HomeMy WebLinkAbout1411 Aurora Ct Technical - Building TEe leAL .. ,~~ , . ~ '{D' \'\~ ~~'o >%' t) '0 ~ , f'. '{.. Vl> ') s(' 0~ (jJ~eS \CJ ~ \.i\J1 -'eh- v ~,,~ : ' ,. .. Fire Sprinkler System Plan Innovated Fire Sprinkler Systems 81 New Haven Lane Port Angeles, WA., 98362 (360) 452-7583 March 21,2006 For: Want Action Construction P. O. Box 1425 . Sequim, WA. 98382 Location: 1411 Aurora Court Port Angeles, WA., 98362 1~ V I1l:'VKAULIC CALCULATIONS. W 0 r k she e t . For lit CPVC Pipe Two heads require 26 gpm flow at designed pressure. [+ 5 gpm domestic u~ One head requires 18 gpm flow at designed pressure. ~ 1. Pipe size = 11. , CPVC (friction loss. 1067). 2. Watet pressure at street (2) = 75 psi. 3. Meter friction loss (3) = OJ psi (see Table 4-4.3d NFPA 131 4. (2) 7 S minus (3) . c; (4) = ~ G psi remainir 5. Loss from street main to control valve = ~O feet X I .1067' , = (;, '10 feet (see friction loss chart). 6. (4) G G minus (5) G t f-I d' = (6) 5CJ I Go psi remainin< 7. Elevation loss (building & street) - I 2- feet X .434 = . .S. 2./ p~ 8. (6) St. CP 0 minus (7) S",_2J - ~ '1. J 7 psi remainin 9. Total length of pipe from control valve to the farthest sprinkler = .so fe X I .1067/ = S. 33 psi. 10. (8) . S '-It.] 0, minus (9) S~ :3 J lj 0; , Q e;. psi r~r:nalnln: 11. Equivalent length for valves and fittings(m~ter to farthest sprinkler f1ead): Tvpe Number Equivalent 1 " T run S X II] = .5 1" T Branch 3 X m = } S 1 " 90 Elbo.W :J X [TI = 2 I 1" Coupling I X 0 = / 1" 45 Elbow 0 X [TI = 0 1 n Gate Valve I X [TI = }. (11) Tot.al Feet L/3 12. Loss in fittings (11) <-I_"? feet X 1.1067 I = Lf, S Cj pSI 13. (10) Y7,OC; minus (12) t-/,S"c, = L/L//'f) .psiremaining. 14. PSI remaining (13) 'l/~'t'Jminus 3, 'i (loss in riser) parts = ~//,o 7 . 1'5. (14) Lf I, 0/ is more than the minimum design psi required for 2 or 1 sprinkler heads operating. Riser Parts Potter flow switch 2.4 psi Soft seat valve 1.0 psi Needed Information: Type of sprinkler head T c.-o L GPM & pressure 1 st head / GPM & pressure 2nd head 26' 3/4" water meter FP-9C Revised 5/29/91 . . '. . -. - .. -.. . . .SPB-.l N.K:L.E.R .MAN 1 ~OL 0 ~ I.~~~.T~_~__ .----- ..TO..J~_.EAD5. . i p v c.._. __..' ?>.. -' 1) . _ n __9-:A-.!!rr. E:- . -. ---... .-.- .. -..- .--.--......-...-.. .-----.---....--... ---. --. . ... - -.--.--.--..... .--.'-" -----.---..-----.--.-..-- ... ...-_..... ...___..__. .__.. ._.. ._ _._ __n.. ... .... .-. ... . . ... .. ... ... .-..' - .-. ~.~. ...... ---.- ..' ._~. ......... ... ...... _ .___,,____ . ... DR.A.IN_RT.EST..VALV _. .(PLVN\B.EDTO.. oVTsioE) .' - --.. --. - ..- .--.--- .. -.--. .-- . . ..-. .-..-.....--. - -.--...-.--....- ...- --.... Q.l< :. . .... _ ___E_L,o.\~y___SWJT-CJ-L _._ _.. - - - IE ~ I.Q.N.. _ _ _ .. .. .. -...... -.. .--.....-. - - -.-.... .. .. .0 ~ 1= -- .- -~_. -- V_E_________ .- -- .. .-..--.- --- -.-.. .. ..-.... -. --- -.-.- - - ....- .. . .- . ...-.-..------.-.-..-------.--.-- ...-- .---..-.-..... -.. -.-----.---.- . -' . ____.. .___..._....._.___....._.___. ._. ._. __U. . _"h' . ._ ..._ _...' .______._.. ___.. .._. . .__u. ... ---.---...---.--- ....- ..-..---.---.---..- ----..-- .- . . __ :_\ - - .._ ____________._________. . n_ .._ ...-.------...: .0_0 __n__. _ . . . . . ...-... -... ..... -.... ... ~...-.. - .. ~. ......--- .-' ...' . . . .- ...______ __.. 1."..P\.P€._:_ ..... --. ... ... ---_.__. .-.- -.- -_. -.. ;----. _...-- - --..--.... ---.. ...-.--.. -... -.-.--..---...-...-...-.-...--..--....-.-.. -.. _.- - ....---.-.-- -.-- - ...-. S.l.G:N~ D ._..8 Y.: ._ ___;. . ._. __.. ....: .. .. .. " ... .'--" . " .,. . . J f\\ 0 V ATE. D F \ R E. S _? R\ l\\ K L E RS . F ~OJ"V\ . M '::: y~ '0') '. t .\.w~-~ . r-- I I . ,\' ,.1' . i 3 . . , tqca IFire & Building / Products Direct Sales (Central): Tel: (800) 523-65121 Fax: (215) 362-5385 Distribution Sales (GemlStar): Tel: (800) 558-52361 Fax: (800) 8n-1295 Technical Services: Tel: (800) 381-93121 Fax: (800) 791-5500 Series LFII Residential Concealed Pendent Sprinklers, Flat Plate 4.2 K-factor General Description The Series LFII (TY2596) Residential Concealed Pendent Sprinklers are decorative, fast response, fusible sol- der sprinklers designed for use in resi- dential occupancies such as homes, apartments, dormitories, and hotels. The cover plate assembly conceals the sprinkler operating components above the ceiling. The flat profile of the cover plate provides the optimum aestheti- cally appealing sprinkler design. In ad- dition, the concealed design of the Se- ries LFIl (TY2596) provides 1/4 inch (6,4 mm) vertical adjustment. This ad- justment reduces the accuracy to which the fixed pipe drops to the sprin- klers must be cut to help assure a perfect fit installation. The Series LFII are to be used in wet pipe residential sprinkler systems for one- and two-family dwellings and mo- bile homes per NFPA 130; wet pipe residential sprinkler systems for resi- dential occupancies up to and includ- ing four stories in height per NFPA 13R; or. wet pipe sprinkler systems for the residential portions of any occu- pancy per NFPA 13. The Series LFII (TY2596) has a 4.2 (60,5) K-factor that provides the re- quired residential flow rates at reduced pressures, enabling smaller pipe sizes and water supply requirements. The Series LFII (TY2596) has been designed with heat. sensitivity and water distribution characteristics proven to help in the control of residen- . tial fires and to improve the chance for occupants to escape or be evacuated. The Series LFIl (TY2596) Residential Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is being in- Page 1 of 4 stalled or finished. The tip of the Pro- tective Cap can also be used to mark the center of the ceiling hole into pIas- ter board, ceiling tiles, etc. by gently pushing the ceiling product against the Protective Cap. When the ceiling in- stallation is complete the Protective Cap is removed and the Cover Plate Assembly installed. WARNINGS The Series LFII (TY2596) Residential Concealed Pendent Sprinklers de- scribed herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the integrity of these devices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. Sprinkler/Model Identification Number SIN TY2596 Technical Data Approvals: UL and C-UL Listed. Maximum Working Pressure: 175 psi (12,1 bar) Discharge Coefficient: K = 4.2 GPMlpsi1f.! (60.5 LPMlbar1f.!) Temperature Rating: 160oF1710C Sprinkler with 1350F/SrC Cover Plate .JULY, 2002 ... It-ll Vertical Adjustment: 1/4 inch (6,4 mm) Finishes: Cover Plate: Rat White. Bright White, Chrome, or Custom Physical Characteristics: Body. . . . . . . . . . . . Cap. . . . . . . . . . . . . Saddle . . . . . . . . . . . Sealing Assembly . . . . . . . . . . . Beryllium Nickel wI Tenont Soldered Link Halves . Nickel Lever . . . . . . . . . . . . . Bronze Compression Screw . . . . . . Brass Deflector . . . .. ..... Bronze Guide Arm Frame . . . . Bronze Guide Arms . Stainless Steel Support Cup . . . . Steel Gover Plate .... .... Copper Retainer . . . . . . . _ . . . . Brass Cover Plate Ejection Spring .... . . . . . . . . . . . . Stainless Steel . Brass Bronze . Brass tDuPont Registered Trademark TFP440 .1 .Page 2 of 4 Operation When exposed to heat from a fire, the Cover Plate, which is normally sol- dered to the Support Cup at three points, falls away to expose the Sprin- kler Assembly. At this point the Deflec- tor supported by the Arms drops down to its operated position. The fusible link of the Sprinkler Assembly is com- prised of two link halves that are sol- dered together with a thin layer of sol- der. When the rated temperature is reached, the solder mells and the two link halves separate allowing the sprin- kler to activate and flow water. Design Criteria The Series LFII (TY2596) Residential Concealed Pendent Sprinklers are UL and C-UL Usted for installation in ac- cordance with the following criteria. NOTE When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be accept- able to the Authority /-laving Jurisdic- tion. System Type. Only wet pipe systems may be utilized. Hydraulic Design. The minimum re- quired sprinkler flow rate for systems designed to NFPA 130 or NFPA 13R are given in Table A as a function of temperature rating and the maximum allowable coverage areas. The sprin- kler flow rate is the minimum required discharge from each of the total number of "design sprinklers" as speci- fied in NFPA 130 or NFPA 13R. For systems designed to NFPA 13, the number of design sprinklers is to be the the four most hydraulically de- manding sprinklers. The minimum re- quired discharge from each of the four sprinklers is to be the greater of the following: · The flow rates given in Table A for NFPA 130 and 13R as a function of temperature rating and the maxi- mum allowable coverage area. · A minimum discharge of 0.1 gprnlsq. ft. over the "design area" comprised of the four most hydraulically de- manding sprinklers for the actual coverage areas being protected by the four sprinklers. Obstruction To Water Distribution. locations of sprinklers are to be in TFP440 '-1 Minimum Flow (b) and Minimum Row (b) Bnd Maximum Maximum Residual Pressure Residual Pressure Coverage Spacing For Horizontal Ceiling For Sloped CeIling Area (a) Ft. (Max. 2 Inch Rise (Max. 8 Inch Rise Ft. x Ft. (m) for 12 Inch Run) for 12 Inch Run) (m x m) 1600Fm oC 160oFmoC Sprinkler Sprinkler 12 x 12 12 13 GPM (49,2 LPM) 18 GPM (68,llPM) (3,7 x 3,7) (3,7) 9.6 psi (0,66 bar) 18.4 psi (1,27 bar) 14 x 14 14 14 GPM (53,0 LPM) 18 GPM (68,lLPM) (4,3 x 4,3) (4,3) 11.1 psi (0,77 bar) 18.4 psi (1,27 bar) '/': 'TOx16 1 16 16 GPM (60,6 LPM) 18 GPM (68,1 LPM) (4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) '18x~ 18 20 GPM (75,7 LPM) N/A (5,5 x 5,5) (5,5) 22.7 psi (1,57 bar) 2Ox2O 20 24 GPM (90,8 LPM) N/A (6,1 x 6,1) (6,1) 32.7 psi (2,25 bar) (a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details. TABLE A NFPA 130 AND NFPA 13R HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER accordance with the obstruction rules of NFPA 13 for residential sprinklers. Operational Sensitivity. The sprin- klers are to be installed relative to the ceiling mounting surface as shown in Figure 3. Sprinkler Spacing. The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum spacing be- tween sprinklers cannot exceed the length of the coverage area (Ref. Table A) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 teet for a 20 ft. x 20 ft. coverage area). Installation The Series LFII (TY2596) must be in- stalled in accordance with the follow- ing instructions: NOTES Damage to the fusible Link Assembly during installation can be avoided by handling the sprinkler by the frame arms only (i.e., do not apply pressure to the fusible link Assembly). A leak tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 fUbs. (9,5 to 19,0 Nm). A maxi- mum of 21 tUbs. (28,S Nm) of torque is to be used to install sprinklers. Higher levels of torque may distort the sprinkler inlet with consequent leak- age or impairment of the sprinkler. Do not allempt to compensate for in- sufficient adjustment in an Escutcheon Plate by under- or over-tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. Step 1. The sprinkler must only be installed in the pendent position and with the centerline of the sprinkler per- pendicular to the mounting surface. Step 2. Remove the Protective Cap. Step 3. With pipe thread sealant ap- plied to the pipe threads, and using the W- Type 18 Wrench shown in Figure 2, install and tighten the. Sprinkler/Sup- port Cup Assembly into the fitting. The W-Type 18 Wrench will accept a 1/2 inch ratchet drive. Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec- tive Cap helps prevent damage to the Deflector and Arms during ceiling in- stallation and/or during application of : . TFP440 Page 3 of 4 s BODY (112" NPl) SEALING ASSEMBLY WRENCH RECESS CAP SPRINKLER WRENCHING AREA D SADDLE COMPRESSION SCREW PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA LEVER FIGURE 2 W-TYPE 18 SPRINKLER WRENCH GUIDE ARM GUIDE ARM FRAME I I I I I I I I I I I I I I ,.J L./ 'L.J l, .....,..;--"""----""""-......., DEFLECTOR (OPERATED POSITlON) SPRINKLER/SUPPORT CUP ASSEMBLY THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING o o RETAINER WITH THREAD DIMPLES EJECTION SPRING SOLDER TABS (3) COVER PLATE/RETAINER ASSEMBLY FIGURE 1 SERIES LFI/ (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER COVER PLATE FACE OF SPRINKLER FITTING SPRINKlER- SUPPORT CUP ASSEMBLY OPERATED SPRINKLER 1-718".:t118" (47,6 mm .:t3.2mm) COVER PLATE RETAINER ~ ~ COVER- SPRINKLER- RETAINER SUPPORT CUP ASSEMBLY ASSEMBLY 3-114" DIA. (82.6 mm) =r'MOUNTING 3116" J SURFACE (4,8mm) 718" (22.2 mm) 1-118" (28,6 mm) 1 TIP DEFlECTOR IN OPERATED POSITION FIGURE 3 SERIES LFlI (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER INSTALLA nON DIMENSIONS / PROTEcnVE CAP / ACTIVA TED DEFLECTOR . . .. ~age 4 of 4 the finish coating of the ceiling. It may also be used to locate the center of the' clearance hole by gently pushing the ceiling material against the center point of the Cap. NOTE As long as the protective Cap remains in place, the system is considered to be .Out Of Service". Step 5. After the ceiling has been com- pleted with the 2-1/2 inch (63 mm) diameter clearance hole and in prepa- ration for installing the Cover Plate As- sembly, remove and discard the Pro- tective Cap, and verify that the Deflector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire Sprin- kler assembly. Do not attempt to mod- ify or repair a damaged sprinkler. Step 6. Screw on the Cover Plate As- . sembly until its flange comes in con- tact with the ceiling. Do not continue to screw on the Cover Plate Assembly such that it lifts a ceil- ing panel out of its normal position. If the Cover Plate Assembly cannot be engaged with the Mounting Cup or the Cover Plate Assembly cannot be en- gaged sufficiently to contact the ceil- ing, the Sprinkler Fitting must be repo- sitioned . Care and Maintenance The Series LFII (TY2596) must be maintained and serviced in accord- ance with the following instructions: NOTES Absence of an Escutcheon Plate may delay the sprinkler operation in a fire situation. Before closing a fire protection system main control valve for maintenance work on the fire protection system which it controls, permission to shut down the affected fire protection sys- tem must be obtained from the proper authorities and all personnel who may be affected by this action must be no- tified. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be shipped or stored where the tempera- ture will exceed 100oFI380C and they must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified or over heated sprin- klers must be replaced. Care must be exercised to avoid dam- age - before, during, and after instal- lation. Sprinklers damaged by drop- ping, striking, wrench twisVslippage, or the like, must be replaced. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment. as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in- stalling contractor or sprinkler manu- facturer should be contacted relative to any questions. NOTE The owner must assure that the sprin- klers are not used for hanging of any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service. Limited Warranty Products manufactured by Tyco Rre Products are warranted solely to the original Buyer for ten (10) years against defects in material and work- manship when paid for and properly installed and maintained under normal use and service. This warranty will ex- pire ten (10) years from date of ship- ment by Tyco Fire Products. No war- ranty is given for products or components manufactured by compa- nies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corro- sion, or which have not been installed, maintained, modified or repaired in ac- cordance with applicable Standards of the National Fire Protection Associa- tion, andlor the standards of any other Authorities Having Jurisdiction. Mate- rials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products' sole option. Tyco Fire Products neither as- sumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. TFP440 G IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CON- TRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THE- ORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, RE- GARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' LI- ABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED. INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT- NESS FOR A PARTICULAR PUR- E!QSE.. Ordering Procedure When placing an order, indicate the full product name. Contact your local dis- tributor for availability.. Sprinkler Assembly: Series LFII (TY2596), K=4.2, Residen- tial Concealed Pendent Sprinkler with- out Cover Plate Assembly, PIN 51-122-1-160. Cover Plate Assembly: Cover Plate Assembly having a (spec- ify) finish for the Series LFII (TY2596), K=4.2, Residential Concealed Pen- dent Sprinkler, PIN (specify). Chrome..... .... ......... PIN 56-122-9-135 Bright White............... PIN 56-122-4-135 Rat White..... ........... PIN56-122-5-135 Custom...... ... ....... .. PIN 56.122-X-135 Sprinkler Wrench: Specify: W-Type 18 Sprinkler Wrench, PIN 56-000-1-265. TYCO ARE PROOVCTS. 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 '. ....... .'.... (~1POTIER @ BELLS PBA-AC & PBD-DC Potter Electric Signal Company 2081 Craig Ad./P,O. Box 28480 St. Louis, MO 63146 (314)878~321/(800) 325-3936 .lfE\;;~i::;:::,' ~~Jj~t~J:; :~. .' ...,.;....,_.:..'~:iii.."'~.... ,.:.;.'..A. . .~~ff.~~i~;,~~'~~~t;~{i:.t : .' .... . .:':':~~ ..;:.:..... .t;.;-;f:i.~,....;:::)..!r.'J;'J.fi...J :~".' :." >.:.:. : . . .. ...:..0 ."I..:....~....... .,"" ";~"'.c~'"ii.......~~,\~:.:..\"tt)J\i''a. .t.. ". ....~. ...... . 6" BELL SHOWN Potter Electric Signal & Mfg. L TO - 1967 Leslie Street . Don Mills, Ontario. Canada M382M3 (416) 441-1833 UL LISTED. FM APPAOVED Sizes Avallable:~ 8". and 10" Voltages Available: ~ 20VA 12VOC (102 to 15.6) Polarized 24VOC (20.4 fa 312) Polarized ServIce Use: Fire Alarm General Signaling Burglar Alarm Environment: Indoor or Outdoor Use (See Note 1) -400 to lsooF (outdoor use require weatherproof backbox) TermInation: 4 No. 18 AWG stranded wires Finish: Aed powder coating Optional: ModeIBBK-l weatherproof backbox "hese vibrating type bells are designed for use as fire. burglar. or general signaling devices. They have low power onsumption and high decibel ratings. The unit mounts on a standard 4. square electrical box for indoor use. or on a model tBK-l weatherproof backbox for outdoor applications: ALL DC BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION: SIZE VOLTAGE MOOEl. NO. STOCK NO. CURRENT (MAX) TYPICAL dB MINIMUM dB o 10 FT. o 10 FT. 6 12VOC PaO 126 1706012 .12A 85 75 8 12VQC PaOl28 1706012 .12A 90 75 10 12VQC PB01210 1710012 .12A 92 75 6 24VQC PB0246 170602<1 .06A 87 75 8 24VQC PB0248 170602<1 .06A 91 79 10 24VQC PB02410 1710024 .06A 94 79 6 24VAC PaA246 180602<1 .17A 91 75 8 24VAC P8A248 180602<1 .17A 94 75 . 10 2<1VAC PaA2410 181002<C .17A 94 75 , 6 120V AC PaA 1206 1806120 .OSA g2 62 8 120V AC PeA 1206 1806120 .OSA 119 82 10 120VAC PBA12010 1610120 .OSA 99 85 eatherproof backbox model 881<.1 Stk. No. 1500001. Ccs: U4nimumCl6 ''''''-9$ aie c..lc.....",.,,, It"", ;oc"9'aled o.ound pt..ssu.... meu....~ made a, Undetwfil..... Labota,o<ies as ~<I.... Ul SlancUtd 464. UL ~. ........, '''''9<' .s .30' '0 1 SO"( . Tyop<aI dO ,.(~, .'e C.ICc.Jf~t~ ("om ~.aSOf'ecnenc, m.ade 'tIIIIfCh. COAYen(ton.t &.OOnd......,., n.e'" and .,e inc:k:.atfve of OUCpuIleve(s ., an &Clue' tnst..~'4()of1. INTEO IN OSA .......,..,-.. AC7 - "1. " , . @..POTTER )otte.- Electric Signal Company ~081 Crnig Road. P.O. Box 28480 it. Louis, MO 63146-4161 314) 878-4321 . (800) 325-3936 Cf) VSR-SF FOR SMALL PIPE VANE lYPE WATERFLOW ALARM SWITCH WITH RETARD Potte.- Elect.-ic Signal & Mfg. L TO 1967 Leslie St.-eet Don Mills, Ontario, Canada M382M3 (416) 441-1833 " ;TK. NO. 1113000 I.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 )THER PATENTS PENDING. UL., ULC, CSFM USTED and NYMEA ACCEPTED Service Pressure: Up to 250 PSI Minimum Row Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Enclosure: 0ie<aSt. red enamel finish Cover held In place with tamper resistant SCfews Contact Ratings: 2 sets of SPOT (Focm C) 15.0 Amps at 125f250 VAC 2.0 Amps at ()..3() VDC Conduit Entrances: 2 knockouts provided fof 1/Z' conduit Usage: Usted Plastic. Copper and Schedule 40 lroo Pipe Fits pipe sizes - 1", 11/4", and 1 112" Note: 8 paddles are furnished with each unit. one for each pipe size of threaded or sweat TEE. one for 1" CPVC, and one for 1112" potybutylene (CTS..coppertubing size) Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and diEH;ast housing. NEMA4 Rated Enclosure-usewithappropriate conduit fining. Temperature Range: 40" F/120" F (4.5" C/49" C) Caution: This device is not intended for appfications in explosive environments Service Use: Automatic Sprinkler NFPA-13 One or two family dweUing NFP A-13D Residentiafoccupancy up to four stories NFP A-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch. ortler SIk. No. 0090018 he Model VSR-SF is a vane type waterftow switch lor use on wet :>rinlder systems that use 1", 1 1/4", or 1 112' pipe size. The unit laY also be used as a sectional watefflow detector on targe (Stems. . he unit contains two single pole double throw soap action Hitches and an adjustable, instantly recyding pneumatic retard. he switches are actuated when a flow of 10 gallons per minute or .()("e occurs downstream of the device. The flow condition must ICist for a period or time OC<:essary to overcome the selected retard ~riod. 1ST At-LA TION: 1hese devices may be mounted in horizontal or ~rti<:al pipe. On horizontal pipe they should be installed on the top de or the pipe where they will be accessible. The units should not ~ installe<f within 6" of a valve, drain or fitting which changes the rectioo or the waterflow. 1he unit has a 1" NPT bushing for reading into a non~rrosive TEE. See Fig. 2 for pcoper TEE ze. type and installation. ':Xew the device into the TEE fitting as shown in Fig. 2. Care must , taken to propef1y orient the device for the direction of waterflow. The vane must not rub the inside 01 the TEE or bind in any way. The stem should move freely when operated by hand. The device can also be used in copper or plastic pipe installations with the proper adapters so that the specified TEE fining may be installed on the pipe run.o INSPECTION AND TESTING: Ched< the operation of the unit by opening the inspecto( test valve al the end of the sprinkfer tine or the drain and test connection. if an inspecto(s test valve is not provided. If there are no provisions for testing the operalion or the flow . detection device on the system. application of the VSA-SF is not recommended or advisable The frequency of the inspection and testing and its associaled protective monitoring system should be in accoo:1ance with the appflCable NFPA Codes and Standards and/or authority having jurisdictioo (manufacturer recommends quartef1yor more frequently). RImED IN USA PAGE 1 OF 2 .MKT. .8800003 - REV J MFG. .S400802 - 8195