sink location,
in the Northwest corner of the front shop This area was found to be very
consolidated sandy loam with good structural support capacity Estimated at
between 2000 and 3500 pounds per square foot (psf) An excavation was made
to determine the extent of foundation and found that the Block wall pilasters were
constructed first on a 24 inch square footing about 5 inches thick. These were
about 12 inches below the finished floor grade The block walls were then
constructed on a small concrete ribbon which I would not call a foundation yet in
extreme loading would act as one The slab was poured later and was
constructed with water pipes in the concrete as part of heating system This
heating system is no longer functioning The soil in all this excavation was found
to be very consolidated with very good bearing values
The second excavation was just inside the front door of the Dive Shop This
was aimed at finding the leak in the water line A leak detection service had
recommended this was the place to excavate We found a copper water pipe
about 3 inches under the surface at about 6 feet from the front wall of the store
The soil was the same sandy silty which was very well consolidated There was
no evidence of excessive moisture in the soil
Next the concrete surrounding the water shut off valve was removed This
exposed flowing water on the outside of the front foundation wall of the building
The flow was large enough to leak the predicted 2+ gallons per minute which was
what earlier investigation led us to expect. It also showed that the flow had
washed away portions of the soil near the foundation
Next the concrete in front of the North wall of the Dive Shop was removed
This was an area about 2 feet by 3 feet. The water was found to be on the street
PE
side of this hole at about 3 feet from the building The soil on the building side of
the hole was still sound and resisted probe intrusion very well
This investigation revealed some significant data which greatly effects my
original report. The significant items are
The soil under this building is significantly consolidated and is a very good
foundation base
•The main water line supplying the building runs North -South in front of the
stores It is in a position which is outside the foundation
The front wall of the buildings has settled from one to six inches since it was
first constructed This settlement has occurred in the front wall from the paint
store door, North to the center of the pet shop
•The water pipe was poured in the concrete foundation (no sleeve)
•Normal snow loading of the foundation creates a pressure of 2250 PSF
•The storm event created a soil pressure of between 3080 PSF and 4062
PSF
•The back wall of the building has settled where downspouts are not properly
connected to the storm drain system This has allowed the soil to saturate and
loose its bearing capacity
The conclusion I have reached as a result of this investigation are as follows
•The storm event of December 1996 created a soil bearing load which
caused settlement of the front foundation of the building
•The settlement of the foundation caused a crack on the water supply pipe
that services the Dive Shop
•The water flowing beside the foundation towards the North caused the soil to
soften enough to cause additional settlement of the West wall of the building
•The present deformation of the front wall of the building has the
characteristics that say previous snow events have loaded the awning to settle
the front foundation so that water pipes serving the other units of this building
have also cracked and compromised the foundation along the front wall of the
building The Photographs on pages 1, 8 and 9 show this settlement.
•The unreinforced masonry front wall and front ten to twenty feet of partition
walls have settled enough and separated enough to make repair impractical
•The front sidewalk has settled enough to drain water towards the store fronts
instead of away from them towards the street as originally constructed
•The roof drainage system on the East side of the building is not properly
controlling water It is allowing water to saturate the rear foundation soils which
in turn allows the wall to settle under high loading conditions
As stated in my first report dated June 19, 1997 the building needs to be
evaluated cost wise as to what is the better solution Do you replace the building
or do you significantly repair by replacing portions of the building The settlement
97034R2.DOC 2
of the front wall of the building and water problem to the front wall dictates the
following
•The water service lines to each of the building section needs to be rebuilt so
that it is isolated from the structural support system
•All the unreinforced masonry walls and their footings need to be replaced
with separation walls meeting current code
•The foundation system, pilasters, and roof support beams need significant
work. The foundation and pilasters need to be replaced The beams need to be
evaluated after being exposed as to being replaced or left with the new support
system
•The sidewalk out front needs to be replaced
•The front four to six feet of floor of the building needs to be replaced along
with the front wall. The front portion of the building will be brought up to level
when this work in done
•The roof drainage in the back needs to be repaired This will include
cleaning the underground plumbing and assuring it is connected to the storm
system
These are the results of my findings Thank you for using Gene Unger
Consulting Engineer on this project.
Sincerely,
97034R2.DOC 3
Gene H Unger, P E.
ind., Photographs
Foundation Plan (copy of first reports)
tx'Pmzs. 7- V
I
19 June 1997
Jay Ketchum
Dive Shop
509 S Lincoln
Port Angeles, WA.
Subject: Condition
Dear Mr Ketchum,
97034R1.DOC
98362
Inspection of Building
Gene H. Unger
Consulting Engineer
Civil Structural Management
1401 West 7th Street
Port Angeles, Washington 98363
Office Fax (360) 452 -2098
I am pleased to have inspected your facility on 20 April 1997 Your Dive
Shop at 509 W Lincoln is the central business in a building which contains
Patricia's Pets, your business, a collection agency and the Paint Store I returned
on May 1st and met Tom Bennett, P E of Pacific Engineering and conducted a
complete inspection of the entire building It is obvious that your building
foundation has settled significantly This report will describe how and why, along
with giving you recommendations as to how to repair the situation
The photographs on page P3 show that the front wall of the building has
settled at least two inches This is verified by the stnng line on the top of the
dividing wall between the collection agency and the Paint Store on pages P9
through P12. The top photo on P12 shows 6 inches where the photo on the
bottom of page P11 shows 8 inches This difference is the direct settlement of
the front wall The photographs on P11 and P30 show what this has done to the
roof parapet wall and the inside walls
The movement is a settlement of the front wall with a rotational failure of the
front ten to twenty feet of East -West walls This shows in vertical cracks on the
wall above the rotational point. Thus the foundation of the central east -west walls
of the building is intact. The front has settled significantly and the back has
settled some
The front wall settlement is the result of several conditions working together
First, the foundation was constructed on fill which was sluiced in when Lincoln
street was filled in before 1940 This material was water deposited and
significant compaction did not occur Thus any structure founded on this material
should have had larger than typical footings. Second, this building was
constructed of non reinforced concrete masonry units, or CMU's This has
allowed sections of the walls to rotate, break away, and settle without significantly
pulling the rest of the building along
Third, the significant awning which was constructed on the front of the
building was cantilevered off the front wall, with a flat top This allowed significant
I
snow buildup that loaded the walls and foundations. This has now been changed
so that the top surface sheds snow
The fourth and deciding condition was the large snow fall that occurred this
winter in Port Angeles This amounted to at least 40 P S F (pounds per square
foot) load on the roof and awning of this building This load exceeded the
Uniform Building Code design load for this area The block walls have significant
cracks and movement. Fortunately, the roof system rafters overlap on the
support walls of this building allowing these failed walls to continue to hold the
roof up even though it has settled more than 2 inches
The CMU walls have moved enough that it is not reasonable to try to stabilize
them in place The slope of the roof has been effected and the grade at the
footing is now such that other adverse conditions are being created I am
therefore recommending that these walls be replaced
On May 1st when I met Tom Bennett at the site, it was speculated that the
settlement might have been exacerbated by a leak in the water line. I have
obtained the past 3 years meter readings from the city of Port Angeles (See
chart 1) They show a very even distribution fro d, 1995 through February of
1997 March and April of 1997 are significant flow d May is back down some
This would say that there have been some majo 'n history, but there is not
one which agrees with the settlement of this winter would say that the
plumbing in this building needs to be replaced The three year history shows
significant leaks which are typical for buildings in Port Angeles with galvanized
plumbing of this vintage
Other findings during inspection.
•The front soffit has be replaced with one that does not have a flat top This
will make the over loading of the front footing less likely, but the significant
settlement has already occurred
•The South wall of the building has several cracks. The most significant is
near the East end shown on page p 5 of the photographs.
•Significant cracks exist in the masonry wall on the East side. One is shown
at building line "C" where it connect with the interior wall. There is movement
here
•The North side of the shows cracks mainly from the ends of window
and door headers One also shows at the step in the roof
•The new roof over the center section appears to be in good condition and
working well
•The roof parapet wall on building line "C" has several major cracks They
range from hairline to over 3/4" These are shown on pages p 9 through p 11
These photographs also show that the center of the wall is higher than the two
reference marks by one inch. This makes the West end settlement closer to
three inches than the measured two plus inches
97034R1.DOC 2
•The parapet wall between the Dive Shop and the pet shop at building line «E"
has significant rotation This is shown on the photograph on page p 13 This is
due to the adverse settlement of the Dive Shop due to its awning load on the
front wall The pet shop does not have this awning and thus its front wall is not
loaded so significantly The Southwest corner of the pet shop has settled
significantly as shown by the cracking of the floor near that corner All of these
visible results show that this foundation has significant settlement. The snow
load is the major contributor
•The roof of the storage room for the pet shop is poorly constructed The
Simpson and angle iron splices shown on page p 17 are more appropriate for a
tension installation rather than the compression installation they are used in This
roof deformed significantly during the snow event of 1996 -7 It would have failed
without emergency bracing under the roof The helper rafters were cut from the
top to allow installation with existing wiring in original rafters This in effect did
little to add to the strength of the ceiling
•The East end of building line "E" is shown on page p.24 of the photographs.
It shows the connection of the roof beam to the East pilaster This connection
has significant movement and deterioration which could easily allow the beam to
come off the pilaster in an earthquake
•The horizontal crack shown on page p.25 is a typical crack from the
settlement of the West end of the bearing walls This starts to show the
magnitude of the settlement and separation of structure.
•The front wall is tipped West on top at 1/2" in 4' typically
•The front wall has deformed enough that the windows in the front of the Dive
Shop and the Collection Agency have lost their glass stop effectiveness These
windows are at least 1/2" out which required the owner to install emergency stops
to keep the windows from falling out of the frames.
•The roof rafters are 2 "x12" 16" o c. which are good for a 22' -8" span
under the present code The 1991 code would allow a 23'-6" at least. Thus the
rafters are reasonable for the installation they are used in here The sloping roof
is created by using a 2 "x6" upper rafter at 2' o c. over the ceiling joist. This
makes a reasonable roof system
The results of my findings are that the roof system has enough overlap at the
supports to allow this building to be used for the short term to allow a solution to
be determined The long term effect of the wall movement will make this building
uninhabitable
The wall systems have failed because of the significant settlement and
deformation They are unreinforced so it is not reasonable to try to repair the
walls They would also not meet earth quake requirements without
reinforcement. It is not practical to insert reinforcing into existing CMU walls
which have cracked significantly All these conditions dictate that the cracked
97034R1.DOC 3
wall segments be removed and replaced The cracked wall segments make up
such a significant portion of the walls, and considering the earth quake
requirements, it is highly likely that all walls will have to be rebuilt to bring this
building into compliance This is due to the requirement that if you do more than
50% of the value of the building in repair and remodeling, you have to bring the
entire building into conformance with the present code
The footing system has settled significantly I see this as at least 3" in the
West wall and 1" in the East wall Thus the foundation was not sized for the
loads appropriate to the bearing capacity The foundation units need to be
removed and replaced with properly sized units to hold the loads This will
require deeper excavation into the soil to assure that the new foundation units are
placed in onginal soil, not in the sluiced in material which is under Lincoln Street.
The water plumbing in the building needs to be replaced These old
galvanized pipes will continue to leak and could potentially undermine the building
foundation This would obviously further compromise the structure
It appears to me that the roof system could be held up with temporary
supports This would allow removal of the walls and replacement with a properly
designed foundation and wall system The water system could be replaced at the
same time New windows and doors could be installed The floor system could
be repoured to level after the new foundation units were in place. This would
give the building (roof system) new support and correct the existing safety
problems with the doors, windows, and walls.
The entire building could be reconstructed to correct the structural problems
which exist. The cost comparison would have to be done to see if that is the
most effective solution The operation of the existing businesses would have to
be considered in the decision of how to proceed
These are the results of my findings. Thank you for using Gene Unger
Consulting Engineer on this project.
Sincerely,
Gene H Unger, P E.
incl Photographs
Water Consumption
Utility Consumption Reports
Foundation Plan
97034R1.DOC 4
EXPIRES 7- 8
7000
6000
5000
4000
LL
c) 3000
2000
1000
97034W1.XLS
Water Consumption
1 1 1 1 1 1 1 1 1 1- 1 1- 1 1 1 1 1- 1 1-
May- Jul- Sep- Nov- Jan- Mar- May- Jul- Sep- Nov- San Mar May- Jul- Sep- Nov- Jan- Mar- May
94 94 94 94 95 95 95 95 95 95 96 96 96 96 96 96 97 97 97
Date
Page 2
Readings
•4
UB200##Z6 Utility Billing Inquiry Consumption
Location 075949 501 513 S LINCOLN
Customer 075949 002 HONEYCUTT, PATRICIA
Meter W5418641 Roll No 075949
Yr Per
97 5
97 4
97 3
97 2
97 1
96 12
96 11
96 10
96 9
96 8
96 7
96 6
96 5
Owner Alert
Units 1 00:
Service 02 Service Service Service
Consumption Days Consumption Days Consumption Days Consumption Days
3172 00 30
6543 00 31
5909 00 28
1984 00 31
932 00 31
1250 00 30
1247 00 31
615 00 30
601 00 31
908 00 31
341 00 30
925 00 31
755 00 30
1997
(1) account (3) services (4) prop info (6) trans (7) meter (8) readings
(9) consumpt (10) comments (11) aging (12) liens (14) def pay (16/32) exit
U$2'004Z6 Utility Billing Inquiry Consumption
Location 075949 501 513 S LINCOLN
Customer 075949 002 HONEYCUTT, PATRICIA
Meter W5418641 Roll No 075949
Owner Alert
Units
1 00
Service 02 Service Service Service
Yr Per Consumption Days Consumption Days Consumption Days Consumption Days
95 5 1813 00 30
95 4 3624 00 31
95 3 4643 00 28
95 2 5112 00 31
95 1 1831 00 31
94 12 4524 00 30
94 11 5395 00 31
94 10 2396 00 30
94 9 2301 00 31
94 8 3543 00 31
94 7 3055 00 30
94 6 3408 00 31
94 5 4741 00 30
1997
(1) account (3) services (4) prop info (6) trans (7) meter (8) readings
(9) consumpt (10) comments (11) aging
(12) liens (14) def pay (16/32) exit
Cr ck
utslde ntt/
F9
Froni nil etttenent 2'
at doorway,
17
Paint Sore
I I.
--m
15'
Lincoln Street
co
V N
CU C
N CO
Floor Cr I 1_) T T u a)
J W r\
0J in c o
Iii vi L uw �3
v
N
KO
-its -C7- C� EEC S -F' N -l
---you Cracks ---,ft Cr ck I— N V/
CD c
CD 3
ii HIS- I -I I- .1 Eo o L
o
-40_
1 ��VnII Cracks Vnll Cracks
Vali Cr cks/
Collection
_Agency
Vnll cracks
�Vsll Cracks Vntl Cr cks
Vall Cr cks
IHF-- I:1
Significant sepnrnti In Pa npet Vail oaf
/'mall !sans ut 7/8' In 4'
Vail Cracks\
Dive Shop
Wall Cracks.,
140'
r Clt
�VaU Cr chs
Wall Cr -ks
4 t
Patricia s Pet Shop
Wall Cracks
IEH ED
•Crack a1 Pr nt all
:0'
15' 15'— 20'
Vall Cracks\
Revisions'
Office I aft .1une'47
CU
1/40
CO
v
C
3
c l!1
O O Cu
a O}
d 0J c
4
N.� L
o >o 0
L. Ct.
d C
T. d
I-
Scale'
1 /e" =1'
Job'
97034fp
Date'
June, '97
Sheet
I EXPIRES. 3/17/98 I of 1