Loading...
HomeMy WebLinkAbout240 W Front St Technical Fire Sprinklers - BuildingTECHNICAL Permit n9- 29 g Address Al yf 54-- Project description Ryn �e of PA kre. J Date the permit was finaled 01 -27-Ib Number of technical pages 77 r A Fire Sprinkler Corporation PMB 42 5 114 w Fosdick D, NW #F Gig Harbor WA 98335 Phone 253.853 7780 Fax 253.853.5890 SPRINXJF @AOL.COM SPRIN fire protection Fire Protection Sprinkler System Hydraulic Calculations, Material Submittals Operation Maintenance Manuals FOR PORT ANGELES AMBULATORY HEALTH CARE 240 WEST FRONT STREET PORT ANGELES, WA 98362 EMERGENC Y IINI ORMA HON IN THE ASI Of FIRE AND \OR I LOODING DIAL 911 IMMEDIA I'LL Y MAINTENANCI AND INSPLCTION OFFICE (253) 853 780 FAX (253) 853 5890 INDEX HYDRAULIC CALCULATIONS HEADS 1. VIKING VK302 WHITE RECESSED 155 DEG. PENDENT QR 2. VIKING VK300 BRASS UPRIGHT 155/200 DEG K =5.6 NPT QR 3 VIKING VK305 HOR. SIDEWALL 133 DEG K=5.6 NPT QR 4 VIKING VK178 DRY HOR. SIDEWALL 155 DEG. K =5 61" NPT QR 5. 12 HEAD SPRINKLER HEAD CABINET DEVICES 6. 4" VIKING RISER MANIFOLD GRV X GRV "EASYPAC" 7 4" WILKINS 350ADA DOUBLE DETECTOR CHECK VALVE BACKFLOW 8. 4" G X G VIKING SWING CHECK VALVE MOD G-1 9 POTTER 8" ELECTRIC BELL 24V DC PIPE, FITTINGS HANGERS 10. ALLIED SUPER 40 PIPING 11. THREADED FITTINGS 12. ALLIED DYNA FLOW PIPING 13. GROOVED FITTINGS 14. STEEL PIPE HANGERS RING HANGERS, ALL THREAD ROD, UNI- STRUT, TOP BEAM C- CLAMP, SIDE VERTICAL SAMMY SCREWS, STEEL SIDE SAMMY WITH RETAINER NUT) 15. EARTH QUAKE BRACING TOLCO FIG. 907,FIG. 1000, FIG 909, FIG. 800 FIG. 4A) SUPPLIER INFORMATION VIKING SUPPLY NET KENT, WA. 253- 872 -8444 FERGUSON FIRE AND SAFETY RENTON, WA. 1-866-507-5758 Fire Protection by Computer Design SPRINX FIRE PROTECTION INC PM B-42 5114 PT FOSDICK DR. NW #E GIG HARBOR, WA. 98335 253 853 -7780 Job Name PORT ANGELES AMBULITORY CARE Building Location 240 WEST FRONT STREET PORT ANGELES WA 98363 System REMOTE AREA 1 Contract Data File FM -FP -1 wx1 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 SPRINX FIRE PROTECTION INC Page 1 PORT ANGELES AMBULITORY CARE Date 031109 S Y S T E M D E S I G N Note Hydraulic Design Information Sheet Name AMBULATORY CARE CENTER Date 4 -2 -09 Location 240 WEST FRONT STREET PORT ANGELES WA 98363 Building System No REMOTE AREA 1 Contractor SPRINX FIRE PROTECTION INC Contract No Calculated By JGF Drawing No FP -2 0 Construction Combustible (X) Non Combustible Ceiling Height 22'5 5" Occupancy LIGHT HAZARD MEDICAL BUILDING (X) NFPA 13 (X) Lt Haz Ord Haz Gp 1 2 3 Ex Haz NFPA 231 NFPA 231C Figure Curve Other Specific Ruling Made By Date Area of Sprinkler Operation 1527 Density 1000 Area Per Sprinkler 125 00 Elevation at Highest Outlet 21' -0" Hose Allowance Inside 0 Rack Sprinkler Allowance 0 Hose Allowance Outside 100 Calculation Flow Required 336 438 Press Required 74 9069 At Node TEST Summary C- Factor Used 120 Overhead 140 Underground W Water Flow Test Pump Data A Date of Test 1993 T Time of Test Rated Cap E Static Press 130 Press R Residual Press 107 Elev Flow 3056 S Elevation 0 U P Location CLOSEST HYDRANT TO SITE P L Source of Information KEN DEBUC (PORT ANGELES FIRE DEPT) Y C O M M S R T A O C Commodity Storage Ht Storage Method Solid Piled R K Flue Spacing A Longitudinal G E Horizontal Barriers Provided Class Area Single Row Conven Pallet Double Row Slave Pallet Mult Row System Type (X) Wet Dry Deluge Preaction Other Sprinkler /Nozzle Make VIKING Model VK300 Size 1/2" K- Factor 5 6 Temp Rat 155 Tank or Reservoir Cap Elev Well Proof Flow Location Aisle W Palletized o Rack Auto Storage Encap Solid Shelf Non Open Shelf Clearance Storage to Ceiling Transverse Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Water Supply Curve (C) SPRINX FIRE PROTECTION INC PORT ANGELES AMBULITORY CARE City Water Supply .C1 Static Pressure 130 C2 Residual Pressure: 107 C2 Residual Flow 3056 150 140 130 P 120 R 110 E 100 S 90 S 80 U 70 D R 60 E 50 40 30 20 10 C l 400 800 1200 1600 2000 2400 FLOW N 2800 3200 Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Demand D1 Elevation D2 System Flow D2 System Pressure Hose (Adj City Hose Demand D3 System Demand Safety Margin 3600 Page 2 Date 031109 9 095 236 438 74 907 100 336 438 54 705 Flow Diagram SPRINX FIRE PROTECTION INC Page 3 PORT ANGELES AMBULITORY CARE Date 031109 70.1 30.6 5 4 3 2 1 1 49.4 14.8 I 70.1 70.3 30.6 6 -*18 17 -*16 -*15 T 49.5 14.8 I 140.4 I 71.2 31 7 14 13 -4. 12 11 T 50.2 15 I 211.6 I 24.9 8 9 I T 236.4 19 I 236.4 20 T 236.4 R12 T I 236.4 I 236.4 TOR- BOR- TEST 236.4 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittints Used Summary SPRINX FIRE PROTECTION INC Page 4 PORT ANGELES AMBULITORY CARE Date 031109 Fitting Legend Abbrev Name Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Y2 1 1 1Y2 2 2Y2 3 3% 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Pressure Flow Summary STANDARD SPRINX FIRE PROTECTION INC PORT ANGELES AMBULITORY CARE Node Elevation K -Fact Pt No. Actual Pn The maximum velocity is 15.27 and it occurs in the pipe between nodes 14 and 7 Page 5 Date 031109 Flow Density Area Press Actual Req. 15 21.0 5.6 7.0 na 14.82 0.1 125 7.0 16 210 5.6 7.93 na 15.77 0.1 125 7.0 17 21.0 5.6 1147 na 18.97 0.1 125 7.0 18 21 0 5.6 13.75 na 20.76 0.1 125 7 0 11 21.0 5.6 7 18 na 15.01 0.1 125 7 0 12 21.0 5.6 B.13 na 15.97 0.1 125 7.0 13 210 5.6 1176 na 19.2 0.1 125 7.0 14 21.0 5.6 14.09 na 21.02 0.1 125 7.0 9 21.0 5.6 19.71 na 24.86 0.1 125 7 0 1 21.0 5.6 7.02 na 14.83 0.1 125 7.0 2 21.0 5.6 7.95 na 15.79 0.1 125 7.0 3 210 5.6 11.21 na. 18.75 0.1 125 7.0 4 21.0 5.6 13.65 na 20.69 0.1 125 7.0 5 16.0 21.04 na 6 16.0 21 17 na 7 16.0 21 63 na 8 16.0 22.64 na 19 16.0 35.74 na 20 16.0 53.98 na RI2 16.0 61 6 na TOR 8.0 65.77 na BOR 10 72.69 na TEST 0.0 74.91 na 100.0 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations Hazen Williams SPRINX FIRE PROTECTION INC Page 6 PORT ANGELES AMBULITORY CARE Date 031109 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref 'C' or Ftng's Pe Pv Notes Point Qt Pf /Ft Eqv Ln Total Pf Pn *P -6 15 14.82 1 049 0 0 12.410 7 000 K Factor 5 60 to 1200 00 00 00 16 14 82 0 0747 0 0 12.410 0 927 Vel 5 50 16 15 76 1 049 0 0 12.410 7 927 K Factor 5 60 to 1200 00 00 00 17 30 58 0:2855 0 0 12.410 3 543 Vel 11.35 17 18.97 1 38 0 0 12.410 11 470 K Factor 5 60 to 1200 00 00 00 18 49.55 0 1833 0 0 12.410 2.275 Vel 10 63 18 20 76 1 38 1E 3.0 6 000 13 745 K Factor 5.60 to 120 0 1T 6 0 9 000 2.166 6 70 31 0 3503 0 0 15 000 5.254 Vet 15 08 00 70 31 21 165 K Factor 15.28 *P -9 11 15 01 1 049 0 0 12.410 7 182 K Factor 5 60 to 1200 00 00 00 12 15 01 0 0765 0.0 12.410 0 949 Vel 5 57 12 15 97 1 049 0 0 12.410 8 131 K Factor 5 60 to 1200 00 00 00 13 30 98 0.2923 0 0 12.410 3 628 Vel 11 50 13 19.20 1 38 0 0 12.410 11 759 K Factor 5 60 to 1200 00 00 00 14 50 18 0 1877 0 0 12.410 2.329 Vel 10 76 14 21 02 1 38 1E 3 0 6 000 14 088 K Factor 5 60 to 120 0 1T 6 0 9 000 2.166 7 71.2 0 3585 0 0 15.000 5.378 Vel 15.27 00 71.20 21 632 K Factor 15.31 *P 12 9 24 86 1 38 1E 3.0 6 000 19 711 K Factor 5 60 to 120 0 1T 6 0 9 000 2.166 8 24 86 0 0512 0 0 15.000 0 768 Vel 5.33 00 24 86 22.645 K Factor 5.22 *P15 1 14.83 1 049 0 0 12.410 7 018 K Factor 5 60 to 1200 00 00 00 2 14 83 0 0749 0 0 12.410 0 929 Vel 5 51 2 15 79 1 049 0 0 11 410 7 947 K Factor 5 60 to 1200 00 00 00 3 30 62 0.2862 0 0 11 410 3.265 Vel 11.37 3 18 75 1 38 0 0 13.410 11.212 K Factor 5 60 to 1200 00 00 00 4 49 37 0 1821 0 0 13 410 2.442 Vel 10 59 4 20 69 1 38 1 E 3.0 6 000 13.654 K Factor 5 60 1 to 1200 IT 60 9000 2.166 5 7006 03480 00 15000 5.220 Vel= 1503 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Final Calculations Hazen Williams SPRINX FIRE PROTECTION INC Page 7 PORT ANGELES AMBULITORY CARE Date 031109 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref 'C' or Ftng's Pe Pv Notes Point Qt Pf /Ft Eqv Ln. Total Pf Pn 5 00 2.703 00 9 500 21 040 to 1200 00 00 00 6 70 06 0 0132 0 0 9 500 0 125 Vet 3 92 6 70 32 2.703 0 0 9 790 21 165 to 1200 00 00 00 7 140 38 0 0477 0 0 9 790 0 467 Vet 7 85 7 71.20 2.703 0 0 9 950 21 632 to 1200 00 00 00 8 21158 01018 00 9950 1013 Vel 11.83 8 24 86 2.703 1T 18 651 86 120 22.645 to 1200 00 18651 00 19 236 44 0 1250 0 0 104 771 13 097 Vel 13.22 19 0 0 2.703 2E 18.651 108.580 35 742 to 120 0 1T 18.651 37 302 0 0 20 236 44 0 1250 0 0 145 882 18.236 Vel 13.22 20 0 0 2.703 2E 18.651 23.660 53.978 to 120 0 1T 18 651 37 302 0 0 RI2 236 44 0 1250 0 0 60 962 7 621 Vel 13.22 RI2 0 0 4 31 1E 13.937 12.700 61 599 to 120 0 1T 27.874 41 811 3 465 TOR 236.44 0 0129 0 0 54 511 0 702 Vel 5.20 TOR 0 0 4 31 1E 13.937 8 000 65 766 to 1200 1B 16724 30661 6429 BOR 236 44 0 0129 1Zic 0 0 38 661 0 499 BOR 0 0 4 1 2E 29 067 83.000 72.694 to 140 0 1G 2.907 61 041 0 433 TEST 236 44 0 0124 1T 29 067 144 041 1 780 100 00 336 44 74 907 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fixed loss 3.398 Vel 5.20 Vet 5.75 Qa 100 00 K Factor 38 87 Fire Protection by Computer Design SPRINX FIRE PROTECTION INC PMB-42 5114 PT FOSDICK DR. NW #E GIG HARBOR, WA. 98335 253 853 -7780 Job Name PORT ANGELES AMBULATORY CARE Building Location 240 WEST FRONT STREET PORT ANGELES WA 98363 System REMOTE AREA 2 Contract Data File FM -FP 1 wx2 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 S Y S T E M D E S I G N W A T E R S U P P L Y C 0 M M S T 0 R A G E SPRINX FIRE PROTECTION INC PORT ANGELES AMBULATORY CARE Area of Sprinkler Density Area Per Sprinkler Elevation at Highest Outlet Hose Allowance Inside Rack Sprinkler Allowance Hose Allowance Outside Water Flow Test Date of Test Time of Test Static Press Residual Press Flow Elevation Commodity Storage Ht Storage Method 0 Single Row R Double Row A Mult Row C K Flue Spacing Longitudinal 1993 Horizontal Barriers Provided Hydraulic Design Information Sheet Name AMBULATORY CARE CENTER Date 4 -2 -09 Location 240 WEST FRONT STREET PORT ANGELES WA 98363 Building System No REMOTE AREA 2 Contractor SPRINX FIRE PROTECTION INC Contract No Calculated By JGF Drawing No FP -2 0 Construction Combustible (X) Non Combustible Ceiling Height 10'6 Occupancy LIGHT HAZARD MEDICAL BUILDING (X) NFPA 13 (X) Lt Haz Ord Haz Gp 1 2 3 Ex Haz NFPA 231 NFPA 231C Figure Curve Other Specific Ruling Made By Date Operation 907 1000 195 10'6 Solid Piled 0 0 100 Note QUICK RESPONSE SPRINKLERS AREA REDUCTION System Type (X) Wet Dry Deluge Preaction Other Sprinkler /Nozzle Make VIKING Model VK302 Size 1/2" K- Factor 5 6 Temp Rat 155 Calculation Flow Required 320 841 Press Required 57 9848 At Node TEST Summary C- Factor Used 120 Overhead 140 Underground Location CLOSEST HYDRANT TO SITE Pump Data Rated Cap 130 Press Source of Information KEN DEBUC (PORT ANGELES FIRE DEPT) Class Area Conven Pallet Slave Pallet Tank or Reservoir Cap Elev 107 Elev Well 3056 Proof Flow Location Aisle W Palletized a Rack Auto Storage Encap Solid Shelf Non Open Shelf Clearance Storage to Ceiling Transverse Computer Programs by Hydratec Inc. Route 111 Windham N.H USA 03087 Page 1 Date 031109 Water Supply Curve (C) SPRINX FIRE PROTECTION INC PORT ANGELES AMBULATORY CARE City Water Supply C1 Static Pressure 130 C2 Residual Pressure: 107 C2 Residual Flow 3056 150 I 140 130 P 120 R 110 E 100 S 90 S 80 U 70 R 60 E 50 D 40 30 20 10 r C1 D2 .ns........... 400 800 1200 1600 2000 2400 FLOW (N "185) 2800 r_9 3200 Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Demand D1 Elevation D2 System Flow D2 System Pressure Hose (Adj City Hose Demand D3 System Demand Safety Margin 3600 Page 2 Date 031109 4 548 220 841 57 985 100 320 841 71 660 Flow Diagram SPRINX FIRE PROTECTION INC Page 3 PORT ANGELES AMBULATORY CARE Date 031109 89.9 42.2 49 48 47 46 45 65 20.6 I 89.9 I 130.9 81 7 20.5 44 43 42 a 41 -0. 40 39 106.6 60.3 I 220.8 20 I 220.8 R/2 BOR I 220.8 1 TOR TEST Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Fittings Used Summary SPRINX FIRE PROTECTION INC Page 4 PORT ANGELES AMBULATORY CARE Date 031109 Fitting Legend Abbrev Name Units Summary 1 3/ �2 Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch 1 1' /e 1 2 2% 3 3A 4 5 6 8 10 12 14 16 18 20 24 B Generic Butterfly Valve 0 0 0 0 0 0 7 10 0 12 9 10 12 19 21 0 0 0 0 0 E 90' Standard Elbow 2 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G Generic Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T 90' Flow Thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Zic Wilkins 350ADA Fitting generates a Fixed Loss Based on Flow Computer Programs by Hydratec Inc. Route 111 Windham N H USA 03087 Pressure Flow Summary STANDARD SPRINX FIRE PROTECTION INC Page 5 PORT ANGELES AMBULATORY CARE Date 031109 Node Elevation K -Fact Pt No. Actual Pn Flow Actual D101 9.5 5.6 12.25 na 19.6 D102 9.5 5.6 12.25 na 19.6 51 10.5 K K EQ01 12.19 na 19.6 52 10.5 K K EQ02 13.37 na 20.22 50 10.5 K K EQ01 18.74 na 24.3 45 10.5 K K EQ01 13.44 na 20.58 46 10.5 K K EQ02 15.33 na 21.65 47 10.5 K K EQ02 16.92 na 22.74 48 10.5 K K EQ02 20.38 na 24.96 49 10.5 25.92 na 39 10.5 K K EQ01 13.33 na 20.5 40 10.5 14 77 na 41 10.5 K K EQ02 14.91 na 21.34 42 10.5 K K EQ02 20.39 na 24.96 43 10.5 20.71 na 44 10.5 26.15 na 20 16.0 38.3 na RI2 16.0 45.02 na TOR 8.0 49.1 na BOR 1.0 55.98 na TEST 0.0 57.98 na 100.0 The maximum velocity is 20 63 and it occurs in the pipe between nodes 43 and 44 Density Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Area Press Req. 0.1 196 7 0 0.1 196 7 0 N otes Final Calculations Hazen Williams SPRINX FIRE PROTECTION INC Page 6 PORT ANGELES AMBULATORY CARE Date 031109 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref 'C' or Ftng's Pe Pv Point Qt Pf /Ft Eqv Ln. Total Pf Pn Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 D101 19 60 1 049 1E 2.0 1 000 12.250 K Factor 5 60 to 120 0 0 0 2.000 -0 433 EQ01 19 6 0 1253 0 0 3.000 0 376 Vel 7.28 00 19 60 12.193 K Factor 5 61 D102 19 60 1 049 1T 5 0 1 000 12.250 K Factor 5 60 to 120 0 0 0 5 000 -0 433 EQ02 19 6 0 1253 0 0 6 000 0 752 Vel 7.28 00 19 60 12.569 K Factor 5.53 *P -6 51 19 60 1 049 1E 2.0 7 410 12.193 K Factor node EQ01 to 120 0 0 0 2.000 "0 0 52 19 6 0 1254 0 0 9 410 1 180 Vet 7.28 52 20.22 1 38 0 0 11 450 13.373 K Factor node EQ02 to 1200 00 00 00 40 39.82 0 1223 0 0 11 450 1 400 Vel 8 54 00 39 14 773 K Factor 10 36 *P -9 50 24.30 1 049 1T 5 0 5.580 18 740 K Factor node EQ01 to 1200 00 5000 00 43 24 3 0 1866 0 0 10 580 1 974 Vel 9 02 00 24 30 20 714 K Factor 5.34 *P 12 45 20.58 1 049 1E 2.0 11 830 13.437 K Factor node EQ01 to 120 0 0 0 2.000 0 0 46 20.58 0 1371 0 0 13.830 1 896 Vel 7 64 46 21 64 1 38 0 0 11 660 15 333 K Factor node EQ02 to 1200 00 00 00 47 42.22 0 1364 0 0 11 660 1 590 Vel 9 06 47 22.75 1 38 0 0 11 410 16 923 K Factor node EQ02 to 1200 00 00 00 48 64.97 0 3026 0 0 11 410 3.453 Vel 13.94 48 24.95 1 38 1T 6 0 4 040 20 376 K Factor node EQ02 to 1200 00 6000 00 49 89.92 0 5522 0.0 10 040 5.544 Vel 19.29 49 0 0 2.703 0 0 11 000 25 920 to 1200 00 00 00 44 89 92 0 0209 0 0 11 000 0.230 Vel 5 03 00 89 92 26 150 K Factor 17 58 *P 15 39 20 50 1 049 1T 5.0 5 580 13.333 K Factor node EQ01 to 120 0 0 0 5.000 0 0 40 20 5 0 1361 0 0 10 580 1 440 Vel 7 61 Final Calculations Hazen Williams SPRINX FIRE PROTECTION INC Page 7 PORT ANGELES AMBULATORY CARE Date 031109 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref 'C' or Ftng's Pe Pv Point Qt Pf /Ft Eqv Ln. Total Pf Pn 40 39 81 1 38 0 0 0 500 14 773 to 1200 00 00 00 41 60 31 0.2640 0 0 0 500 0 132 41 21 35 1 38 0 0 11 870 14 905 to 1200 00 00 00 42 81 66 0 4620 0 0 11 870 5.484 Notes Vel 12.94 K Factor node EQ02 Vel 17 52 42 24 96 1 61 0 0 0 910 20 389 K Factor node EQ02 to 1200 00 00 00 43 106 62 0 3571 0 0 0 910 0 325 Vel 16 80 43 24 30 1 61 1T 8 0 2.410 20 714 to 120 0 0 0 8 000 0 0 44 130 92 0 5222 0 0 10 410 5 436 Vel 20 63 44 89 92 2.703 1E 9 325 103.910 26 150 to 120 0 1T 18 651 27.976 2.382 20 220 84 0 1102 0 0 131 886 14 532 Vel 12.35 20 0 0 2.703 2E 18.651 23.660 38.300 to 120 0 1T 18 651 37 302 0 0 RI2 220 84 0 1102 0 0 60 962 6 717 Vel 12.35 RI2 00 431 1E 13.937 12.700 45017 to 120 0 1T 27 874 41 811 3.465 TOR 220 84 0 0114 0 0 54 511 0 619 Vel 4 86 TOR 0 0 4 31 1E 13.937 8 000 49 101 to 120 0 1B 16 724 30 661 6.443 Fixed loss 3.411 BOR 220 84 0 0114 1Zic 0 0 38.661 0 439 Vel 4 86 BOR 0 0 4 1 2E 29 067 83.000 55.983 to 140 0 1G 2.907 61 041 0 433 TEST 220 84 0 0109 1T 29 067 144 041 1 569 Vel 5 37 100 00 Qa 100 00 320 84 57.985 K Factor 42.13 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 August 27 2004 Sprinkler 41 a WING® 1 PRODUCT NAME Viking Microfast® and MicrofastHP® Model M Quick Response Pendent •prinklers 2. MANUFACTURER The Viking Corporation 210 N. Industrial Park Road Hastings, Michigan 49058 U.S.A. Telephone (269) 945 -9501 (877) 384 -5464 Fax: (269) 945 -9599 e-mail techsvcs @vikingcorp.com 3. PRODUCT DESCRIPTION Viking Microfast® and MicrofastHP® Quick Response Pendent Sprinklers are small, thermosensitive spray sprin klers available with several finishes temperature ratings, and orifice sizes to meet design requirements. The special Poly finishes and Teflon® coatings can be used in decorative applications where colors are desired In addition, these two finishes are corrosion resis- tant and provide protection against many corrosive environments. The pip cap and`sealing assembly of the sprinkler is held in place by a bulb tye operating element. During fire condi- tions, when the temperature around the sprinkler reaches its operating tempera- ture, the heat sensitive liquid in the glass bulb expands, causing the bulb to shatter releasing the pip -cap and seal- ing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern to extinguish or control the fire. Form No F_081296 Nominal Sprinkler Temp. Rating (Fusing Point) 155 °F (68 °C) 175 °F (79 °C) 200 °F (93 °C) 286 °F (141 °C) TECHNICAL DATA 4. TECHNICAL DATA LISTINGS AND APPROVALS Referto theApproval Chart on page 41 b Glass -bulb fluid temperature rated to -65 °F 55 °C) Minimum Operating Pressure. 7 psi (48,3 kPa) RATED WATER WORKING PRES- SURE Sprinklers VK317 and VK342 are rated for use with water working pressures ranging from the mini- mum 7 psi (48,3 kPa) up to 250 psi (1 724 kPa) for high pressure sys- tem's. High pressure (HP) sprin- klers can be identified by locating the number `250' on the deflector All Other Sprinklers: Maximum 175 psi (1 207 kPa) wwp. Factory tested hydrostatically to 500 psi (3 448 kPa) Testing: U S.A. Patent No 4,831,870 SPRINKLER MATERIALS Frame. Brass Castings UNS- C84400 Deflector Brass UNS- C51000 or Cop per UNS- C19500 for Sprinkler Base Part Nos. 06662B, 06666B 06765B, Maximum Ambient Ceiling Temperature 100 °F (38 °C) 150 °F (65 °C) 150 °F (65 °C) 225 °F (107 °C) Sprinkler Temperature Classification Ordinary Intermediate Intermediate High Sprinkler Finishes: Brass, Chrome Enloy® (patents pending), White Polyester (White Poly finish for P/N 06662B), Black Polyester (Black Poly finish for P/N 06662B), and Black Teflon Corrosion- Resistant Coatings White Polyester (White Poly finish for P/N 06662B), Black Polyester (Black Poly finish for P/N 06662B). and Black Teflon Footnotes 1 Based on NFPA -13 Other limits may apply depending on fire loading, sprinkler location, androther requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 2 The temperature rating is stamped on the deflector 3 The corrosion resistant coatings have passed standard corrosion tests required by particu- lar approving agencies. Refer to the approval chart on page 41 b. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed environment. The coatings indicated are applied to the exposed exterior surfaces only NOTE. The sprihg is exposed on sprinklers with Teflon Coating or Poly finishes. Bulb Color Red Yellow Green Blue MICROFAST MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS 12104 Copper UNS- C19500 for Sprinkler 12282. Brass UNS- C26000 for all other Part Nos. Bushing (for Sprinkler Base Part Nos. 06718B 06720B and 12290): Brass UNS- C36000 Bulb Gl nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Screw Brass UNS- C36000 Pip Cap and Insert Assembly Copper UNS- C11000 and Stainless Steel UNS- S30400 Pip Cap Attachment: Brass UNS- C36000 Ejector Spring (Part No 12104): Stain- less Steel Sprinklers with Teflon® Coating Belleville Spring: Nickel Alloy exposed Screw Brass UNS- C36000 Nickel plated Pip Cap Teflon® Coated Sprinklers with Polyester Coating or Poly Finish Belleville Spring: Nickel Alloy exposed AVAILABLE FINISHES Brass, Chrome Enloy® (patents pend- ing), White Polyester (White Poly finish for Sprinkler 06662B), Black Polyester (Black Poly finish for Sprinkler 06662B), and Black Teflon® ACCESSORIES Sprinkler Cabinets (Available since 1971): A. Six -head capacity Part No. 01724A B Twelve -head capacity Part No. 01725A Sprinkler Wrenches A. Standard Wrench. Part No. 10896W/B (available since 2000) or 05000CW /B (no longer avail- able). B Wrench for coated and recessed Viking Microfast® and MicrofastHF® QR Pendent Sprinklers: Part No 07398W* (available since 1990), or Part No 12144W/B* available since 2003. NOTE. Recessed pendent sprinklers with protec tive caps must use wrench 12144W/B A W ratchet is required (not available through Viking). Refer to the 'SPRINKLER ACCES- SORIES" section of the Viking Engi- neering and Design Data book. Note: Units of measure in parentheses may be approximations. Replaces page 41 a -b dated May 14 2004 (updated deflector materials). Refer to technical data page QR1 2 for care, in- stallation, and maintenance information. Sprinkler 41 b WING® I Thread Size NPT ..BSP W 15 mm 3/4' I 3/4" i 2 -1/4" (58 mm) 12/,' 115mml 1 5mm 15mm 10mm 20 mm 20 mm 15 mm Standard Orifice Mix. Pressure I Base Part SIN Nominal K- Factor( Overall Length PSIG I NumhP� U.S. I metric I Inches mm 175 I 066695 VK302 5 6 I R 1 _2 1/4 I SR Larne Orifice 115 0fi6_66R VK357 R n I 11„5 I 9 R/8 60 175 19104 VK35? R 0 I 1 1 5 I 9 1/4 58 175 067655 VK352 R 0 1 1 5 2 3/8 60 Small Orifice? 175 067188 VIS3 9 8 I4 n 1 2 3/16 175 067205 I VK331 4. I 6 0 9 1/4 175 066325 VK331 4 9 I 6 n I 9 3/8 i Maximum 250 PSI WWP Standard Orifice Nominal Factor Over Lenoth SIN I U.S. I metric Inc mm VK317:' 5 6 R,1 I 9 1L4 SR Small Orifiice 250 I 12 290 VK342 2 8 I 40 I 2 3/16 56 I A3X, f3 iv I Thread Size Max. Pressure I Base Part I NPT BSP PSIG I Numberl 15 mm 250 I 12282 Approved Temperature Ratings 1 A 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 B 155 °F (68 °C), 175 °F (79 °C), and 200 °F 3 (93 °C) C 155 °F (68 °C) 4 Quick Response Pendent Sprinkler Quick Response Pendent Sprinkler with a Standard 1/8' (3,1 mm) Surface- Mounted Escutcheon i Ceiling Opening Size: 2 5/16' (59 mm) Minimum, 2 1/2' (64 mm) Maximum. TECHNICAL DATA Approval Chart Microfast and MicrofastHP Quick Response Pendent Sprinklers Maximum 175 PSI WWP Approved Finishes Brass, Chrome -Enloe White Poly Finish Black Poly Finish and Black Teflon ®11 Brass and Chrome -Enloe Brass, Chrome Enloy White Polyester Black Polyesterll and Black Teflon Brass Chrome Enloy White Poly Finish, and Black Poly Finish 2° 1 -3/4" (51 mm) (.45 mm) Maximum 1 I 2 -1/8" (54 mm) 56_ A3X a3Y 58 A3X E33Y I 50 1 -1/2" (32 mm) Minimum Quick Response Pendent Sprinkler Installed with the Viking Microfast Model F 1 Adjustable Escutcheon Figure 1 Replaces page 41' a -b, dated May 14 2004 (updated deflector materials). Refer to tech- nical data page QR1 2 for care, installation, and maintenance information. August 27 2004 MICROFAST MicrofastHP QUICK RESPONSE PENDENT SPRINKLERS Temperature KEY T Finish A1X4 Escutcheon (if applicable) Listinos and Aonroval" cULus I FM I NYC 'VdS LPCB. CE 5) A1X B1Y IA4X. B4YIAIX. ROY C2__A4X A4X I A:1X 133Y 1A 3X F. 9X 92Y AYYI I I C2 I A3X R3Y I IA3X R3Y A?X IA3X Bay] I A3X Fi3YI I C21 Listinos nd Aoorovals cULus j FM NYC 'VdSJLPCB A3X R3YI A3X I CE Footnotes 1 Base part number is shown. For complete part number refer to Viking's current price schedule. 2 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Checkwith the manufacturer for any additional approvals. 3 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219- 76 -SA. 4 The sprinkler orifice is bushed. 5 CE Certified, Standard EN 12259 -1 EC- certificate of conformity 0832 -CPD -2001 6 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 7 cULus Listings and NYC Approvals limited to Light- Hazard Occupancies with hydraulically calculated wet systems. 8 Metric K- Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K- Factor shown by 10.0 9 FM Approved for use only in wet -pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies de- scribed in the Factory Mutual Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins. 10 The Viking Microfast Model F 1 Adjustable Escutcheon is considered a surface- mounted escutcheon because it does not allowthe fusibleele- ment of the sprinkler to be recessed behind the face of the wall or ceiling. 11 cULus Listed as corrosion resistant. 12 Acc ppted for use, City of New York Department of Buildings, MEA 89 -92 -E, Vol XVI. 13 Refer to the 'Sprinkler Accessories' section of the Viking Engineering and Design Data book for technical data on approved escutcheons and other accessories. 2 -1/8" (54 mm) 1 -3/4" (45 mm) Maximum I 1 -1/8 (28,6 mm) Minimum Quick Response Pendent Sprinkler Installed with the Viking Micromatic Model E 1 Recessed Escutcheon Form No F_081296 .i A3X Approved Escutcheons X Standard surface mounted escutcheon or the Viking Microfast Model F 1 Ad- justable Escutcheon Y Standard surface mounted escutch- eon or the Viking Microfast Model F 1 Adjustable Escutcheon or recessed with the Viking Micromatic Model E 1 or P Recessed Escutcheon May 14 2004 NIKING® PRODUCT NAME Viking Microfast® and MicrofastHP® Model M Quick Response Upright and Conventional Sprinklers 2. MANUFACTURER The Viking Coi:poration 210 N. Industrial Park Road Hastings, Michigan 49058 U S.A. Telephone (269) 945 -9501 (877) 384 -5464 Fax: (269) 945 -9599 e -mail: techsvcs @vikingcorp.com 3. PRODUCT DESCRIPTION Viking Microfast® and MicrofastHP® Quick Response Upright and Conven- tional (Old Style) Sprinklers are small thermosensitive spray sprinklers equipped with a 3 mm glass bulb Viking Microfast® and MicrofastHP® Quick Response Upright and Conven- tional Sprinklers are available with sev- eral finishes temperature ratings, and orifice sizes to meet design require- ments. The special Polyester and Tef- lon® coating can be used in decorative applications where colors are desired. In addition, the Polyester and Teflon® coatings are corrosion resistant, provid- ing protection against many corrosive environments The pip cap and sealing assembly of the sprinkler is held in place by a 3 mm glass bulb. During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat sensitive liquid in the glass bulb ex- pands, causing the bulb to shatter re- Sprinkler Temperature I Nominal Sprinkler Temperature Classification Rating (Fusina Point) Note. Units of measure in parentheses may be approximations. Form No F_080488 TECHNICAL DATA Conventional Upright leasing the pip -cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler de- flector forming a uniform spray pattern to extinguish or control the fire. 4 TECHNICAL DATA LISTINGS AND APPROVALS Refer to the Approval Chart on page 51 b Glass -bulb fluid temperature rated to -65 °F 55 °C). Minimum Operating Pressure: 7 psi (48,3 kPa). RATED WATERWORKING PRESSURE Sprinklers VK315 and VK340 are rated for use with water working pressures ranging from the mini- mum 7 psi (48,3 kPa) up to 250 psi (1 724 kPa) for high pressure sys- tems. High pressure (HP) sprin- klers can be identified by locating the number '250' on the deflector. All Other Sprinklers: Maximum 175 psi (1 207 kPa) wwp. Factory tested hydrostatically to 500 psi (3 448 kPa). Max. Ambient I Bulb Ceiling Temp Color Ordinary I 155 °F (68 °C) 100 °F (38 °C) Red Intermediate I 175 °F (79 °C) 150 °F (65 °C) Intermediate i 200 °F (93 °C) I 150 °F (65 °C) I Green High I 286 °F (141 °C) I 225 °F (107 °C) I Blue Sprinkler Finishes: Brass, Chrome Enloy® (patents pending), White Polyester (White Poly finish for Part Nos. 06661B, 06665B, 06764B, 07060, and 12281), Black Polyester (Black Poly finish for Part No. 06661 B), and Black Teflon Corrosion- Resistant Coatings White Polyester (White Poly finish for Part Nos. 06661B 06665B, 067648 07060 and 12281), Black Polyester (Black Poly finish for Part No 06661 B). and Black Teflon Footnotes 1 Based on NFPA -13. Other limits may apply depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 2 The temperature rating is stamped on the deflector 3 The corrosion- resistant coatings have passed standard corrosion tests required by particu- lar approving agencies. Refer to the approval chart on page 51 b. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed environment. The coatings indicated are applied to the exposed exterior surfaces only NOTE. The spring is exposed on sprinklers with Polyester Finishes and Teflon coating. Table 1 Sprinkler 51 a MICROFAST AND MicrofastHP QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS Spring: U S.A. Patent No. 4 167,974 Bulb U S.A. Patent No 4 796 710 Testing: U S.A. Patent No 4 831,870 SPRINKLER MATERIALS Frame. Brass Castings UNS- C84400 Deflector Copper UNS- C19500 for Sprinkler Base Part Nos. 06661B 06665B 07060 and 12281 Brass UNS- C26000 for all other Part Nos. Bushing (for Sprinkler Base Part Nos. 06719B 06717B and 12286): Brass UNS- C36000 Bulb. Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Screw Brass UNS- C36000 Pip Cap and Insert Assembly Copper UNS- C11000 and Stainless Steel UNS- S30400 Sprinklers with Teflon® Coating Belleville Spring: Nickel Alloy exposed Screw Nickel plated Pip Cap. Teflon® Coated Sprinklers with Polyester Coating Belleville Spring Sealing Assembly Exposed AVAILABLE FINISHES Brass, Chrome Enloy® (patents pend- ing), White Polyester (White Poly finish for Part Nos. 06661 B 06665B 06764B 07060 and 12281), Black Polyester (Black Poly finish for Part No 06661 B), and Black Teflon ACCESSORIES Sprinkler Cabinets: A. Six -head capacity Part No. 01724A B Twelve -head capacity Part No 01725A Available since 1971 Sprinkler Wrenches. A. Standard Sprinkler Wrench. Part N o 10896W/B (available since 2000) or 05000CW /B (no longer available). B. Wrench for coated and recessed sprinklers. Part No 07398W` A V2 ratchet is required (not available from Viking). Refer to the "SPRINKLER ACCES- SORIES" section of the Viking Engi- neering and Design Data book. Replaces page 51 a -b dated February 27 2004 (Sprinkler 06931 B is now VK327). Refer to technical data page QR1 2 for general care, installation, and mainte- nance information. Sprinkler 51 b \JIKING® NPT. BSP 34 i 15mm l 15 mm %2 15mm Approved Temperature Ratings A 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) B 155 °F (68 °C) Approval Chart May 14 2004 MICROFAST AND MicrofastHP QUICK RESPONSE UPRIGHT AND CONVENTIONAL SPRINKLERS KEY Temperature y 1 v Finish Microfast® and MicrofastHP® Quick Response Al Escutcheon (if applicable) Upright and Conventional Sprinklers Maximum 175 PSI WWP Standard Orifice Thread Size Max' S rinkler Descri tion Nominal 1 Overall 2 Pressure P p K- factor Length i Listings and Approvals PSIG Sprinkler I Base Part No. SIN U.S. metric Inches mm cULus FM NYC" VdS, LPCB I C E 3 I 175 I Upright 06661B VK300 I 5.6 I 8,1 2 3/16 56 A6 I A7 I A6• 175 I Upright 07060 VK345I 5.6 1 8,1 2 3/161 56 1 A3 B1 A7 I A7 175 I Conventional 06766B VK310 I 5 6 I 8,1 1 2 3/16 I 56 A5 A5 A5 A5 Large Orifice 3/4" 120 mm .175 Upright 06665B VK350I 8.0 11,5 12 5/16 I 59 A4 A3 A4 I i31 '14 20 mm 175 Upright 06764B VK350I 8.0 11,5 12 5/16 I 59 A4 1 I A4 I i 3/4" 120 mm 175 Conventional 06768B VK354 I 8.0 I 11,5 12 5/161 59 AS I AS I Small Orifices 15 mm 175 I Upright 06717B VK325 I 2.8 I 4,0 2 3/16_1 56 A2 Al A2. 15 mm 175 I Upright 06719B VK327I 4.2 6,0 2 3/161 56 A2 i A2 10 mm 175 I Upright I 06931B I VK3271 4.2 1 6,0 12 3/16 I 56 I I B1 I Maximum 250 PSI WWP Standard Orifice Thread Size Max. Sprinkler Description Nominal Overall I 2 Pressure p K- factor Length Listings and Approvals I BSP I PSIG I Style Base Part No. SIN U.S. I metric Inches I mm cULus FM NYC VdS` LPCB 1 E Yz 1 15 mm. I 250 I Upright 12281 VK315 5.6. I 8,1 12 3/161 56 A2 1 I A2 I Small Orifice ;2 115 mm I 250 I Uoright I 12286 VK3401 2.8 I 4.0 12 3/16 I 56 A2 I A2 I 1 Approved Finishes 1 Brass and Chrome Enloy® 2 Brass, Chrome- Enloy White Polyester' Black Polyester' and Black Teflon ®7 3 Brass, Chrome Enloy® and White Poly Finish 4 Brass, Chrome Enloy® White Poly Finish' Black Polyester' and Black Teflon ®7 5 Brass, Chrome Enloy® White Polyester' and Black Polyester" 6 Brass, Chrome Enloy White Poly Finish' Black Poly Finish' and Black Teflon 7 Brass, Chrome-Enloy®, White Poly Finish, and Black Poly Finish Footnotes 1 Base part number is shown. For complete part number refer to Viking's current price schedule. 2 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 3 C E Certified, Standard EN 12259 -1 EC- certificate of conformity 0832 -CPD -2001 4 The sprinkler orifice is bushed. 5 Listings and Approvals are limited to Light Hazard occupancies with hydraulically calculated wet systems only 6 Listed by Underwriters Laboratories Inc. for use in the U.S and Canada 7 cULus Listed and NYC Approved as corrosion- resistant. B FM Approved for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory Mutual Global Loss Prevention Data Sheets and Technical Advisory Bulletins. 9 Metric K- Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K-Factor shown by 10.0 10 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219- 76-SA. 11 Accepted for use, City of New York Department of Buildings, MEA 89 -92 -E, Vol. 16. Replaces page 51 a -b dated February 27 2004 (Sprinkler 06931 B is now VK327). Refer to Form No F_080488 technical data page QRI 2 for general care, installation, and maintenance information. May 2, 2003 NIKING® 1 PRODUCT NAME Viking Microfast® and MicrofastHP® Quick Response Model M -5 Horizontal Sidewall Sprinklers Sprinkler SIN VK305t (Sprinkler Base Part Number 12121) HP Sprinkler SIN VK319t (Sprinkler Base Part Number 12285) t The SIN is stamped on the sprinkler deflector 2. MANUFACTURER The Viking Corporation 210 N. Industrial Park Road Hastings, Michigan 49058, U.S.A. Telephone (269) 945 -9501 (877) 384 -5464 Fax: (269) 945 -9599 e -mail: techsvcs @vikingcorp.com 3. PRODUCT DESCRIPTION Viking Microfast® and MicrofastHP® Quick Response Horizontal Sidewall Sprinklers are small, thermosensitive Sprinkler Temperature Classification Ordinary Intermediate Intermediate High Form No. F_030103 TECHNICAL. DATA spray sprinklers available with several different finishes and temperature rat- ings to meet varying design require- ments. The special Polyester and Tef- lon coatings are available for use in decorative applications. In addition, these two finishes are listed as corro- sion- resistant finishes for protection against many corrosive environments The pip cap and sealing assembly of the sprinkler is held in place by a 3 mm glass bulb. During fire conditions when the temperature around the sprinkler reaches its operating temperature the heat sensitive liquid in the glass bulb expands, causing the bulb to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler de- flector forming a uniform spray pattern to extinguish or control the fire. 4 TECHNICAL DATA LISTINGS AND APPROVALS Refer to the Approval Chart on page 43 b. Thread Size. 1 h NPT (15 mm) Nominal K- Factor 5.6 U.S (8,1 metric Metric K- Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multi plythe metric K- Factorshown by 10.0. Overall Length: 2 11/16' (68 mm) Glass -bulb fluid temperature rated to -65 °F (55 °C) Nominal Sprinkler Temperature Maximum Ambient Rating (Fusing Point) !Ceiling Temperature' 155 °F (68 °C) 100 °F (38 °C) 175 °F (79 °C) 150 °F (65 °C) 200 °F (93 °C) 150 °F (65 °C) 286 °F (141 °C) 225 °F (107 °C) Bulb Color Red I Yellow Green Blue Sprinkler Finishes: Brass, Bright Brass, Chrome- Enloy® (patents pending) White Polyes- ter Navajo White Polyester Black Polyester and Black Teflon® Corrosion Resistant Coatings White Polyester Navajo White Polyester Black Polyes- ter and Black Teflon Footnotes 1 Based on NFPA -13. Other limits may apply depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation stan- dards. 2 The temperature rating is stamped on the deflector 3 The corrosion- resistant coatings have passed standard corrosion tests required by particu- lar approving agencies. Refer to the approval chart. These tests cannot and do not repre- sent all possible corrosive environments. Prior to installation, verify through the end -user that the coatings are compatible with or suitable for the proposed environment. The coat- ings indicated are applied to the exposed exterior surfaces only NOTE: The spring is exposed on the Teflon coated and Polyester coated sprinklers. Table 1 Sprinkler 43 a MICROFAST AND MicrofastHP QUICK RESPONSE HSW SPRINKLERS (SIN VK305 VK319) Minimum Operating Pressure 7 psi (48,3 kPa) RATED WATER WORKING PRES- SURE Sprinkler VK319 is rated for use with water working pressures ranging from the minimum 7 psi (48,3 kPa) up to 250 psi (1 724 kPa) for high pressure systems. High- pressure (HP) sprinklers can be identified by locating the number `250' on the deflector Sprinkler VK305 is rated to a maxi- mum 175 psi (1 207 kPa) wwp Factory tested hydrostatically to 500 psi (3 448 kPa) Spring U.S.A. Patent No 4 167,974 Deflector* U.S.A. Patent No 4,296,816 Testing U.S.A. Patent No 4 Bulb U.S.A. Patent No. 4 796,710 SPRINKLER MATERIALS Frame Brass Castings UNS- C84400 Deflector Copper UNS- C19500 Bulb Glass, nominal 3 mm diameter Belleville Spring Sealing Assem- bly Nickel Alloy coated on both sides with Teflon Tape Screw Brass UNS- C36000 Pip Cap and Insert Assembly Copper UNS- C11000 and Stainless Steel UNS- S30400 Pip Cap Attachment: Brass UNS C36000 Teflon® Coated Sprinklers Belleville Spring Sealing Assembly Ex posed Screw Nickel plated Pip Cap Teflon® Coated Polyester Coated Sprinklers Belleville Spring Sealing Assembly Ex posed ACCESSORIES Sprinkler Wrenches A. Standard Wrench. Part Number 10896W/B (available since 2000) or 05000CW /B (no longer available) B. Wrench for coated and recessed sprinklers: Part Number 07398W (available since 1990) *A' ratchet is required (not available from Vi- king). Refer to the `SPRINKLER ACCES- SORIES" section of the Viking Engi- neering and Design Data book. Note Units of measure in parentheses may be approximations. Replaces page 43 a -b dated February 28, 2003 (new sprinkler base part number and SIN) Refer to technical data page QR1 -2 for general care, installation, and maintenance information. Sprinkler 43 b WING® I Thread Size Max. Pressure _1L ch mm PSIG 1/ 15 175 I Thread Size Max- Pressure I Inch min H PSIG I 1 15 175 For Deflectors must be LThread Size Max Pressure Sprinkler I Inch mm I PSIG Base Part No. I 1/, 15 250 12285 I Approved Temperature Ratings A 155 °F (68 °C), 175 °F (79 °C) 200 °F (93 °C), 1 and 286 °F (141°C) B 155 °F (68 °C) 175 °F (79 °C) and 200 °F (93 2 1 i X 7'(31,8 mm) 1/2' (15 mm)- NPT Microfast QR Horizontal Sidewall Sprinkler VK305 or VK319 Sprinkler VK305 or VK319 installed with a Standard 1/8' (3,1 mm) Surface- Mounted Escutcheon Approval Chart Microfast and MicrofastHP Quick Response Horizontal Sidewall Sprinklers Maximum 175 PSI WWP For Light or Ordinary Hazard Occupancies. Deflectors must ne located 4' to 12' (102 mm to 305 mml below the ceilinn 1 Sprinkler SIN I Nominal K- Factor I Overall Lenoth u 12121 I VK305 I 5.6 I 8 1 P-11/16 i Maximum 175 PSI WWP For Light Hazard Occupancies Only Deflectors must be located 4" to 6' (102 mm to 152 mm) below the cei ina- Sprinkler 1 SIN I No final K- Factor I Overall Len Base Part No. I U.S. I metric Inch i mm I 6 12121 VK305 I 5 5 I 8 1 2 i 68 Base Part No. S metric 1ar1 I A1X R1W A1X Maximum 250 PSI WWP Light or Ordinary Hazard Occupancies. located 4' to 12" (102 mm to 305 mm) below the ceilina- Nominal K- Factor Overall Lenoth SIN VK319 Approved Finishes Brass, Bright Brass, Chrome- Enloy White Polyesters Navajo White Poly- ester Black Polyester° and Black Teflon Brass Footnotes 1 Base part number is shown. For complete part number refer to Viking's current price schedule. 2 Metric K- Factor shown is for use when pressure is measured in kPa When pressure is measured in BAR, multiply the metric K Factor s hown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 Accepted for use, City of New York Department of Buildings, MEA 89 -92 -E, Vol. 16. 5 The Microfast Model F 1 Adjustable Escutcheon is considered a surface mounted escutcheon because it does not allow the fusible element of the sprinkler to be recessed behind the face of the wall or ceiling. 6 FM Approved for use in wet pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory Mutual Global Loss Prevention Data Sheets and Technical Advisory Bulletins. 7 Listed by Underwriter's Laboratories, Inc. for use in the U.S. and Canada. 8 cULus Listed as corrosion resistant. NOTE: Must be installed with deflector located between 4' and 6' (102 mm and 152 mm) from walls. Exception: Deflector may be located less than 4" (102 mm) from the wall in which the sprinkler is installed. Always install with the top of the deflector aligned parallel with the ceiling or roof. 2- 1r /I6' (68,3 mm) U.S. metric- i mm 56 81 Sprinkler VK305or VK319 Installed with a Microfast Model F -1 Adjustable Escutcheon Figure 1 Replaces page 43 a -b dated February 28, 2003 (new sprinkler base part number and SIN) Re- fer to technical data page QR1 -2 for general care, installation, and maintenance information. May 2, 2003 MICROFAST AND MicrofastHP QUICK RESPONSE HSW SPRINKLERS (SIN VK305 VK319) Temperature KEY Finish AIX4 Escutcheon (if applicable) Listings and Aporovals I mm cSJLus 68 I nth Listings and Approvals I cUI ,fie FM I NYC I I A2X I Listings and Aporovals I cULus I FM I NYC I 2 11/16 I 68 I A1X R1W I I A1X Approved Escutcheons W Standard surface mounted escutcheons or the Microfast Model F 1 Adjustable Es- cutcheons or recessed with the Micromatic Model E 1 or E 2 Recessed Escutcheon X Standard surface escutcheons or the Microfast Model F 1 Adjustable Escutch- eon Form No F_030103 May 13 2005 Sprinkler 106 a NIKING® 1 PRODUCT NAME Viking Model M Quick Response Dry Horizontal Sidewall Sprinklers Adjustable Recessed Sprinkler Base Part No 08386 (SIN VK182) Adjustable Standard Sprinkler Base Part No 08384 (SIN VK178) Plain Barrel Sprinkler Base Part No 08388 (SIN VK174) Available since 1993 2. MANUFACTURER The Viking CorpOration 210 N Industrial Park Road Hastings, Michigan 49058, USA Telephone: (269) 945 -9501 (877) 384 -5464 Fax: (269) 945 -9599 e -mail: techsvcs @vikingcorp corn 3. PRODUCT DESCRIPTION Viking Quick Response Dry Horizontal Sidewall Sprinklers are thermosensitive glass -bulb spray sprinklers suitable for use in areas subject to freezing. They are designed for dry systems and preaction systems where it is necessary to prevent water or condensation from entering the supply nipples before the sprinklers oper ate. They may also be installed in spaces subject to freezing and supplied from a wet system in an adjacent heated area. The sprinkler assembly features a sealed brass inlet and a durable threaded steel barrel with an Electrodeposited Epoxy Base coating. The sprinklers are of the Model M design with a glass bulb operat- ing element and horizontal sidewall deflec tor The glass bulb operating element meets the response criteria for quick re- sponse sprinklers. Viking Dry HSW Sprin- klers are available in finishes and tempera- ture ratings to meet design requirements. The seal at the threaded end of the as- sembly is held in place by force transmit- ted from the compression screw through the glass bulb and internal parts, onto a special sealing spring. During fire condi- tions, the heat sensitive liquid in the glass bulb expands, causing the glass to shat- ter releasing the internal parts to open the waterway Water flowing through the sprinkler orifice strikes the sprinkler de- flector forming a uniform spray pattern to extinguish or control the fire. Viking QR Dry HSW Sprinklers may be installed with the barrel exposed (refer to Figure 1 on page 106 b), or with one of two escutcheon styles. For recessed in- stallations, a recessed style escutcheon with up to 5/8' (15,8 mm) adjustment (see Figure 4) is available For standard installations, the sprinkler is available with an adjustable surface mounted es- cutcheon, which allows up to 2" (50,8 mm) of adjustment (see Figures 2 and 3): Both escutcheon styles slide over -the Note: Units of measure in parentheses may be approximations. Form No F_031993 For Light Hazard Occupancies Only sprinkler deflector allowing installation of the escutcheon after the wall finish has been applied. These sprinklers may be or dered in lengths from 1 -1/2" (38,1 mm) for sprinkler 08384 3' (76,2 mm) for sprinkler 08388, and 3-1/4" (82,5 mm) for sprinkler 08386. They have listings and approvals with a maximum length of 45 -1/2' (1 156 mm) for sprinkler 08384* 47 (1 194 mm) for sprinkler 08388* and 47 1/2' (1 207 mm) for sprinkler 08386* Lengths over the standard length are available, with no approvals, on a `made- to-order" basis: Recessed Dry HSW up to 65 -1/2" (1 664 mm). Adjustable Standard Dry HSW up to 63 -1/2' (1 613 mm). Plain Barrel Dry HSW up to 6F (1 651 mm). Contact the manufacturer for more information. The recessed style is available in 1/4' (6,35 mm) increments, while the adjustable stan- dard escutcheon style and the plain barrel style, installed with no escutcheon, are available in %2" increments. 4 TECHNICAL DATA LISTINGS AND APPROVALS Refer to the Approval Chart on page 106 d. Glass -bulb fluid temperature rated to -65 °F 55 °C). Rated to 175 psi (1 207 kPa) water work- ing pressure. Thread Size: 1 NPT Min. Operating Pressure: 7 psi (48,3 kPa) Nominal K- Factor 5 6 U S. (8,1 met- ric**) for all approved lengths. `Metric K- Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K- Factor shown by 10.0. Factory tested pneumatically at 100 psi (685 kPa). SPRINKLER MATERIALS Frame. Brass Castings UNS- C84400 Sprinkler Temp. Nominal Sprinkler Temp. Classification Ordinary Intermediate Intermediate High 286 °F (141 °C) Ratina (Fusing Pointl 155 °F (68 °C) 175 °F (79 °C) 200 °F (93 °C) QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS Adjustable Recessed Adjustable Standard Plain Barrel Deflector Copper UNS- C19500 Bulb. Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with Teflon Tape Spring Base. Brass UNS- C31400 or UNS- C31600 Screw' Brass UNS- C36000 Pip Cap: Brass UNS- C31600 Ejector Spring: 17 7 Stainless Steel Seat: Copper UNS- C21000 Orifice. Copper UNS- C21000 Washer Stainless Steel UNS- S30400 Gasket: Buna -N Tube. ERW Hydraulic Steel Tube Inlet: Brass UNS- C31600 Support (Internal): Stainless Steel UNS- S30400 Spring (Internal): Stainless Steel UNS- S30200 Barrel: Steel Pipe UNS- G10260 Elec trodeposited Epoxy Base finish Sleeve (for Adjustable Standard style only). Brass UNS- C26000 or UNS- C26800 ESCUTCHEON MATERIALS 1 Adjustable Standard Dry Escutcheon: Brass UNS- C26000 or UNS- C26800 2. Recessed Dry Escutcheon. Cold Rolled Steel UNS- G10080 AVAILABLE FINISHES Recessed: Chrome- Enloy® (patents pending) or White Polyester Standard Adjustable: Chrome- Enloy® or White Polyester sprinklerwith a Chrome Enloy® Sleeve and Escutcheon Plain Barrel. Chrome- Enloy® or Brass (sprinkler only) Maximum Ambient Ceilino Temoeraturel 100 °F (38 °C) 150 °F (65 °Cl 150 °F (65 °C) 225 °F (107 °C) Bulb Color Red Yellow Green Blue 1 Based on NFPA -13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 2 Temperature rating is stamped on the deflector Table 1 Replaces page 106 a -d, dated Dec. 1 2004 (added option for white sprinkler with chrome sleeve and escutcheon for Adj. Standard) Sprinkler 106 b NIKING® ACCESSORIES Standard Dry Sprinkler Wrench Part No. 07297W/B Recessed Dry Sprinkler Wrench: Part No 07565W/B *Requires a separate ratchet (not available from Viking). Replacement Escutcheons: 1 Adjustable Standard Dry Escutcheon: Base Part No 08086F 2. Recessed Dry Escutcheon: Base Part No 05459A 5. ORDERING INFORMATION For proper shipment, specify model, fin- ish, temperature rating, escutcheon type. and length ('A Dimension). Viking Quick Response Dry Horizontal Sidewall Sprin- klers are ordered in specific lengths noted as the A Dimension (see Figures 1 through 4). The A Dimension is the dis- tance from the face of the fitting (tee) to the finished surface of the wall in which it is to be installed. The Viking Quick Re- sponse Dry Horizontal Sidewall Sprinkler must be ordered and manufactured spe- cifically for one of three styles of installa- tion: with the adjustable recessed es- cutcheon (see Figure 4), with the adjust- able standard escutcheon (see Figures 2 and 3), or the plain barrel (see Figure 1). For limits of adjustment for the recessed escutcheon, see Figure 4 Details and limits of adjustment for the standard es- cutcheon style, with 2' (50,8 mm) of ad- justment, are shown in Figures 2 and 3. 6. INSTALLATION WARNING: Viking sprinklers are manu- factured and tested to meet the rigid re- quirements of approving agencies. The sprinklers are designed to be installed in accordance with recognized installation standards. Deviation from the standards or any alteration to the sprinkler after it leaves the factory including, but not limited to: painting, plating, coating, or modification, may render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by Viking. A. Viking sprinklers are to be in- stalled in accordance with the lat- est edition of Viking technical data, the latest standards of the National Fire Protection Associa- tion, FM Global, Loss Prevention Council, Assemblee Pleniere, Verband der Sachversicherer or other similar organizations, and also with provisions of govern- mental codes, ordinances, and standards whenever applicable. The use of dry sprinklers may be limited due to occupancy and haz ard. Refer to the Authority Having Jurisdiction prior to installation. B Sprinklers must be handled with care They must be stored in a cool. dry place in their original shipping con- tainer Never install sprinklers that have been dropped, damaged in any way or exposed to temperatures in excess of the maximum ambient temperature allowed (refer to the temperature chart). Such sprinklers should be destroyed. Never install any glass -bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb If a glass bulb lacks the appropriate amount of fluid, it should be set aside and returned to Viking (or an authorized Viking distributor) for analysis as soon as possible If the sprinkler is not returned to Viking, it should be destroyed immediately C Use only sprinklers listed for corro- sive environments when subject to corrosive atmospheres. Viking OR Dry HSW Sprinklers are not intended for use in corrosive environments. D WARNING. Viking dry sprinklers are to be installed in the 1' outlet or run of malleable or ductile iron threaded tee fittings that meet the dimensional re- quirements of ANSI B16.3 (Class 150), or cast iron threaded tee fittings that meet the dimensional require- ments of ANSI B16.4 (Class 125), even at branch line ends. The threaded end of the dry sprinkler is de- signed to allow the seal to penetrate and extend into the fitting to a prede- termined depth. This prevents con- densation from accumulating and freezing over the sprinkler seal. 1 DO NOT install the dry sidewall sprinkler into a threaded elbow coupling or any other fitting that could interfere with thread pene- tration. Such installation would damage the brass seal. For A Dimension: 1 Determine the distance from the face of tee to the base of sprinkler 2. Round to next higher 12' (12,7 mm) increment, between 3' and 47" (76,2 mm and 1 194 mm). N A Outside diameter 1 -5/16' (33,4 mm) [same as 1 (25 mm) Schedule 40 pipe]. QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS 2. DO NOT install the dry sidewall sprinkler into a coupling or fitting that would allow condensation to accu- mulate above the seal, when lo- cated in an area subject to freezing. 3. NEVER try to modify the dry horizon- tal sidewall sprinkler The sprinklers are manufactured for specific A Di- mensions and cannot be modified. E. The sprinkler must be installed after the piping is in place to prevent me- chanical damage Before installation, be sure to have the correct sprinkler model and style with the appropriate A dimension, temperature rating, ori- fice size, and response characteris- tics. Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time the sprinkler is shipped or handled. 1 Apply a small amount of pipe -joint compound or tape to the male threads only taking care not to al- low a build -up of compound over the brass inlet and seal. NOTE: Sprinklers with protective caps or bulb shields must be contained within the caps or shields before ap- plying pipe joint compound or tape. 2. Install the dry sidewall sprinkler on the piping using the special dry sprinkler wrench only while tak ing care not to damage the sprin- kler DO NOT use a pipe wrench on the barrel of the dry sidewall sprinkler A pipe wrench may damage the barrel finish. 3. To install the escutcheon for the Viking Adjustable Standard Quick Response Dry Horizontal Side wall Sprinkler refer to Figure 3 F After installation, the entire sprinkler system must be tested. The test must Yr IIIIIIIIIIIIIIIIIIIE= Ceiling Wall 4" (102 mm) minimum 6" (152 mm) maximum 2 -7/16" (61,9 mm) L May 13 2005 (12,7 mm) i Do not exceed 6" (152 mm). Do not recess wrench boss. Figure 1 Plain Barrel Quick Response Dry Horizontal Sidewall Sprinkler May 13, 2005 Sprinkler 106 c NIKING® For A Dimension: 1 Determine the distance from face of tee to finished face of wall. 2. Round to nearest Y2" (12,7 mm) between 1 1/2' and 45 -1/2' (38,1 mm and 1 156 �h- mm). NOTE: Deflector will extend approxi- mately 4 -1/4 (108 mm) from wall with 2 1 (25,4 mm)j of horizontal adjustment available Minimum wall opening diameter 1 -3/4' (44 45 mm). Maximum wall opening diameter 2 1/4' (57 mm). Slot STEP 1 Align slot in escutch- eon with the horizontal sur- face of deflector as shown. A be conducted to comply with the in- stallation standards. Make certain the unit has been properly tightened. If a thread leak occurs, normally the unit must be removed, new pipe joint compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal leaks, the sealing compound is washed out of the joint. G Wet pipe systems supplying dry sprinklers must be provided with ade- quate heat. Refer to appropriate in- stallation standards and the AHJ H. Remove plastic protective sprin- kler caps and bulb shields AFTER the wall finish work is completed STEP 2: Push rounded end of slot against the near edge of deflector Push far side of escutcheon past the deflector toward the sleeve. unuunuunununnuuunnun Finished Ceiling Finished Wall 4 (102 mm) minimum 6' (152 mm) maximum 3 -1/16' (77,8 mm) (12,7 mm) Sleeve diameter 13/16' 1 1/2' (38 1 mm). (20,6 mm) Sleeve finish matches finish of escutcheon. Figure 2 Adjustable Standard Quick Response Dry Horizontal Sidewall Sprinkler STEP 3. Pull escutch- eon away from the near edge of deflector Move near side of escutcheon over deflector Figure 3 Adjustable Standard Escutcheon Installation where the sprinkler is installed and there no longer is a potential for mechanical damage to the glass bulbs. To remove the bulb shields, simply pull the ends of the shields apart where they are snapped together To remove caps, turn the caps slightly and pull them off the sprinklers. SPRINKLER CAPS AND BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! I. If it is necessary to remove the entire sprinkler unit. the system must be "1 QUICK RESPONSE DRY HORIZONTAL SIDEWALL SPRINKLERS Deflector at minimum distance from wall. t" rr STEP 4. Push and ro- tate the escutcheon onto the sleeve. NOTE. To locate deflector at minimum distance from wall, with no adjustment available, order the adjustable standard dry horizontal sidewall sprink- ler 1 ,(25 4 mm) shorter than A Dimension. NOTE: To locate the deflec for at the maximum distance from the wall, with no adjust- ment available, order the adjustable stan- dard dry horizontal sidewall sprinkler 1 (25,4 min) longer than the A Dimension. Push and rotate Slot STEP 5. To minimize visibility of the slot in the escutcheon, position the slot at top of sprinkler sleeve. taken out of service. See Mainte- nance instructions and follow all warnings and instructions. 7 MAINTENANCE NOTICE The owner is responsible for maintaining the fire- protection system and devices in proper operating condi- tion. For minimum maintenance and in- spection requirements, refer to the ap- propriate NFPA standard that describes care and maintenance of sprinkler sys- tems In addition, the Authority Having Jurisdiction may have additional mainte- nance, testing, and inspection require- ments that must be followed. Sprinkler 106 d 'JIKING® A. Sprinklers must be inspected on a regular basis for signs of corrosion, mechanical damage, obstructions, paint, etc The frequency of inspec tions may vary due to corrosive atmo- spheres, water supplies, and activity around the device. B Sprinklers that have been field painted, caulked, or mechanically damaged must be replaced immedi- ately Sprinklers showing signs of corrosion shall be tested and /or re- placed immediately as required In- For A Dimension: 1 Determine the distance from face of tee to face of finished wall. 2. Round to nearest 1/4' (6,35 mm) between 3 -1/4 and 47 1/2' (82,5 mm and 1 207 mm). NOTE: The sprinkler will be recessed approxi- mately 5/16" (7,9 mm) with 5/8' (15.8 mm) horizontal adjustment available Thread Site INPT BSP Il I1 1 A Minimum ceiling hole size: 2 1/8' (54 mm) diameter Maximum ceiling hole size: 2 1/2" (63,5 mm) diameter stallation standards require sprin- C klers to be tested and, if necessary replaced after a specified term of ser vice. Refer to the installation stan- dards (e.g NFPA 25) and the AHJ for the specified period of time after which and /or replacement is required. Never attempt to repair or D reassemble a sprinkler Sprinklers that have operated cannot be reas- sembled or re -used, but must be re- placed. When replacing sprinklers, use only new sprinklers. 111111111111111E- Ceiling Wall 4 (102 mm) minimum 6" (152 mm) maximum (12,7 mm) 3 -1/16' (77,8 mm) Available Adjustment 1 -7/8" (47,6 mm) minimum 2 1/2" (63.5 mm) maximum 5/16" (7,9 mm) outward adjust/, lent 5/16" (7,9 mm) inward adjustment Figure 4 Adjustable Recessed Quick Response Dry Horizontal Sidewall Sprinkler Approval Chart Quick Response Dry Horizontal Sidewall Sprinklers Sprinkler Description Nominal K- factor Sprinkler Style Base Part No. SIN U.S. I metric Adjustable Standard I 08384 VK178 5.6 8.1 Adiustable Recessed I 08386 VK182 5.6 I 8.1 Plain Barrel I 08388 VK174 5.6 8.1 May 13 2005 QUICK RESPONSE DRY HORIZONTAL SIDEVVALL SPRINKLERS E. The sprinkler discharge pattern is criti- cal for proper fire protection. Nothing should be hung from, attached to. or otherwise obstruct the discharge pat- tern. All obstructions must be immedi- ately removed or if necessary addi- tional sprinklers must be installed. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system de- scription and/or valve instructions. Prior to removing the system from ser vice, notify all AHJs. Consideration should be given to employment of a fire patrol in the effected area. 1 Remove the system from service drain all water and relieve all pressure on the piping. 2. Using the special dry sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the replacement sprinkler is the proper model and style, with the appropriate A dimension, orifice size, and temperature rating, and response characteristics 3 Place the system back in service and secure all valves. Check for and repair all leaks. Sprinkler systems that have been sub- jected to fire must be retumed to ser vice as soon as possible. The entire system must be inspected for damage, and repaired or replaced as necessary Sprinklers that have been exposed to corrosive products of combustion or high ambient temperatures, but have not operated, should be replaced. Re- fer to the AHJ for minimum replace- ment requirements. i Temperature v Finish A1X" Escutcheon (if applicable) Order Lenath Increment Inches mm 12.7 1/4' 6.35 12.7 KEY Listinas I cULus NYC I Al Al I B2 B2 I A3 A3 I Available Approved Finishes Approved Temperature Ratings 1 Chrome- Enloy or White Polyester sprinkler with a Chrome -Enloy A 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) Sleeve and Escutcheon B 155 °F (68 °C), 175 °F (79 °C). and 200 °F (93 °C) 2 Chrome Enloy or White Polyester 3 Chrome Enlov or Brass Footnotes 1 Base part number is shown. For complete part number refer to Viking's current price schedule. 2 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. UL and C -UL Listings are limited to Light-Hazard occupancies only 3 Minimum length (A Dimension) is 1 1/2" (38,1 mm) for sprinkler 08384 3" (76.2 mm) for sprinkler 08388, and 3 -1/4" (82,5 mm) for sprinkler 08386. Maximum standard (listed) length is 45 -1/2' (1 156 mm) for sprinkler 08384 47" (1 194 mm) for sprinkler 08388, and 47 1/2" (1 207 mm) for sprinkler 08386 K- Factor applies for all lengths indicated in Footnote 3. Metric K- Factor shown is for use when pressure is measured in kPa. When pressure is measured in BAR, multiply the metric K- Factor shown by 10 0 5 Accepted for use, City of New York Department of Buildings, MEA Number 89 -92 -E, Vol. 15 6 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. Replaces page 106 a -d, dated Dec. 17 2004 (added option for white Form No F_031993 sprinkler with chrome sleeve and escutcheon for Adj Standard). May 27 2005 Sprinkler 133 a NIKIINC® 1 PRODUCT NAME Viking Sprinkler Wrenches and Sprinkler Cabinets 2. MANUFACTURER The Viking Corporation 210 N. industrial Park Road Hastings, Michigan 4908 USA Telephone: (269) 945 -9501 (877) 384-5464 Fax: (269) 945 -9599 e -mail: techsvcs @vikingcorp com 3. PRODUCT DESCRIPTIONS AND TECHNICAL INFORMATION A. SPRINKLER AND SPRAY NOZZLE WRENCHES Viking sprinkler wrenches are special in- stallation tools specifically designed for use with the various Viking sprinklers and spray nozzles. The appropriate wrenches must be used with the indi- cated sprinklers and nozzles to provide the proper leverage when tightening sprinklers or nozzles and to minimize slippage during installation. Using wrenches other than the ones designated for installation may damage the sprinkler See Table 1 and Figure 1 for wrenches that are available for in- stalling Viking sprinklers. Wrench part numbers 10896W/B** 07297W/B 05118CW/B 10285W/B, and 12143W/B provide the amount of le- verage needed to tighten sprinklers and spray nozzles into pipe fittings while pre- venting sprinkler damage. No additional tools are necessary with these wrenches. "Wrench part number 10896W/B replaces part number 05000CW /B, which is no lon- ger available. Wrench part number 05000CW /B may still be used until it needs to be replaced. Wrench part numbers 08336W/B, 10366W/B 07398W 07565W/B, 11663W/B 12144W/B 13032W/B and 13196W/B require a separate W ratchet (not available from Viking) to provide the correct amount of leverage. The internal diameters of sprinkler wrenches 08336W/B and 10366W/B are designed for use with the sprinkler contained in the protective shell. (A pro- tective shell should be retained in the spare sprinkler cabinet.) Wrench part number 10551W/B is re- quired for threading institutional es- cutcheon plates onto institutional sprin- klers. Wrench part number 10729 is a 2 1/2' C -C face spanner wrench used for removing institutional escutcheon plates from institutional sprinklers (refer to the DISASSEMBLY section of institu- tional sprinkler technical data pages). Note. Units of measure in parentheses may Form No. F 122598 TECHNICAL DATA For Sprinkler Models: Viking frame -style sprinklers 10896W/B** and spray nozzles, including Available wax coated sprinklers since 2000. Viking recessed frame -style sprinklers without protective caps, Polyester and Teflon coated frame -style sprinklers and spray nozzles, domed concealed sprinklers, and Silhouette residential concealed sprinklers Viking recessed frame -style 12144W/Bt sprinklers with Available protective caps. since 2003. Viking standard adjustable 07297W/B and plain barrel dry sprinklers, Available ECOH 14K sprinkler since 1991. 13032W/Bt Available since 2004. 13196W/Bt Available since 2005. Viking recessed and domed 07565W /Bt concealed dry sprinklers Available since 1991. Viking High Challenge' Sprin- 05118CW/B klers and upright ESFR sprin- Available klers, and ELO sprinklerstt since 1981. Viking coated recessed, 11663W/B and domed concealed Available ELO sprinklerstt since 2001. 10285W/B Available since 1999. 12143W/B Available since 2003.. 08336W/Bt (heavy duty) and flush style sprinklers Available since 1993. 10366W/Bt* Viking concealed and flush (light duty) style sprinklers Available since 1998. Viking coated and recessed ECOH 14K sprinkler Viking coated and recessed Res. HSW Sprinkler VK452 Viking pendent 14K ESFR sprinklers Viking pendent 25.2K. ESFR sprinklers Viking concealed Wrench Part Numbers 07398Wt Available since 1990 Viking institutional style flush sprinklers (for installation of the tamper resistant escutcheon plate) Viking institutional style flush sprinklers (spanner wrench for removal of the tamper- resis- tant escutcheon plate) `Ideal for sprinkler cabinets. **Wrench part number 10896W/B replaces wrench part number 05000CW/B. Although wrench part number 05000CW/B is no lon- ger available, it may still be used until wrench replacement is necessary tRequires a separate YYz ratchet (not avail- able from Viking). ttELO sprinklers manufactured before Dec. 2001 use wrench part number 07297W/B, or 07565W/B for coated and recessed. Table 1. Sprinkler Wrenches be approximations. 10551W/B Available since 1999 10729 Available since 1999 SPRINKLER WRENCHES AND CABINETS Part No. 07398W Part No. 12144W/B 1 L Part No. 08336W/B 10896 Part No. 10896W/B L h I T Part No. 13196W/B C Part No. 13032W/B VIKING O 9 Part No. 07297W/B 1 Part Nos. 07565W/B 11663W/B Part No. 05118CW/B (Oozes] O) Part No. 10285W/B VEXING 12143 Q)) Part No. 12143W/B Part No. 10366W/B m 0 0 Part No. 10551W/B Part No. 10729 Figure 1 Sprinkler-Wrenches Replaces page 133 a -b, dated August 27 2004 (added wrench 13196W/B). Sprinkler 133 b May 27 2005 'JIKING® Installation Instructions: Refer to the appropriate sprinkler or spray nozzle technical data page. Ordering Instructions 1 Determine appropriate wrench for use with the given sprinkler or spray noz zle model from Table 1 on the previ- ous page. 2. Specify the wrench part number and quantity needed. B. SPRINKLER CABINETS Viking sprinkler cabinets are metal en- closures constructed to store an emer gency supply of six or twelve spare sprinklers and a sprinkler installation wrench. NFPA 13 requires a representative number of each type and temperature rating of sprinkler head to be kept in a cabinet on the premises. NFPA 13 also requires a special sprinkler wrench to be provided in the cabinet. This allows for immediate removal and replacement of sprinklers that have operated or that have become damaged. Stock of spare sprinklers should include sprinklers of all the types and tempera- ture ratings as are installed in the sprin- kler system in the following quantities: Number of Sprinklers in System Under 300 300 -1 000 Over 1 000 Minimum Number of Spare Sprinklers Required 6 12 24 The cabinets are designed with four 3/16' diameter holes in back. Spacing of mounting holes: 3 -1/2' (88,9 mm) length, 3 -1/2' (88,9 mm) height. The sprinkler cabinet should be located adja- cent to the main system riser Finish Painted high -gloss red enamel interior and exterior chrome plated door knob. Material Cabinets: Cold Rolled Steel, 20 gauge Shelves: Cold Rolled Steel, 1.6 gauge Ordering Instructions 1 Determine appropriate cabinet from Table 2 on this page for use with the specific model of sprinklers of a given number to be contained in the cabinet. 2. Specify cabinet part number (see Ta- ble 2 above) and quantity needed. Sprinklers and sprinkler wrenches are not supplied with the cabinets; they must be ordered separately Care and Maintenance The cabinet should be easily accessi- ble. Replace's page 133 a -b dated August 27 2004 (added wrench 13196W/B). For Sprinkler Models: Viking frame style and ESFR 14K pendent sprinklers Typical Pendent Sprinkler Typical Upright Sprinkler Figure 2 Wrench —i— Typical ESFR Pendent Sprinkler Correct orientation of sprinklers and wrench inside cabinet (A 12 -head cabinet is illustrated.) Cabinet Capacity 01724A 10 -3/16' 4- 11/16' 2 -9/16' Available (259 mm) since 1971. 01725A 10 -3/16' 8 -9/16' 2 -9/16 Available (259 mm) since 1971. Viking concealed and 01731A 13- 13/16' flush style sprinklers and ESFR 5 -6 sprinklers Available (351 mm) 25.2K pendent sprinklers since 1971. High Challenge° Sprinklers, 03985A 12 5/8' upright ESFR sprinklers, and 6 sprinklers Available (321 mm) Intermediate Level Sprinklers since 1977. Table 2: Sorin The cabinet must not be exposed to corrosive atmospheres or tempera- tures above 100 °F (38 °C). The stock of spare sprinklers should include an adequate number of sprin- klers of each type and temperature rat- ing. The stock of sprinklers must be in good condition. A sprinkler wrench of the appropriate type must be included in the cabinet. Orient sprinklers and sprinkler wrench as indicated in Figure 2 below CAUTION: When replacing automatic sprinklers in an existing system, be sure to replace with sprinklers of the correct type, thread size, orifice size, temperature rating, and finish. 4 AVAILABILITY SERVICE Viking products are available through a network of domestic, Canadian, and international distributors. See the Viking Viking frame style sprinklers 6 sprinklers 12 sprinklers SPRINKLER WRENCHES AND CABINETS Cabinet Size Part Length Height Depth Number kler Cabinets (103 mm)_ (65 mm) (217 mm) (65 mm) 5-11/16' 3' (144 mm) 76 mm) 9 -1/8" 4 -1/8' (232 mm) (105 mm) Corp Web site for your closest distribu- tor or contact The Viking Corporation. Viking technical data may be found on The Viking Corporation's Web site at http. /www vikingcorp.com. The Web site may include a more recent edition of this technical data page. 5. GUARANTEES For details of warranty refer to Viking's current price schedule, or contact The Viking Corporation directly Sprinkler Cabinet: Part Number 01724A (sprinklers and wrench not included). Sprinkler Cabinet: Part Number 01725A (sprinklers and wrench not included). Figure 3 Form No. F_122598 April 2008 30a VIKING Form No F_102307 EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4' 6" (DN32 DN150) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269- 945 -9501 Technical Services 877- 384 -5464 Fax: 269 945 -4495 Email' techsvcs @vikingcorp.com 1 DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1 1/4 1 1/2" 2' 2 1/2" 3" 4 and 6' for commercial systems. They are available with an AGF TESTanDRAIN valve, and /or pressure relief valve (PRV) to meet NFPA 13 requirements for gridded systems and any system requiring a pressure relief valve. This configuration eliminates the need to drain the system before installing the relief valve, while a built in test port allows hydrostatic testing without draining the system EasyPac Commercial Assemblies are designed with all required equipment and standard components that can be replaced in the field, including pressure gauges, Potter flow switches, 3 -way gauge control valve and appropriate drain valve. All assemblies are available in grooved inlet and outlet connections 1 1/4 -6' using Schedule 10 steel pipe. The 1 1/4" to 2" assemblies are also avail- able with male NPT threaded inlets and outlets or threaded inlets x grooved outlets using Schedule 40 steel pipe NOTE. The EasyPac Commercial Riser Manifold Assembly can be installed horizontally with the flow switch on top, or vertically with flow upward. 2. LISTINGS AND APPROVALS Pressure Gauges. UL Listed, FM Approved Waterflow Alarm Switch UL Listed Category USQT cUL Listed, FM Approved Waterflow Detectors, Vane Type CSFM Listed Ball Valve: UL Listed, FM Approved AGF TestanDrain Model 1000• UL Listed Category VEHZ, FM Approved Sprinkler System Alarm Testers AGF TestanDrain Model 1011 with Pressure Relief Valve: UL Listed Category VEHZ, FM Approved Sprinkler System Alarm Testers 3. TECHNICAL DATA Specifications and Material Standards Available since 2007 Pressure Rating 250 PSI (17.2 bar) maximum water working pressure Fabricated steel pipe. Available in grooved inlet and outlet connections 1 1/4' to 6' using Schedule 10 steel pipe. 1 1/4" 1 1/2' and 2" assemblies are also available with male NPT threaded inlet and outlet, or threaded inlet x grooved outlet using Schedule 40 steel pipe. Riser bodies coated with black Ecoat. Flow Switch Two single -pole double -throw switches with Form C contacts rated at 15 Amps 125/250 V AC 2.5 Amp 0 -30 V DC Each switch can be wired for open or closed circuit operation. See Figure 1 Ordering Information (Also refer to the current Viking price list.) Three different options are available for the commercial line Basic Commercial EasvPac Assemblies with Ball Valve Drain (See Figures 2 -4.1 Includes a ball drain valve of the appropriate size for system requirements, available for 1 1/4 -6" riser assemblies. Basic Model EPCAG (grooved connections) EPCAT (threaded connections 1 1/4" to 2' assemblies only) or EPRATG (threaded x grooved connections, 1 1/4' to 2" assemblies only) Part No 14840 Model 114EPRAT 1 1/4 Threaded with ball drain valve Part No. 14841 Model 114EPRAG 1 1/4' Grooved with ball drain valve Part No 14905 Model 114EPRATG. 1 1/4' Threaded x Grooved with ball drain valve Part No 14842 Model 112EPRAT 1 1/2' Threaded with ball drain valve Part No 14843 Model.112EPRAG 1 1/2" Grooved with ball drain valve Part No. 14849 Model 112EPRATG 1 1/2" Threaded x Grooved with ball drain valve Part No. 14899 Model 2EPCATBV• 2" Threaded with ball drain valve Part No 14848 Model 2EPCAGBV 2" Grooved with ball drain valve Part No 14846 Model 2EPRATG 2' Threaded x Grooved with ball drain valve Part No 14852 Model 212EPCAG 2 1/2' Grooved with ball drain valve Part No. 14855 Model 3EPCAGBVV 3" Grooved with ball drain valve Part No 14858 Model 4" Grooved with ball drain valve Part No. 14861 Model 6EPCAGBV• 6" Grooved with ball drain valve Viking Technical Data may be found on The Viking Corporation's Web site at http: /www.vikinggroupi nc.com. The Web site may include a more recent edition of this Technical Data Page. Commercial EasvPac Assemblies with TESTanDRAIN Valve (See Figures 5 -7.1 Includes a test orifice with size specified from 3/8' (K2.8) to 25K ESFR* depending on the smallest sprinkler installed Model is EPCTDAG (grooved connections) or EPCTDAT (threaded connections, 1 1/4' -2' assemblies only) Must add suffix to the part number for the desired orifice size. A 3/8' (K2.8) B 7/16" (K4.2) C 1/2" (K5 (K8 0), ELO'= E (K11:2) K14 F K25 G on the system. 6) D 17/32' Replaces page 30a -g dated February 1 2008 (Added Part Numbers 14840 14846 14849 14905 and 14935) 30b April 4 2008 EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4" 6' (DN32 DN150) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269 -945 -9501 Technical Services 877 384 -5464 Fax: 269 945 -4495 Email techsvcs @vikingcorp.com NIKIM For example Part No 1 Part No 14871 Model Part No 14872 Model Part No 14875 Model Part No 14876 Model Part No 14935 Model Part No 14850 Model Part No 14853 Model Part No 14856 Model Part No 14859 Model Part No 14862 Model *ESFR not available with 1 1/4 1 1/2' or 2' risers. 4871C 1 1/4 Threaded EasyPac Commercial Assembly with TESTanDRAIN using a 1/2' test orifice 114EPCTDAT 1 1/4 Threaded with TESTanDRAIN 114EPCTDAG 1 1/4' Grooved with TESTanDRAIN 112EPCTDAT 1 1/2' Threaded with TESTanDRAIN 112EPCTDAG 1 1/2' Grooved with TESTanDRAIN 2EPCTDAT 2" Threaded with TESTanDRAIN 2EPCTDAG. 2' Grooved with TESTanDRAIN 212EPCTDAG 2 1/2' Grooved with TESTanDRAIN 3EPCTDAG. 3" Grooved with TESTanDRAIN 4EPCTDAG. 4' Grooved with TESTanDRAIN 6EPCTDAG 6' Grooved with TESTanDRAIN Commercial EasvPac Assemblies with TESTanDRAIN and Pressure Relief Valve (PRV) (See Fiaures 8 -10.1 Includes test orifice and pressure relief valve. The test orifice must be specified at order based on the smallest sprinkler installed on the system for 3/8" (K2.8) to K25 ESFR* The pressure relief valve is not factory assembled to the TestanDrain. The Model is EPCTDAGRV (grooved connections) or EPCTDATRV (threaded connections, 1 1/4' 2' assembliesy only) Must add suffix to the part number for the desired orifice size and pressure setting of the pressure relief valve. A 3/8" (K2.8) B 7/16" (K4.2) C 1/2" (K5.6) D 17/32' (K8 0) ELO E (K11.2) K14 F K25 G for orifice size 175 185 195 205 225 or 250 for pressure setting of the pressure relief valve For example, Part No 14873C175 1 1/4' Threaded EasyPac Commercial Assembly with TESTanDRAIN using a 1/2' test orifice and pressure relief valve with 175 PSI pressure setting: Part No. 14873 Model 114EPCTDATRV 1 1/4' Threaded with TESTanDRAIN and PRV Part No 14874 Model 114EPCTDAGRV 1 1/4' Grooved with TESTanDRAIN and PRV Part No. 14877 Model 112EPCTDATRV 1 1/2' Threaded with TESTanDRAIN and PRV Part No 14878 Model 112EPCTDAGRV 1 1/2' Grooved with TESTanDRAIN and PRV Part No 14847 Model 2EPCTDATRV 2" Threaded with TESTanDRAIN and PRV Part No. 14851 Model 2EPCTDAGRV 2' Grooved with TESTanDRAIN and PRV Part No 14854 Model 212EPCTDAGRV 2 1/2' Grooved with TESTanDRAIN and PRV Part No. 14857 Model 3EPCTDAGRV 3' Grooved with TESTanDRAIN and PRV Part No 14860 Model 4EPCTDAGRV 4' Grooved with TESTanDRAIN and PRV Part No. 14863 Model 6EPCTDAGRV 6' Grooved with TESTanDRAIN and PRV NOTE. It is important to note that the pressure rating of the relief and closing of the valve Standard relief valves are required to rating The valves are required to CLOSE at a pressure at»" *ESFR not available with 1 1/4 1 1/2' or 2' risers. 4 INSTALLATION Refer to appropriate NFPA Installation Standards. 5. TESTANDRAIN VALVE OPERATING INSTRUC- TIONS 1 To Test: Turn valve handle counterclockwise from 'Off' to "Test" The handle will stop automatically After test is completed return handle to "Off" 2. To Drain: Turn handle counterclockwise from "Off" to "Test" The handle will stop automatically Depress 'Push button and turn handle to "Drain When system is empty return handle clockwise to "Off" position. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7 AVAILABILITY The Viking EasyPac Riser Assemblies are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or confacf The Viking_CorPor•ation. 8. GUARANTEE For details of warranty refer to Viking's current list price valve indicates an operating range of pressure for both opening OPEN in a range of pressure between 90% and 105% of their RO% of that ratin0 BELL OR HORN figure 1 Flow Switch with 2 Single Pole, Double Throw Micro Switches LE t :PIPE'DIAMETERS; 1 1/4" 1 1/2" 2" 2 1/2" 3" 4" 6" 1 66" (42.2 mm) 1.9" (48.3 mm) 2.38" (60.3 mm) 2.88' (73 mm) 3.5" (88.9 mm) 4.5' (114.3 mm) I 6.63" (168.3 mm) I T ry annu ato or ntrol whe equ ed 1 45" (36.6 mm) 1.38" (35.1 mm) 1.69" (42.7 mm) 1.61 (40.9 mm) 1 2.16" (54.8 mm) 2.07" (52.5 mm) 2.64" (66.9 mm) N/A 3:26" (82:8 "mm) N/A 4.26' (108.2 mm) N/A 6.36' (161.5 mm) I N/A April 4 2008 30c N1K1M The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269 945 -9501 Technical Services 877- 384 -5464 Fax: 269 945 -4495 Email. techsvcs @vikingcorp.com 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR FLOW SWITCH 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR -S FLOW SWITCH A A 16 -1/2 (419 mm) 1 NPT DRAIN CONNECTION Figure 2: 1 1/4 and 1 1/2' (DN32 and DN38) Basic Commercial EasyPac 6 -7/16 (163 5 mm) A WATER FLOW 5- 51/64 (147.5 mm) 6- 3/32'* (154.5 mm) 6 -11/32 (161 mm) A WATER FLOW FOR 1 -1/2 ASSEMBLIES, ADD 1/8 (3.5 mm) I TO DIMENSIONS WITH AN ASTERISK FOR 2 -1/2 ASSEMBLIES, ADD 1/4 (6 35 mm) TO DIMENSIONS WITH AN ASTERISK FOR 3 ASSEMBLIES ADD 9/16 (14.3 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6 35 mm) 9- 23/64'* NOTE. DIMENSIONS ARE 1/4 (6 35 mm) (238 mm) EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4' 6' (DN32 DN150) A 15 (381 mm) 8- 9/16 (218 mm) NOTE. LENGTH OF HANDLE MAY VARY L 5/8 1 -1/4 NPT DRAIN (16 mm) CONNECTION Figure 3: 2' 2 1/2' and 3' (DN50, DN60, and DN80) Basic Commercial EasyPac 1 x 2 NIPPLE 1 x 4 NIPPLE 1 x 90 ELBOW 1 UL /FM BALL VALVE 1 -1/4 90 ELBOW (2) 1-1/4 x 2 NIPPLES UL /FM BALL VALVE NOTE. LENGTH OF HANDLE MAY VARY 30d N1IQ.NG The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269 945 -9501 Technical Services 877 384 -5464 Fax: 269- 945-4495 Email techsvcs @vikingcorp.com 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY'\ 300 PSI GAUGE 1/4 PLUG VSR FLOW SNITCH 14 -1/2" (369 mm) 1/4 x 3 NIPPLE 300 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR -S FLOW SWITCH 16 -1/2 (420 mm) 7 -1 /2 (190.5 mm) I r. WATER FLOW 1 6 -25/32 (172.5 mm) TECHNICAL DATA 6 -3/32 (154.5 mm) FOR 6' ASSEMBLIES, ADD 1 -3/64 (27 mm) TO DIMENSIONS WITH AN ASTERISK A WATER FLOW NOTE. DIMENSIONS ARE 1/4 (6.35 mm). 1 -3/4 (44 mm) 13- 5/16 (338 mm) 1 J 2 NPT DRAIN CONNECTION Figure 4 4' and 6' (DN100 and DN150) Basic Commercial EasyPac 6- 11/32'* (161 rrim) 9 -3/32 (231 mm) -10 4- 15/32 (114 mm) EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4" 6' (DN32 DN150) FOR 1 -1/2 ASSEMBLIES, ADD 1/8 (3.5 -mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6.35 mm) 1 NPT DRAIN CONNECTION 13' (330 mm) 1 x 2" NIPPLE TESTANDRAIN 5 -1/8" (381 mm) (131 mm) I i Figure 5. 1 114 and 1 112' (DN32 and DN38) Commercial EasyPac with TESTanDRAIN April 4 2008 (2) 2 x 3' NIPPLES 2" x 90 DEG ELBOW 2' UL /FM BALL VALVE NOTE. LENGTH OF HANDLE MAY VARY April 4 2008 30e NIKIM The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269 -945 -9501 Technical Services 877 384 -5464 Fax: 269 945 -4495 Email techsvcs @vikingcorp.com 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAYN 300 PSI GAUGE 1/4 PLUG VSR FLOW SWITCH 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR FLOW SWITCH 14 -1/2 (369 mm) 6 -7/16 (163 5 mm) 5 -51/64 (147 5 mm) 7 -1/2'* (190 5 mm) WATER FLOW 6- 25/32'* (172.5 mm) FOR 2 -1/2' ASSEMBLIES, ADD 1/4 (6 35 mm) TO DIMENSIONS WITH AN ASTERISK FOR 3' ASSEMBLIES, ADD 9/16 (14.3 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6.35 mm) 10 -45/64 (271.5 mm) 5 -13/64 (132.5 mm) Figure 6. 2' 2 1/2' and 3' (DN50, DN60, and DN80) Commercial EasyPac with TESTanDRAIN 8- 3/16'* (208 mm) 5 -31/64 (139 mm) FOR 6' ASSEMBLIES, ADD 1 -3/64 (27 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6.35 mm) 16 -3/8 (416 mm) 1 -1/4 NPT DRAIN CONNECTION 2 -5/8 (66 mm) N EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4' 6" (DN32 DN150) x 2 NIPPLE TESTA TESTANDRAIN 2 x 3 NIPPLE TESTAN DRAI N 13 (330 mm) L_ 8 -1/8 (206.5 mm) Figure 7 4' and 6' (DN100 and DN150) Commercial EasyPac with TESTanDRAIN 2 NPT, DRAIN_____ CONNECTION r 30f April 4 2008 The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269 945 -9501 Technical Services 877 384 -5464 Fax: 269- 945 -4495 Email techsvcs @vikingcorp.com 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR -S FLOW SWITCH 9-3/32 I I (231 mm) 5 -1/8 6- 11/32'* (131 mm) (161 mm) I� Figure 8 1 1/4 and 1 1/2' (DN32 and DN38) Commercial EasyPac with TESTanDRAIN and Pressure Relief Valve A 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR FLOW SWITCH 14 -1/2 (369 mm) 16-1/2 (420 mm) 1j WATER FLOW 6 -7/16 (1 63 5 m' 6 -3/32 (154 5 mm) 5 51/64 (147.5 mm) FOR 1-1/2 ASSEMBLIES, ADD 1/8 (3 5 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6.35 mm) 21 (113.5 mm) FOR 2 -1/2 ASSEMBLIES, ADD 1/4 (6.35 mm) TO DIMENSIONS WITH AN ASTERISK FOR 3 ASSEMBLIES ADD 9/16 (14.3 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6 35 mm) 5 -1/4 (133 5 mm j J 3 -1/4 1 -1/4 NPT DRAIN (83 mm) CONNFCTION (273 mm) 10 -45/64 EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4' 6' (DN32 DN150) 1 x 2 NIPPLE TESTANDRAIN WITH PRESSURE RELIEF VALVE 15 (381 mm) *NOTE. PRESSURE REUEF VALVE KR IS SHIPPED LOOSE. IT IS NOT FACTORY INSTALLED. A 1 -1 /4 x 2 NIPPLE TESTANDRAIN WITH PRESSURE RELIEF VALVE 13 (330 mm) 1 NPT DRAIN CONNECTION "NOTE PRESSURE REUEF VALVE KIT IS SHIPPED LOOSE. R IS NOT FACTORY INSTALLED. Figure 9' 2' 2 1/2' and 3' (DN50, DN60, and DN80) Commercial EasyPac with TESTanDRAIN and Pressure Relief Valve April 4 2008 30g EASYPAC COMMERCIAL RISER MANIFOLD ASSEMBLIES 1 1/4" 6' (DN32 DN150) The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058 Telephone 269- 945 -9501 Technical Services 877 384 -5464 Fax: 269 945 -4495 Email techsvcs @vikingcorp.com 'J 1/4 x 3 NIPPLE 1/4 GAUGE VALVE 3 WAY 300 PSI GAUGE 1/4 PLUG VSR FLOW SWITCH 14 -1/2" (369 mm) 7 -1/2 (190.5 mm) 4 WATER FLOW 6 -25/32 (172.5 mm) FOR 6 ASSEMBLIES, ADD 1 -3/64 (27 mm) TO DIMENSIONS WITH AN ASTERISK NOTE. DIMENSIONS ARE 1/4 (6.35 mm) 16 -5/16" (414 mm) I 8 -3/16' (208 mm) 1 -5/8" (41.5 mm) 2 -5/8" (66 mm) TEST.x DRAIN I 2' NPT DRAIN CONNECTION 13 (330 mm) 2" x 3' NIPPLE TESTANDRAIN WITH PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE KIT IS SHIPPED LOOSE. R tla FACTORY Figure 10 4 and 6' (DN100 and DN150 Commercial EasyPac with TESTanDRAIN and Pressure Relief Valve THIS PAGE INTENTIONALLY LEFT BLANK Form No F_102307 Replaces page 30a -g dated February 1 2008 (Added Part Numbers 14840 14846 14849 14905 and 14935) WIL$ INS a ZURN: >cort3pany ouble Check rDetectorAssem (with OS &Y gates) FEATURES Sizes: 2 1/2' 3' 4 0 6' 8' 010' Maximum working water pressure Maximum working water temperature Hydrostatic test pressure End connections (Grooved for steel pipe) (Flanged) OPTIONS (Suffixes can be combined) SPEC (with BGVIC valves) 175 PSI 140 °F 350 PSI AWWA C606 ANSI B16 1 Class 125 with flanged end OS Y gate valves (standard) L less shut -off valves (grooved body connections) LM less water meter with remote reading meter with gpm meter (standard) with cu ft/min meter G with grooved end OS &Ygate valves FG with flanged inlet gate connection and grooved outlet gate connection PI with Post Indicator Gate Valves (4 10 ❑BGVIC with grooved end butterfly valves ACCESSORIES Repair kit (rubber only) Thermal expansion tank (Model WXTP) OS Y Gate valve tamper switch (OSY -40) Test Cock Lock (Model TCL24) DIMENSIONS WEIGHTS (do not include pkg.) 1 WEIGHT MODEL WITH 350ADA WITHOUT WITH OS &Y WITH OS&Y BUTTERFLY SIZE GATES GATES (GXF) GATES (GXG) VALVES (GXG) in. I mm lbs. I kg lbs. kg lbs. kg lbs. I kg 2 1/2 65 1 105 47.5 207 94 1 199 90.3 123.8 56.2 3 80 1 104 47 224 101.51 214 97 124.41 56.5 4 1 100 91 41.3 245 111 1 219 99.4 123 I 55.8 6 1 150 141 64 377 171 1 347 158 193 I 87.6 8 1 200 1 302 137 778 353.2 754 342.3 410 1 186 10 1 250 1 355 161 1040 472.71 918 416.5 527 1 239.3 Model 350 ADA SIZE A WITH A BUTTERFLY VALVES In I mm in I mm 2 1/2 1 65 351/8 892 3 1.80 36 1/8 918 4 1100 38 965 1 33 1/8 6 1 150 47 1194 1 39 7/8 8 1 200 615/8 1565 5412 10 1 250 64 5/8 1642- 58 12 (Patent. No.. 5;9131331):; Page 1 of 2 B LESS GATE VALVES in 1 mm in I mm 321/8 816 1201/81511 32 5/8 829 1 20 1/8 1 511 842 1 19 7/8 1 505 1013 1 25 7/8 1 657 1384 1 38 12 1 978 1485 138 1/2 1 978 In I mm 4 12 1 114 4 12 1 114 41/21114 512 1 140 10 1 254 10 1 254 !CATION DIMENSION (approximate) C D in I mm 9 229 9 229 9 1 229 10121267 12 12 1 305 I 305 APPLICATION Designed for installation on potable water lines connections in fire sprinkler systems to protect against both backsiphonage and backpressure of polluted water into the potable water supply Model 350ADA shall provide protection where a potential health hazard does not exist. Incorporates metered by -pass to detect leaks and unauthorized water use. STANDARDS COMPLIANCE (HORIZONTAL VERTICAL) ASSE® Listed 1048 AWWA Compliant C510 (with gates only) CSA® Certified (4 -8 UL® Classified C -UL® Classified (excluding BGVIC) FM® Approved Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California (excluding 10' BGVIC) NYC M EA 221 -04M -2 (2 1/2'-8") MATERIALS Main valve body Access covers Coatings Internals Fasteners springs Elastomers Polymers MODEL 350ADA with OS &Y option MODEL 350ADA with BGVIC option E E E WITH OS &Y OPEN OS &Y BUTTERFLY CLOSED VALVES in I mm in I mm in 1 mm 16 3/8 416 1 13 7/8 1 352 1 8 203 1 18 7/8 479 1 15 5/8 1 397 1 8 2031 22 3/4 578 1 18 1/4 1 464 1 9 1/8 232 1 30 1/8 765 1 23 3/4 1 603 1 10 1/8 257 1 37 3/4 959 1 29 1/4 1 743 1 11 15/16 453/4 1162 1 35 3/8 1 899 1 13 5/16 F MITTiL SHEET Ductile Iron ASTM A 536 Grade 4 Ductile Iron ASTM A 536 Grade 4 FDA Approved electrostatic epoxy finish Stainless steel, 300 Series NORYLTM NSF Listed Stainless Steel, 300 Series EPDM (FDA approved) Buna Nitrile (FDA approved) NORYLTm NSF Listed In I mm in I 6 1152171/41 6 1152171/41 6 1 152 1 8 1 7 1 178 1 10 1 G 203 1 254 1 303 18 1 /2 216 1 11 1 279 338 1 81/2 216 1 12 1 305 G I c o mm Attention Model 350ADA 184 I (grooved body) and Model 1 350DA (flange body) have 184 1 different lay lengths. DOCUMENT.# REVISION::* BF350ADAs 3/0$ 0.0 0.0 Page 2 of 2 L I) MODEL 350ADA 2 1/2' 3' 4' (STANDARD METRIC) FLOW RATES (I /s) 12.6 25.2 0 200 MODEL 350ADA 6' 8' 10' (STANDARD METRIC) FLOW RATES (VS) 63.1 126.2 o (150mm) (200mm) I 0 1000 2000 FLOW RATES (GPM) TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a mini- mum of 12' (305mm) and a maximum of 30" (762mm) above adequate drains with sufficient side clearence for testing and maintenance. The installation shall be made so that no part of the unit can be submerged. L1 FLOW CHARACTERISTICS (80mm/ 0 400 600 800 FLOW RATES (GPM) 10" (250mm, (100mm) Q Rated Flow (Established by approval agencies) Pipe size 2 1/2' 3' 4 6" 8" 10" 12" 37.9 189.3 3000 Capacity thru Schedule 40 Pipe (GPM) 15 ft/sec 7.5 ft/sec I 75 I 115 I I 198 I 450 I 780 I 1229 I 1763 112 173 298 675 1169 1843 2644 PROTECTIVE ENCLOSURE 12" MIN. _.,A,� ��AA4��30"" MAX. DIRECTION OF FLOW 10ft/sec 115 ft/sec 149 I 224 230 I 346 397 I 595 900 I 1351 1559 I 2339 2458 I 3687 3525 I 5288 r MODEL 350ADABGVIC (VERTICAL INSTALLATION) SPECIFICATIONS The Double Check Detector Backflow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be NorylTm (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM The first and second check valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector Backflow Prevention Assembly shall be a WILKINS Model 350ADA. WILKINS a Zu'rn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805 /238 -7100 Fax:805/238 -57 66 IN CANADA. ZURN INDUSTRIES LIMITED, 3544 Nashua Dr Mississauga, Ontario L4V 1L2 Phone:905 /405 -8272 Fax:905/405 -1292 Product Support Help Line. 1- 877 BACKFLOW (1- 877 222 -5356) Website: http /www.zurn.com MODEL 350ADA (OUTDOOR INSTALLATION) 50.5 104 N 0 w 35 w 69 69 a 252.4 104 0 0 w 35 c0 CD w 0 a 4000 September 5 2008 NIKING® The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone 269 945 -9501 Technical Services: 877 384 5464 Fax: 269 945 4495 Email techsvcs @vikingcorp.com 1 DESCRIPTION The Viking Swing Check Valve is a general purpose rubber -faced check valve ap- proved for use in fire protection systems. The Swing Check Valve is manufactured with a ductile iron body brass seat, and a rubber -faced clapper assembly hinged to a removable access cover for easy inspec tion and maintenance. The valve may be installed vertically or horizontally with access cover facing up For availability of flanged flanged and grooved grooved options, refer to Table 1 Tapped openings (with plugs) and gauge connections are provided on both the inlet and outlet chambers of the valve FEATURES A. Ductile iron body for less weight and extra strength. B Rated to 250 psi (17.2 bar) water working pressure. C Rubber -faced clapper hinged to access cover for quick removal and easy servicing. All moving parts can be serviced without removing the valve from the installed position. D With the cover /clapper assembly removed, the clapper rubber replacement requires removal of only one screw E. Can be installed vertically or horizontally with access cover facing up 2. LISTINGS AND APPROVALS UL Listed Guide No HMER FM Approved Single Check Valves NYC Department of Buildings MEA 89 -92 -E, Vol. XI 3 TECHNICAL DATA Viking Technical Data may be found on The Viking Corporation's Web site at Specifications: http. /www.vikinggroupinc.com Rated to 250 psi (17.2 bar) water working pressure. The Web site may include a more recent Factory tested hydrostatically to 500 psi (34 5 bar) edition of this Technical Data Page Standard Flanged Connections. ANSI B16 42 Class 150 (mates with ANSI Class 125 and Class 150 flanges). Standard Grooved Connections. ANSI /AWVVA C606 Tapped Bosses: 2 1/2 "(DN65) 3' (DN80) and 4 "(DN100): Two 1/2' (15 mm) NPT 6" (DN150) and 8" (DN200) Two 3/4' (20 mm) NPT Material Standards: Refer to Figure 1 Ordering Information Refer to Table 1 for part numbers and shipping weight Size Valve Nominal Inlet Type 2 -1/2" (DN65) 3' (DN80) 4' (DN100) 4' (DN100) 6' (DN150) 6" (DN150) 8" (DN200) 8" (DN200) Form No. F_102688 Groove Goove Flange Groove Flange Groove Flange Groove Groove Groove Flange Groove Flange Groove Flange Groove Table 1 Outlet Type Friction Loss" Shipping Weight 6 ft.(1,8 m) 10 ft. (3,1 m) 13 ft. (4,0 m) 13 ft. (4,0 m) 20 ft. (6,0 m) 20 ft. (6,0 m) 23 ft (7,0 m) 23 ft. (7,0 m) 16 lbs. (7 kg) 20 lbs. (9 kg) 47 lbs. (21 kg) 27 lbs. (12 kg) 75 lbs. (34 kg) 51 lbs. (23 kg) 135 lbs. (61 kg) 106 lbs. (48 kg) Part No. 05497C 08536 08538 08539 08542 08543 08546 08547 I "Expressed in equivalent length of Schedule 40 pipe based on Hazen Williams formula: C 120. Check Valve 803a SWING CHECK VALVE MODEL D -1 G -1 Systems with water working pressures above 175 psi (12 bar) may require extra -heavy pat- tern fittings. Viking Swing Check Valve flanges are Ductile Iron ANSI B1642, Class 150, with a maximum water working pressure of 250 psi (17.2 bar). ANSI B16.42, Class 150 flanges are NOT compatible with ANSI Class 250 or Class 300 flanges. To mate the Viking Swing Check Valve with ANSI Class 250 or Class 300 flanges, use the grooved inlet/grooved- outlet style installed with listed grooved/ flanged adapters of the appropriate pressure rating. For piping with grooved connec tions, the grooved inlet/grooved- outlet style Swing Check Valve may be installed with listed grooved couplings of the appropriate pressure rating. Replaces page 803a -d dated April 4, 2008. (Corrected dimension A for the 3" and 6' valves in Figure 1 Check Valve 803b September 5, 2008 NIKING® SWING CHECK VALVE MODEL D -1 G -1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone 269 945 -9501 Technical Services: 877 -384 -5464 Fax: 269- 945 -4495 Email: techsvcs@vikingcorp.com 4 INSTALLATION The Swing Check Valve must be installed in an area not subject to physical damage. When corrosive atmospheres and /or contami- nated water supplies are present, it is the owner's responsibility to verify compatibility with the Swing Check Valve and associated equipment. Prior to installing the valve thoroughly flush the water supply piping to verify that no foreign matter is present. The Swing Check Valve may be installed in the vertical position with direction of flow up or in the horizontal position with the ac cess cover up Systems with water working pressures above 1.75 psi (12 bar) may require extra -heavy pattern fittings. Viking Swing Check Valve flanges are Ductile Iron ANSI B16 42, Class 150 with a maximum water working pressure of 250 psi (17.2 bar) ANSI B16 42, Class 150 flanges are not compatible with ANSI Class 250 or Class 300 flanges. To mate the Viking Swing Check Valve with ANSI Class 250 or Class 300 flanges, use the grooved inlet/grooved- outlet style installed with listed grooved /flanged adapters of the appropriate pressure rating. For piping with grooved connections, the grooved -inlet /grooved outlet style Swing Check Valve may be installed with listed grooved couplings of the appropriate pressure rating. 5. OPERATION (Refer to Figure 1) Flow through the Viking Swing Check Valve lifts the rubber gasketed clapper (8, and 9) off the seat (12) to enter the sprinkler pip- ing. When flow through the valve stops, the clapper (8) closes quickly. The rubber gasket (9) forms a tight seal against the brass water seat (12) trapping pressure above the clapper and preventing reverse flow from sprinkler piping Hydrostatic Test: The Swing Check Valve is manufactured and listed for use at a maximum water working pressure of 250 psi (17.2 bar). The valve is factory tested at 500 psi (34 5 bar) Check Valves may be hydrostatically tested (in accordance with NFPA 13) at 300 psi (20 7 bar) and /or 50 psi (3.4 bar) above the normal water working pressure for limited periods of time (two hours) for the purpose of ac ceptance by the Authority Having Jurisdiction. If air testing is required, do not exceed 40 psi (2.8 bar) air pressure. 6. INSPECTIONS, TESTS AND MAINTENANCE NOTICE The owner is responsible for maintaining the fire- protection system and devices in proper operating condition. The Viking Swing Check Valve must be kept free of foreign matter freezing conditions (when used on wet systems) corrosive atmospheres, contaminated water supplies, and any condition that could impair its operation or damage the device It is that the system be inspected and tested on a regular basis. The frequency of the inspections may vary due to contaminated water supplies, corrosive water supplies and corrosive atmospheres. For minimum maintenance and inspection requirements, refer to NFPA 25 In addition, the Authority Having Jurisdiction may have additional maintenance testing, and in- spection requirements that must be followed. WARNING Any system maintenance which involves placing a control valve or detection system out of sery ice may eliminate the fire- protection capabilities of that system. Prior to proceeding, notify all the Authority Having Jurisdiction. Consideration should be given to employment of a fire patrol in the affected areas. 6 -A. Five -Year Internal Inspection Internal inspection of Swing Check Valves is recommended every five years unless inspections and tests indicate more fre- quent inspections are required. (Refer to Figure 1) 1 Notify the Authority Having Jurisdiction, remote station alarm monitors, and those in the area affected that the system will be taken out of service. Consideration should be given to employment of a fire patrol in the affected areas. 2. Close the water supply main control valve placing the system out of service. 3. Open the main drain. If necessary open the system test valve to vent and completely drain the system. 4 Use the appropriate wrench to loosen and remove the cover screws (14), and remove the cover /clapper assembly (2 11). 5. Inspect the water seat (12). Wipe away all contaminants, dirt, and mineral deposits. DO NOT use solvents or abrasives. 6. Inspect the cover /clapper assembly (2 11) and the cover gasket (13) Test the hinged clapper (8) for freedom of move- ment. Renew or replace damaged or worn parts as required. CAUTION Never apply any lubricant to seats, gaskets, or any internal operating parts of the valve. Petroleum- based grease or oil will damage rubber components and may prevent proper operation. September 5 2008 Check Valve 803c VIKING$ Table 2 Torque Values for Viking Swing Check Valve Cover Screws Valve Size Screw Size Torque Values 2 1/2' (DN65) 3/8' 16 HHC 19 ft-lbs 2,63 kg -m 3' (DN80) 3/8' 16 HHC 19 ft-lbs 2,63 kg -m 4 (DN100) 3/8' 16 HHC 19 ft-lbs 2,63 kg -m 6' (DN150) 1/2' 13 HHC 45 ft-lbs 6,23 kg -m 8' (DN200) 5/8' 11 HHC I 93 ft-lbs 12,9 kg -m SWING CHECK VALVE MODEL D -1 G -1 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269 945 -9501 Technical Services. 877- 384 -5464 Fax: 269- 945 -4495 Email techsvcs @vikingcorp.com 7 When Internal inspection of the Check Valve is complete perform step 6 of paragraph 11 VALVE MAINTENANCE to re- install the cover /clapper assembly (2 11). 6 B. Valve Maintenance (Refer to Figure 1) 1 Perform steps 1 through 5 of paragraph 6.A FIVE YEAR INTERNAL INSPECTION 2. To remove clapper rubber (9) a. Use the appropriate wrenches to loosen and remove the button -head socket screw (11) hex nut (6), sealing washer (7) and rubber retainer (10) b Remove the clapper rubber (9) for inspection. If the clapper rubber shows signs of wear such as cracking, cuts or excessively deep grooves where the rubber contacts the water seat, replace the rubber 3. To re- install clapper rubber (9): a. Place the clapper rubber (9) over the center hub of the rubber retainer (10). b Position the retainer (10) (with rubber in place) against the clapper (8) as shown in Figure 1 c. Replace and tighten the button -head socket screw (11) sealing washer (7), and hex nut (6) The sealing washer (7) and hex nut (6) must be located on the top side of the clapper as shown in Figure 1 Do not over tighten. 4 To remove clapper (8) and /or hinge pin (4): a. Remove the hinge pin retaining rings (5) to free the hinge pin (4) for removal. After the hinge pin (4) is removed, the clapper (8) can be removed. 5 To re- install clapper (8), and /or hinge pin (4): a. Verify that the clapper rubber (9) is in good condition and that it is properly installed. b Position the clapper (8) with the elongated hinge holes aligned between the holes of the hinge bracket welded inside the cover (2) The system (top) side of the clapper (8) must face the direction indicated by the flow arrow stamped_ inside the cover (2) c. Insert the hinge pin (4) through the holes at one end of the hinge assembly Continue to push the hinge pin (4) through the holes at the remaining end of the hinge assembly d. Re- install the hinge pin retaining rings (5). 6. To re- install cover /clapper assembly (2 11) a. Verify that cover gasket (13) is in position and in good condition. b Slide the cover /clapper assembly (2 11) into the Swing Check Valve so that the clapper rubber (9) contacts the water seat (12) c. Replace the cover screws (14). Use the appropriate wrench to cross-tighten all screws to the torque value shown in Table 2 for the valve used. DO NOT over tighten. 7 AVAILABILITY The Viking Swing Check Valve is available through a network of domestic and international distributors. See the Viking Corp Web site for closest distributor or contact The Viking Corporation. 8. GUARANTEES For details of warranty refer to Viking's current list price schedule or contact The Viking Corporation directly Check Valve 803d NIKING® The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269 945 -9501 Technical Services. 877 384 -5464 Fax: 269- 945 -4495 Email techsvcs @vikingcorp.com ITEM NO. 2 8 9 10 11 Proper Sealing Washe lo otion II alv FLOW Alb tou Nom O 0 to 12 06595A PART NUMBER I D -1 3 -1 I G -1 I G -1 G -1 2 -1/2" 4' 6' (DN65) 3" (DN801 (DN100) (DN150) 8' (DN200)I Cover Assembly, 250 PSI WWP 3 1 07576 I 07576 I 07576 I 07576 None I Bushing 4 I 05355A 05355A1 04900A 104991A 05334A I Clappe Hinge Pi 5 05445A 1 05445A I 05445A I 05445A 05369A I Hinge Pi Reta ing Ring 6 01755A I:.. .7,1.V.:2121111 ;'I Clapper Hex Jam Nut #10-24 UNC I 08159 I 08159 I 71 C lapper Hex Jam Nut 3/8 -24 UNF :Ic.4',. Pcla ,A1 08144 08144 I Clapper He Jam Nut 'A" 20 UNC 7 I 06595A I 08158 I 08158 I 08143 08143 I Sealing Washe I I I I I I I 1 10194 1 10194 1 Form No. F_102688 F 3, 6-11 054998 I 08518 I 08519 I 08520 I 06521 I ClapperAssembly 6, 7 9 -11,13 06343A 08522 08523 08524 08525 Replacement Rubber IGt 5 1 E 6 p A Body Cover Assembly, 175 PSI WWP 1 3/4" (20 mm) NPT Pipe Plug SIZE I A I B C D I E IF I Gs* 2-1/2' (65mm) 3" (80mm) 4 (100mm) DESCRIPTION 12 I I Seat 13 053546 105354B 1 046496 1 049926 105339C I Cover Gasket 01517A 1 01517A 1 01517A -i°'( H.H.C. Screw 3/8" 16 UNC 3/4" (19,1 mm) lg. 14 n tw `.l w ISM. u.:l 04993A H .H.C. Screw '''A" 13 UNC x 7/8' (22,2 mm I s. t 01922A 11 H.H.C. Screw 5/8' 11 UNC x 1 -1/4° (31,8 mm) lg. 1 1) ^1 M1 1/2 (15 mm) NPT Pipe Plug 15 1_ Indicate replacement part is not available Indicates replacement part only available in a Sub Assembly listed below. Sub Assemblies 9" (228,6) 10 -3/16 (259) 10 -5/8" 6" 13 -3/8" (150mm) (340) Clapper Clappe Rubber Clapper Rubbe Retai H .H.C. Screw #10-24 UNC x 1/2" (12,7 mm) lg. 4 W.; Screw. Button Head, Socket, 3/8" 24 UHF 1/2" (12,7 mm 10308 Screw, Button Head, Socket, 1/2" 20 UNF 3/4' (19,1 mm) lg. 10686 Screw, Button Head, Socket, 1/2" 20 UNF x 7/8" (22,2 mm) Ig. 4 -1 /2" 2 -5/8' 2" 2" (114,3) (66,7) (50,8) (50,8) 4 -3/4 2 -3/4 I 2" 2" (120,7) (69,9) (50,8) (50,8) 5 -3/16 3 -3/8" 2 -1/8' 2 -1/4 (131,8) (85,7) (54,0) (57,2) 6 -3/4" 4 -3/8" 2 -1/4" 2 -1/4" (171,5) (111 1) (57,2) (57,2) Figure 1 Ductile Iron, ASTM A536 (65-45 -12) E- Coated I-ISLA Steel, A715 and Stainless Steel, UNS-S30400 E- Coated HSLA Steel, A715 and Stainless Steel, UNS- S30400 Lubncomp 189 Ryton Stainles Steel, UNS-S30400 Stainle Steel, UNS- S15700 Stainless Steel, UNS- S30200 Stainless Steel, UNS- S30400 Stainle Steel, UNS- S30400 EPDM and Stainless Steel Tel Coated HR Steel UNS 010180 EPDM Stainle Steel, UNS- S30400 Stainles Steel, UNS-S30400 Stainless Steel, UNS-S30400 Stainless Steel. UNS- S30400 Stainless Steel, UNS-S30400 Brass, UNS- C84400 SBR Rubber Steel, Zinc Plated Steel, Zinc Plated Steel, Zinc Plated Steel Steel MATERIAL 2 -1,2' 1 2 1 2 1 0 0 1 1 1 1 1 0 0 0 1 1 4 0 0 2 0 September 5 2008 SWING CHECK VALVE MODEL D -1 G -1 Fig -Flg Not Available Flg -Fig Not Available 9" 15/16" (228,6) (23,81) 11" (279,4) 1 (25,4) 8" 17" 8 -3/4' 5 -3/8" 2 -1/2" 2-7/8'113-1/2" (200mm) (431,8) (222,3) 136,5) (63,5) (73,0) 1(342,9) Dimensions shown in parentheses are millimeters. 4" 6' and 8" valves are manufactured with sculptured flanges. Dimension indicates thickness of flange at bolt holes, 2 1I 21 O 1 1I O I 1I 1 11 1 1 O 1 o I 1I 4I O 1 O I 21 O 1 1 -1/8" (28,58) NO. REQ'D I 4' I 6. 1 8 I 1 1 i 1 I 1 I 1 I 2 1 2 0 1 0 1 1 1 0 1 0 0 1 1 6 0 0 2 0 2 0 1 1 2 2 O 0 O 0 1 1 1 1 1 1 O 0 O 0 1 1 O 1 1 1 O 0 6 0 O 6 O 0 2 2 Replaces page 803a -d dated April 4, 2008. (Corrected dimension A for the 3' and 6' valves in Figure 1 POTTER The Symbol of Protection 6' BELL SHOWN These vibrating type bells are designed for use as fire burglar or general signaling devices. They have low power con- sumption and high decibel ratings. The unit mounts on a standard 4 (101 mm) square electrical box for indoor use or on a model BBK 1 weatherproof backbox for outdoor applications. Weatherproof backbox model BBK 1 Stock No 1500001 ALL DC BELLS ARE POLARIZED AND HAVE BUILT -IN TRANSIENT PROTECTION SCE TYPICAL dB MINIMUM dB CURRENT INCHES VOLTAGE MODEL NO. STOCK NO. (MAX.) AT 10 FT. AT 10 FT. (mm) 6 (150) 8 (200) 10 (250)' 6 (150) 8 (200) 10 (250) 6 (150) 8 (200) 10 (250) 6 (150) 8 (200) 10 (250) 12VDC PBD126 1706012 12VDC PBD128 1708012 12VDC PBD1210 1710012 24VDC PBD246 1706024 24VDC P80248 1708024 24VDC PBD2410 1710024 24VAC PBA246 1806024 24VAC P8A248 1808024 24VAC PBA2410 1810024 120VAC PBAl206 1806120 120VAC PBAl208 1808120 120VAC PBAl2010 1810120 BEN= m.��������.�„�.�.����1 1111 .111111111;111111L-1 111.11.1.1 PRINTED IN USA MKT #8850001 REV MFG. #5400776 12/01 UL Listed, FM Approved Sizes Available: 6' (150mm), 8' (200mm) and 10' (250mm) Voltages Available 24VAC 120VAC 12VDC (10.2 to 15 6) Polarized 24VDC (20 4 to 31.2) Polarized Service Use Fire Alarm General Signaling BurglarAlarm Environment: Indoor or outdoor use (See Note 1) -40° to 150 °F -40° to 66 °C) (Outdoor use requires weatherproof backbox.) Termination 4 No 18 AWG stranded wires Finish Red powder coating Optional: Model BBK 1 weatherproof backbox 12A 85 12A 90 12A 92 .06A 87 .06A 91 .06A 94 17A 91 17A 94 17A 94 .05A 92 .05A 99 .05A 99 76 76 76 76 79 79 76 76 76 82 82 85 BELLS PBA -AC PBD -DC Notes: 1 Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464 UL temperature range is 30 to 150 °F 34 to 66 °C) 2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation. Potter Electric Signal Company 2081 Craig Road, St. Louis, MO 63146 -4161 Phone. 800 325 3936 /Canada 888 -882 1833 www.pottersignal.com PAGE 1 OF 2 FIG 1 y 2 11/16 (68) FIG. 3 FROM CONTROL PANEL OR PRECEDING BELL POTTER The Symbol of Protection BELLS D C BELLS (OBSERVE POLARITY) RED (IN) RED (OUT) BLACK (IN) DWG, #776 CAUTION- .(AIR WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN. NOTES: 1 OBSERVE POLARITY TO RING D,C. BELLS. 2. RED WIRES POSITIVE 3. BLACK WIRES NEGATIVE DIMENSIONS INCHES (mm) WIRING (REAR VIEW) TO NEXT BELL FROM CONTROL PANEL OR END -OF -LINE OR RESISTOR PRECEDING BELL DWG. #776 -3 5 3/4 (146) NOTES: ._PRINTED IN USA 'MKT #8850001 REV-Q MFG. #5400776 12/01 FIG. 2 WEATHERPROOF BACKBOX BOX HAS ONE THREADED 112' CONDUIT ENTRANCE —0-II 5/8 (41) DWG. {776 -2 A,C BELLS BELLS PBA -AC PBD -DC WHITE (IN) WHITE (OUT) BLACK (OUT) BLACK (IN) BLACK (OUT) 3 3/B' 5 (86) (127) 1 WHEN USING A_C. BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL 2. END -OF -LINE RESISTOR IS NOT REQUIRED ON A.C. BELLS. i INSTALLATION 1 The bell should be mounted a minimum of 8 ft. (2,4m) from the floor or as close to the ceiling as possible. 2. Remove the gong. 3. Connect wiring (see Fig 3) 4 Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down) 5 Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong) 6 Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as designated by the authority having jurisdiction) PAGE 2-OF 2 Schedule4O®/Schedule-40& Fully Listed and FM Approved Sprinkler Pipe When you specify Schedule 10 /Schedule -40 sprinkler pipe you get a UL listed and FM approved product. Although these products do not require separate approvals, Schedule l0 /Schedule -40 gives you the extra quality assurance you demand.. Our Sch -10 (1 8 pipe and Sch-40 (1"- 2 pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality Galvanized Pipe Schedule 10 /Schedule -40 product can be 'hot -dip' galvanized to meet FM requirements for dry systems m accordance with the zinc coating specifications ofASTM A 123 Superior Coating Our advanced formula mill coating of- fers a clean, durable surface. It is also paint -ready for custom color applications without special preparation. The internal surface of all black Allied Tube Conduit Fire Sprinkler pipe products up to 4.5000' in diameter is coated with our new Antibacterial For mula, ABF' In scientific laboratory test, ABS proved to have superior resis- tance to microbial colonization of pipe walls, thereby delaying or possibly pre venting the onset of Microbiolob cally Influenced corrosion (MIC) when the First Sprinkler System is first installed. American Made Meets 'Buy American' requirement and is available through distributors in the USA, Canada and Mexico. Specifications Approvals Schedule 10 /Schedule -40 pipe are in compliance with the following: ASTM A 135 and NFPA 13 Both pipe products have a working pressure rating of 300 psi maximum and also meet the stringent requirement for the following tests: Welded Outlets Hydrostatic Pressure Side Wall Rupture Vibration Test tgca /Flow Control o ied TUBE CONDUIT Sch.4o Specifications NPS Nominal I.D. Wt. Wt. (H20'Filled) Pcs/ Wt/Lift (21') Wt/Lilt (24') Wt/Lift (25') In; mm In; mm Lbs/Ft, Kg /m Lbs/Ft; Kg /m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1 1.049 1.680 2.05 70 2,470 2,822 2,940 25 26.6 2.5 3.05 70 1120 1,280 1,334 11/4° 1.380 2.270 2.93 51 2,431 2,778 2,894 32 35.1 4.36 4.36 51 1103 1,260 1,313 11" 1.610 2.720 3.61 44 2,513 2,872 2.992 40 40.9 4.0 5.37 44 1140 1,303 1,357 2' 2.067 3.650 513 30 2,300 2,628 2,738 50 52.5 5.4 7.63 30 1,043 1 192 1,242 2W 2.469 5.790 7.86 19 2,310 2,640 2,750 65 62.7 8.6 1173 19 1,048 1 197 1,247 Sch -1O Specifications NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcs/ Wt/Lift (21') Wt/Lift (24') Wt/Lift (25') In; mm In; mm Lbs /Ft; Kg /m Lbs /Ft, Kg /m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1 1.097 1 400 1.81 91 2,675 3,053 3,185 25 27.9 2.1 2.70 91 1,213 1,385 1445 11/4° 1 442 1.810 2.52 61 2,319 2,664 2,760 32 36.6 2.7 3.75 61 1,052 1,208 1,252 1W 1 682 2.080 3.04 61 2,664 3,045 3,172 40 42.7 3.1 4.52 61 1,208 1,381 1 439 2' 2.157 2.640 4.22 37 2,051 2,344 2,442 50 54.8 3.9 6.28 37 930 1,063 1108 2' /i 2.635 3.530 5.89 30 2,224 2,542 2,648 65 66.9 5.3 8.77 30 1,009 1153 1,201 3' 3.260 4.330 7.94 19 1 728 1,975 2,057 80 82.8 6.4 11.82 19 784 896 933 4' 4.260 5 610 11 78 19 2.238 2,558 2,665 90 108.2 8.3 17.53 19 1,015 1160 1,209 5' 5.295 7.77 17.33 10 1 632 1,865 1,943 125 134.5 11.56 25.80 10 740 846 881 6' 6.357 9.290 23 03 10 1,951 2,230 2,322 150 161.5 13.8 34.27 10 885 1,012 1,053 8' 8.249 16 490 40.15 7 2,424 2,770 2,885 200 209.5 24.5 59.75 7 1100 1;256" 1,309 Listed 16100 S Lathrop Harvey IL 60426 11350 Noreom Rd. Philadelphia, PA 19154 2525 N 27 th Ave. Phoenix, AZ 85009 Approved Listed Customer Service (800) 882 5543 Fax 708 -339 -1806 S5 3 4 Dyna -Flow High Strength Steel Pipe The original high strength lightwall sprinkler pipe with hydraulics superior to Schedule -10 Dyna -Flow pipe is the ongmal' high strength lightwall spnnlder pipe. Dyna Flow has outstanding hydraulic capabilities and is recognized as the most popular alternative to Schedule 10 pipe. Lightweight, easy to cut and easy to handle for installation. Dyna -Flow is a valuable addition to any fire protection system. Superior Hydraulics With an inside diameter of up to 11% larger than Schedule -40 and up to 7% larger than Schedule 10 Dyna -Flow pipe hydraulics are exceptional. Larger I.D.s enable Dyna -Flow and related components, to be down -sized within the system, thus increasing the potential for job cost savings. For complete Hazen Williams charts, refer to 'Dyna Flow Hydrauhc Data Tables. Coatings Fabrication Dyna -Flow products are coated with an environmentally approved and specially formulated modified acrylic or water -based coating. This durable coating is pamtable. The black coating acts as an excellent primer and is resistant to weathering and U V degradation from outdoor storage. Metallurgical properties provide excellent fabrication characteristics for end prep finishes, welding and roll grooving. There is no special process or equipment needed for fabrication and installation. The internal surface of all black Allied Tube Conduit Fire Sprinkler pipe products up to 4.5000' in diameter is coated with our new Antibacterial Formula, ABF' In scientific laboratory test, ABS proved to have superior resistance to microbial colonization of pipe walls, thereby delaying or possibly preventing the onset of Microbiologically Influenced corrosion (MIC) when the First Sprinkler System is first installed. .VICE /Flow Control n a iecJ TUBE CONDUIT NPS Nominal l.D. Wt. Wt. (Ii20 Filled) Pcs/ WI/Lift (21') Wt/Lift (24') Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg /m Lbs /Ft Kg/rn Lift Lbs Kg Lbs; Kg Lbs; Kg 1 1 191 0.830 1.31 91 1,586 1,812 1,888 25 30.3 1.2 1.95 91 719 822 856 1 1.536 1 059 1.87 61 1,356 1,550 1,615 32 39.0 1.6 2.78 61 615 703 733 11/2- 1 728 1.667 2.71 61 2,135 2,440 2,542 40 43.9 2.5 4.03 61 968 1107 1153 2' 2.203 2.104 3.79 37 1 634 1,868 1,946 50 56.0 3.1 5.64 37 741 847 883 2W 2.703 2.564 5.10 30 1,615 1,846 1,923 65 68.7 3.8 7.59 30 733 837 872 3' 3.314 3.387 718 19 1,351 1,544 1 608 80 84.2 5.0 10.69 19 613 700 729 4" 4.310 4 473 10.86 19 1 784 2,039 2,124 90 109.5 6.7 16.16 19 809 925 963 Specifications Approvals Dyna -Flow /Super Flo pipe is manufac tured to meet ASTM A -795 Type E, Grade A and is in compliance with NFPA 13 and NFPA 14 All sizes of Dyna Flow /Super Flo are UL Listed, FM Approved and ULC Listed. Listed Approved Listed Dyna -Flow /Super Flo is UL/ULC Listed for use with roll grooved, plain-end couplings, and welded joints for wet, dry, preaction and deluge systems. It is FM Approved for roll grooved, plain -end, and welded points for wet systems. Refer to appropriate documentation for up -to -date hstmg and approval information. Dyna Flow /Super Flo is now available 'hot dip galvanized and has been specifically approved by FM for dry systems uses. 16100 S Lathrop Harvey IL 60426 11350 Norcor i Philadelphia, 19154 2525 N. 27 th Ave. Phoenix, AZ 85009 Additional Benefits Lightweight and easy to install, resulting in more efficient use of your freight and labor dollars. Provides stability needed to comply with standard hanger spacing (15 ft 0 C.) per NFPA. Available in Standard lengths for your convenience, or can be ordered in custom lengths upon approval. Fast cutting and welding, as well as easy roll grooving and end preparation. Available in Factory roll grooved form for quicker shop turnaround. Clean, durable mill coating provides longer 'shelf life' and acts as an excellent primer for custom paint applications. Customer Service: (800)882 5543 Fax 708 -339 -1806 S2 3 CENTRAL THREADED FITTINGS i 0 -01 Threaded Fittings Tyco Fire Products www tyco grooved.com 451 North Cannon Avenue Lansdale Pennsylvania 19446 USA Customer Service /Sales Tel (215) 362 -0700 Fax: (215) 362 5385 Technical Services Tel: (800) 381 -9312 Fax: (800) 791 5500 General Description See Fire Protection Submittal Sheet for pressure rating and Listing and Approval information Ductile Iron threaded fittings (with the exception of California Tees and Street Elbows) conform to ANSI B16 3 They are higher in strength and more corrosion resistant than cast iron fittings. The additional strength is provided by the ductile properties making up the fitting This is accomplished by adding magnesium while the iron is being poured into it final cast shape. This provides an advantage as the fittings are not as susceptible to leaks or cracking and they are also lighter than standard cast iron. Caution: Installers who have not used ductile iron threaded fittings before should be instructed that the fittings are stronger than the pipe and over tightening the fitting can create leaks and cause damage to pipe threads. In general, there is about one -half turn difference between cast iron and ductile iron fittings. Apply Teflon tape or high quality pipe joint compound on the male pipe threads and tighten two to three turns beyond hand tight. If you are using an automatic make -on machine, please exercise caution in setting your machine to the proper parameters prior to tightening fittings onto the male pipe threads. Technical Data Figures: 811 812, 813 814 815 816 817 818, 820 825 827 830 719 California Tees and Street Elbows Sizes: 1 /2 2 Maximum Working Pressure: 800 Series, California Tees, and Street Elbows. 300 psi Figure 719 250 psi Approvals: UL, and FM Note: See Fire Protection Submittal Sheet for exact Listing /Approval information. Manufacture Source: Imported Material: Ductile Iron, conforming to ANSI B16 3 (Note. Figure 719 Plugs are constructed of Cast Iron) Thread: N P T Installation Apply Teflon Tape or high quality pipe joint compound on the male pipe threads and tighten two to three turns beyond hand tight. (See caution in first column) Am■ CENTRAL Grooved Piping Products Ordering Procedure Ordering information: When placing an order indicate the full product name. Please specify the quantity figure number and size. Availability and Service: Grooved Piping Products, valves, accessories and other products are available throughout the U S. Canada, and internationally though a network of distribution centers. You may write directly or call 215 362 -0700 for the distributor nearest you. Care and Maintenance The owner is responsible for the inspection, testing, and maintenance of their fire protection system-and devices in accordance with the applicable standards of the National Fire Protection Association (e g NFPA 25) in addition to the standards of any authority having jurisdiction. The installing contractor or product manufacturer should be contacted relative to any questions Any impairment must be immediately corrected It is recommended that automatic sprinkler systems be inspected, tested and maintained by a qualified Inspection Service No. 21 3.0 A Figure 811 90° Elbow Figure 813 45° Elbow Figure 812 90° Reducing Elbow Figure 814 Tee Size Size Inches 1 /2 3 /4 1 1 I1 1 2 2 A Inches 1 1 1 1 1 15 /16 2 2 "/16 B Inches 9 /16 3 /4 13 /16 1 1 1 1 Size A B C D Part Weight Box Inches Inches Inches Fnches Inches Number Lbs. Qty 3 /4 x 1/2 1 1 1 1 1 5 /6 1 5 /8 1 86342 I 0.33 1 160 1 1 1 x 1 /2 I 1 1 1 /8 1 9 /16 1 13 /16 1 86210 10 44 1 110 1 1 x 3/4 I 1 -/6 1 1 /16 1 '1 /16 1 7 /8 1 86211 I 0.53 90 1 1 x I 15/16 I 1 I 5 /8 15/16 1 86212 I 0 64 75 1 x 3/4 1 17/16 1 1 3 /4 11/16 1 86213 1 0 75 60 1 x 1 1 1 1 7 /8 1 1 86214 10 77 55 1 x 3 /4 1 I 13/4 1 3 /4 1 1 86221 I 0.95 45 1 1 x 1 1 1 1 1 73 /16 1 7 /e 11/8 1 86215 1 0.99 40 11 x 1 113/16 I 17/a 1 1 1 86216 I 1 14 35 1 2 x 3/4 1 1 1 1 1 7 /a 1 1 86217 I 1.39 30 2 x 1 I 13/4 1 21/16 1 2 1 1 86218 I 1.58 25 2 x 1 I 2 I 2 I 1 1 1 86220 I 1.67 20 1 1 2 x 2 1 23/s I 25 /a I 1 17/8 1 86262 I 3.01 15 1 Size A B Part Weight Box Inches Inches Inches Number Lbs. Qty. 1 /2 1 7 /6 3 /6 86780 I 0.22 1 250 3 /4 1 1 7 /16 86781 I 0.33 1'150 1 1 1 13 /16 86280 I 0 48 190 1 1 1 5 /6 86281 1 0.73 1 50 1 1 1 1 11 /16 86282 I 0.93 35 1 2 1 1 15 /16 86283 I 1.55 1 18 I 2 1 1 1 86782 I 2.70 112 1 Size A B Part Inches Inches Inches Number 1 /2 1 1 1 9 /16 1 86340 3 /4 1 15/16 1 3/4 1 86341 1 1 11/2 1 X 1 86230 1 1 1 1 1 1 86231 1 1 115/16 1 1 I 86232 1 2 1 2 1 1 1 86233 21/2 1 1 1 9 /1 6 86234 Part Weight Box Number Lbs. Qty 86206 1 0.24 1 2401 86205 1 0 40 1 120 86200 1 0 64 1 70 86201 1 0.95 140 1 86202 1 1.24 30 86203 1 1 74 20 86204 1 3.28 10 1 Weight Box Lbs. Qty 0.33 1 150 0.50 190 0.85 1 60 1.30 1 35 1.63 1 24 2.63 1 12 4.55 1_...8.- -2- Figure 815 Reducing Tee Size A B CD E F Part Wt. Box Inches Inches Inches Inches Inches Inches Inches Number Lbs. Qty. 1 3 /4 X x1/2 1 1 I 1 I 11/4 1 5/8 1 5 /6 11 /16 18623510 461 95 3 /4 x 3 /4 x 1 1 1 I 1 1 1 I 7 /8 I 7 /8 11 /16 18675510 681 65 I 1 X1/2x1 111 11/ 13/ 1 11/ 1 13/16 1 13 /16 13 /16 186236 1 0 701 55 1 1 x 3 /4 x 1 1 1 1 1 9 /16 5 /8 13 /16 18675610 631 80 1 x 3 /4 X 3 /4 1 1 1 1 I t 3 /4 7 /8 18675710.681 65 1 x x 1 1 1 1 1 7 /6 13 /16 18623710 771 55 1 x 1 x' /z 1 1 1 1 9 /1s 9 /16 13 /16 18623810.661 65 I 1 X 1 X 3 /4 1 1 1 1 71 /16 11 /16 7 /8 18623910.731 60 1 x 1 x1 1 1"/161 1 1 1 7 /8 1862401 0.971 45 1 x11 x1 1 1 1 1 1 7 /6 186241 1 1 141 35 1 x l x 1 /2 1 1 11 5 /e 9 /16 1 1 1862421.0.81 1 50 1 x 1 x 1 1 1 1 /a 3 /4 11 /16 1 1 1862431 0.901 50 x 1 x 1 1 1 1 1 7 /6 13 /16 1 1 18624411 031 45 1 x1 1 1 1 1 1 1 1 1862451 1 101 40 1 1 x1 1 1 1 1 1 1 18624611 431 30 1 1 1 1 1 1 1 "/16 71 /16 1 1 18624710.871 45 1 1 1 x 1 1 1 1 3 /4 3 /4 1 1 186248 0.961 45 1 1 1 1 11 1 7/a 1 7 /6 I 1 1 86249 1 101 40 1 1 1 11 1 1 1 18625011 501 30 11 2 2 1 2 1 1 1 1 18625112.001 24 1 1 X 1 X 1 /2 1 151 1 1 11/16 5 /6 1 1 862521 0.97 40 1 1 x 1 x 3 /4 1 1 /a 1 1 3 /4 51 /16 1 1 8625311 14 40 1 x 1 x 1 1 1 11 7 /a 13 /16 1 1 86254 1 14 30 1 1 x1 1 1' 1 1t 1 1 1 1 86255 1.52. 30 1 1 1 71 /16 5 /8 11 86257 1.03 40 1 /2x1 1 1 I 1 3 /4 3 /4 1 1 86258 1 10 40 1 1 x 1 1 1 11 7 /8 7 /6 1 1 86259 1.31 30 1 2 2' /e 2 1 1 1 86260 1.94 20 .1 1 1 /2 x 1 /2 1 7 /16 1 1"/16 11 /16 11/16 1 1 86261 1 14 35 1 1 x3/4 1 1 1 3 /4 3 /4 1 1 86262 1.23 35 1 1 1 1 1 1 7 /8 7 /6 1 1 86263 1.38 30 1 1 73 /16 1 13 /16 1 1 1 1 1 86264 1.50 30 1 1 2 2 2 17/16 1 1 1 1 86265 2.00 20 2 x 1 x 2 2 2 2 1 1 1 1 86266 2.18 15 2 x 1 x2 2 2 2 1 1 1 1 1 /2 86267 2.31. 15 2 X 1 1 1 1 3 /4 11/15 1 1 86268 1.50 30 2X1 x 1 1 1 /2 1 7 /8 3 /4 1 86269 1.61 25 2x1 1 1 2 1 7 /6 1 86270 1.65 20 2X1'/2X1 2 1 2 1 1 1 86272 2.03 20 1 2 x 1 2 2 2 1 1 1 86273 2.37 15 1 2 x 2 x 1 1 1 3 /4 3 /4 1 86222 1.50 30 2 X 2 X 3 /4 1 1 1 7 /8 7 /8 1 3 /8 86223 1 67 20 2 x 2 x 1 1 1 2 1 1 1 86224 1.91. 20 1 2 x2 x1 1 1 2 1'/a 1 1 86225 2.05 20 2 x 2 x 1 2 2 1 2 1 1 1 86226 2.11 15 1 2 x 2 x 2 2 2 1 2 1 3 /4 1 1 86227 3.67 10 I 2'12 x 2 x 3 /4 13/4 1 1 5 /8 -7 /6 1 86274 2.22 15-1' Figure 816 Figure 825 Extension Piece Reducing Coupling Size Inches 1 1 1 2 1 x 1 1 x 1 1 2x2x1x1 Figure 820 Cap Size A B Part Weight Box Inches Inches Inches Number Lbs. Qty 1 x 1 /21 1 1 11/16 1 86772 1 0.38 12401 1 x 1t 1 1 /2 1 86228 1 0.38 200 1 x 3 /41 1 1 1 /2 1 86229 1 0.53 110 Figure 817 Cross A B Inches Inches 1 1 1 1 1 1 115/16 1 115/16 21/4 I 21/4 1 1 1 1 t 1 1 2 1 1 t- r Figure 818 Straight Coupling Size A B Part Inches Inches Inches Number 1 /2 1 1 5/16 1 72779 3 /4 I 1 1 9/16 1 72778 1 1 1 1 3/6 1 72755 11/4 1 2 I 9 /16 72754 11/2 I 2 1 3/4 1 72753 2 1 2 11/6 1 72752 2 I 3 3 /4 1 72758 C D Part Weight Box Inches Inches Number Lbs. Qty 13/16 I 13 /16 1 86284 I 0.97 145 11/16 1 11/16 1 86285 1 1.59 25 1 1 11 3/16 1 86286 1 1.89 1 20 1 11/2 1 1 86287 1 2.93 1 10 1 I 7 /6 1 86289 1 1.25 1 30 1 1 115/16 1 86322 1 1 48 1 24 1 11/4 1 1 1 86291 1 2.64 1 10 1 Yr I B A Wrench 1 /a 1 1"/16 2 2 2 3 Weight Box Lbs. Qty. 0 18 1 360 0.26 1 200 044 110 054I 75 0 71 1 60 1151301 2.29 I 18 1 Size A Part Weight Box Inches Inches Number Lbs. Qty 1 /2 7 /e 1 72776 015 1500 3 /4 1 1 72777 0.22 1300 1 1 1. 72824 0.33 1 180 1 1 1 72756 0.54 1 110 1 1 1 72822 0.68 1 80 2 1 1 72823- 0.96 1 45 2 1 1 72825 1.80 1 25 3- A Figure 827 Hex Bushing Figure 830 Brass Seat Union Figure 719 Cast Iron Plug- Size A Part Weight Box Inches Inches Number Lbs. Qty 1 /2 x 1 11/2 1 72751 0.20 13001 1 1 /2 x 2 1 2 1 72980 1 0.27 1 250 3 /4 x 1 1 1 72981 I 0.22 1250 3 /4 x 2 1 2 1 72982 1 0.31 1 200 A I Size Inches 1 x 1 x 1 x 1 11 1 2x1 1 2 x1 1 2 x1 A Inches 1 1 1 1 1 1 1 13/4 Part Weight Number Lbs. 72726 1 0.22 72762 1 0 18 72763 1 0.3.1 72757 I 0 53 72764 I 0.35 72759 1 0 75 72761 1 0 69 72775 I 0 62 Size A B Part Weight Box Inches Inches Inches Number Lbs. Qty. 1 /2 1 1 /8 1 13 /16 1 86207 0 47 1 110 3 /4 1 2 1 15/16 1 86275 1 0.66 1 80 1 1 1 2 13 /16 1 86276 1 1 08 1 50 1 I 2 1 1 86277 1 1.54 1 35 1 1 2 /a 1 1 86278 1 2.03 25 1 2 1 3 1 1 1 86279 1 3.15 1 18 Size A Part Inches Inches Number 1 /2 1 15 /16 1 86292 1 3 /4 1 1 1 86293 1 1 1 1 86294 1 1 1 1 86295 1 1 1 1 86296 .1 2 1 1 86297... Weight Lbs. 0 10 0 18 0.28 0.50 0 70 0.90. Box Qty 280 280 150 1001 100 80 80 80 Box Qty 5001 3001 200 110 80 1 45 1 Street Elbows Size A B C Part Weight Inches Inches Inches Inches Number lbs. 1 x I 1 I 3 /4 3 1 42003 10 70 1 x 1 I 1 I 3 /4 13 1 42002 I 0.90 Limited Warranty tgqcci /Flow Control/ Tyco Fire Products Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service This warranty will expire ten (10) years from date of shipment by Tyco Fire Products No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse improper installation corrosion or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association (NFPA), and /or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Products to be defective shall be either repaired or replaced at Tyco Fire Products sole option Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer's representatives. -4- California Tees Box Size A B C D Qty Inches Inches Inches Inches Inches Number 80 I 11 x x 1 I 1 I '/e I 3 I 3 /4 1 42000 60 I 11 x 1 x 1 I 1 I 3 /4 I 3 I 3 /4 1 42001 I General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data is not exceeded. Never remove any piping component nor correct or modify any piping deficiencies without first depressurizing and draining the system. Material and gasket selection should be verified to be compatible for the specific application. Part Weight Box lbs. Qty 0.95 50 0 95 45 IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT TORT STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY FOR INCIDENTAL, INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES INCLUDING BUT NOT LIMITED TO LABOR CHARGES REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE. IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED. INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Printed U.S.A. 10 -01 Technical Services: Tel: (800) 381 -9312 Fax: (800) 791 -5500 www.tyco- fire.com Grinnell Grooved Fire Protection Products Grooved Fittings General Description (LB VdS) 01) The grooved fittings provide an economical and efficient method of changing direction, adding an outlet, reducing, or capping grooved piping systems. Grooved fittings are available in durable ductile iron or fabricated steel as indicated. Note: Figure 510S and 519S fittings are special short radius fittings with smaller center to end dimensions than standard grooved fittings. Depending on the size and coupling used, there may be interferences at the bolt padsthat require repositioning of the coupling orientation The use of flange adapters is not recommended with Figures 510S and 519S fittings. Contact Tyco Fire Products for details. WARNING The Fittings described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of this device. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data See Fire Protection Submittal Sheet for Pressure Rating and Listing/Approval Information Approvals: UL, FM, ULC, VdS, and LPCB• Note: See Fire Protection Submittal Sheet for exact Listing Approval-information. Fire uil d Produas Material. Cast: Figures: 201 210 219, 250, 260 501 510, 519 510DE, 501S, 510S and 519S Ductile iron conforming to ASTM A -536, Grade 65 -45 -12 Fabricated Steel: Figures 391 392, 393 312, 313, 321 327 341 and 350 Carbon Steel, (Sizes 1 6' are Schedule 40); (Sizes 8° 12" are Schedule 30), conforming to ASTM A -53 Grade B Protective Coatings: Non -lead orange paint Fire brigade red (optional) non -lead paint Hot dipped galvanized conforming to ASTM A -153 Ordering Procedure When placing an order indicate the full product name. Pleasespecifythe quantity figure number wall thickness, and size. Grinnell Grooved Piping Products, valves, accessories and other products are available throughoutthe U.S. Canada, and internationally through a network of distribution centers. You may write directly or call 215 -362 -0700 for the distributor nearest you. Care and Maintenance The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in accordance with the applicable standards of the National Fire Protection Association (e.g. NFPA 25) in addition to the standards of any authority having jurisdiction. The installing contractor or p rod uct man ufactu rer should be contacted relative to any questions. Any impairment must be immediately corrected. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service. Limited m Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paidforand properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products o rfo r products and components which have been subject to misuse. improperinstallation, corrosion, orwhich have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association (NFPA), and/orthe standards of any otherAuthorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products sole option. Tyco Fire Products neither assumes, nor authorizes any person to assumefor it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall notbe responsibleforsprinklersystem design errors orinaccurate orincomplete information supplied by Buyer or Buyer's representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT TORT STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY FOR INCIDENTAL, INDIRECT SPECIAL OR CONSEQUENTIAL DAMAGES, I BUTNOT LIMITED TO LABOR CHARGES, REGARDLESS OF WHETHERTYCO Fl RE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCTS' LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING WARRANTY IS MADE IN LiEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED. INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Page i of 6 September 2004 TFP1810 Page 2 of 6 TFP1810 CtoE L Figure 201 88 .9 C to E t. 1. CtoE I Figure 219 Figures 201 210, 219, and 260 Figure 210 Figure 260 Friction Resistance' (Expressed as Equivalent Straight Pipe) I Elbow I' Tee Size 90° I 45° .I Branch I Run Inches Feet Feet Feet Feet mm Meters I Meters I Meters I Meters 1.9 42.4 0.6 0.3 I 1.5 0.6 11/2 2.3 1.2 5.8 2.3 48.3 0.7 0.4 1.8 0.7 2 3.2 1.6 8.0 3.2 60.3 1.0 0.5 I 2.5 1.0 21/2 3.9 2.0 9.8 3.9 73.0 1.2 0.6 I 3.0 1.2 76.1 mm 4 1 2.1 10.3 4 1 1.2 0.6 3.1 1.2 4.9 2.4 12.2 4.9 1.5 0.7 3.7 1.5 108 0.m 6.5 3.3 16.3 6.5 2.0 .1.D I 5.0 2.0 4 6.5 3.3 16.3 6.5 114.3 .2.0 1.0 5.0 2.0 133.0 8.0 4.0 20.0 8.0 2.4 1.2 '6.1 2.4 139 7mm 8.0 4 1 20.0 8.0 2.4 1.3 6.1 2.4 5 8.2 4 1 20.5 8.2 141.3 2.5 1.3 6.3 2.5 159.Omm 9.5 4.8 23.8 9.5 2.9 14 7.2 2.9 165 1 9.5 4.8 23.8 9.5 2.9 1 4 7.2 2.9 6 9.9 5.0 24.8 9.9 168.3 3.0 1.5 7.6 3.0 216.3°° 13.1 6.6 32.8 13.1 4.0 2.0 10.0 4.0 8 13.1 6.6 32.8 13.1 219.1 4.0 2.0 10.0 4.0 10". 16.5 8.3 41.3 16.5 273.0 5.0 2.5 12.6 5.0 12 19.9 9.9 49 7 19.9 323.4 6.1 3:0 15.1 6.1 For reducino tees and branches, use the value that is corrosponding to the branch size. Example: for 8' x 8' z 2" tee, the branch value 2' is 8.0 feet Friction resistance for all elbows and tees except Figures 5105 and 519S. Nominal Size 2" 2 76.1 mm 1 108.0mm 4' 133.0mm 139 7mm 5' 1 159.0mm 165.1 mm 6' I 216.3mm 8' 1 10' 12" Figure 201 Figure 210 45° Elbow 90 Elbow C to E Appx. Wt. C to E Appx. Wt. Inches Lbs. Inches Lbs. mm Kg. mm Kg. mm 1 75 0.9 44.5 0.4 I 69.9 0. 5 I 69.9 1 75 1 1 2.75 1.2 2.75 44.5 0.5 I 69.9 I 0.5 69.9 2.00 1.8 I 3.25 2.0 3.25 50.8. 0.8 82.6 0.9. 82.6 2.25 2.2 3.75 3.0 3.75 57.2 1.0 95.3 14 95.3 2.25 2.2 3.75 3.0 3.75 57.2 1 0 95.3 14 95.3 2.50 3.5 4.25 4.5 4.25 63.5 1 .6 1 108.0 2.0 108.0 2.88 5.5 4 75 8.5 4 75 73.0 2.5 120.7 3.9 120.7 3.00 5.2 5.00 8.5 5.00 76.2 2.4 127.0 3.9 127.0 3.25 7 7 5.25 11.3 5.25 82.6 3.5 133.4 5.1 133.4 3.25 7 7 5.50 11.3 5.50 82.6 3.5 139.7 5.1 1.39.7 3.25 8.5 5.50 13.5 5.50 82.6 3.9 139.7 6.1 139.7 3.50 12.0 6.00 14.6 6.00 88.9 5.4 152.4 6.6 152.4 3.50 12.0 6.50 18.5 6.50 88.9 5.4 165 1 8.4 165.1 3.50 12.0 6.50 18.5 6.50 88.9 5.4 165.1 8.4 165.1 4.25 23.0 7 75 36.5 7 75 108.0 10.4 196.9 16.6 196.9 4.25 23.0 7 75 36.5 7.75 108.0 10.4 196.9 16.6 196.9 4 75 31.0 9.00 60.0 9.00 120.7 14.1 228.6 27.2 228.6 5.25 40.0 10.00 67.0 10.00 133 4 18.1 254.0 30.4 1 254.0 Available with tapped plugs. contact Tyco Fire Building Products. Figure 219 Figure 260t Tee End Cap C to E Appx. Wt. E to E Appx. Wt. Inches Lbs. Inches Lbs. mm Kg. 0.88 0.4 22.4 0.2 0.88 f 0.6 22.4 0.3 0.88 0.9 22.4 0.4. 0.88 0.9 22.4 0.4 0.94 1 1 23.9 0.5 0.88 1 1 22.4 0.5 Kg. 14 0.6 1.8 0.8 2.7 1.2 5.8 2.6 5.8 2.6 7.0 3.2 11.5 5.2 11.8 1.00 2.6 5.4 254 1.2 10.6 4.8 15.3 0.92 4 7 6.9. 23 4 2.1 17.0 1.00 5.0 7.7 25.4 2.3 13.9 6.3 26.0 1.00 7.5 11.8 25 4 3.4 26.0 1.00 7.5 11.8 25.4 3.4 45.0 20.4 45.0 1 19 12.8 20.4 30.2 5.8 72.1 1.25 20.0 32.7 31.8 9 1 92.5 1.25 36.0 42.0 31.8 16.3 Page 3 of 6 TFP1810 Figures 501, 510, 519 and 510E i- CtoE --I Figure 501 Figure 501 Figure 510 Figure 519 45 Elbow 90° Elbow Tee Nominal C to E Appx. Wt. C to E Appx. Wt. C to E Appx. Wt. C to E Size Inches Lbs. Inches Lbs. Inches Lbs. Inches mm Kg. mm Kg. mm Kg. mm 1.75 0.9 2.75 1.0 2.75 14 44.5 0 4 69.9 0.5 69.9 0.6 1.75 1 1 2.75 1.2 2.75 1.8 44.5 0.5 69.9 0.5 69.9 0.8 2.00 1.8 3.25 2.0 3.25 2.7 50.8 0.8 82.6 0.9 82.6 1.2 2.25 2.2 3.75 3.0 3.75 5.8 57.2 1 0 95.3 1 4 I 95.3 2.6 2.50 3.5 4.25 4.5 I 4.25 7.0 63.5 1.6 108.0 2.0 108.0 3.2 3.00 5.2 5.00 8.5 5.00 11.8 76.2 2.4 127 0 3.9 127.0 5.4 3.25 8.5 5.50 13.5 5.50 17.0 82.6 3.9 139.7 6.1 139.7 7 7 3.50 12.0 6.50 18.5 6.50 26.0 88.9 5 4 1 165.1 8.4 I 165.1 11.8 4.25 23.0 I 7.75 36.5 I 7.75 45.0 108.0 10.4 I 196.9 16.6 196.9 20.4 1'/4 1 2' 2 3' .d 5' 6 8 2 3.2 1.6 60.3 1.0 0.5 2Y 3.9 2.0 73.0 1.2 0.6 76.1 mm 4 1 2.1 1.2 0.6 3 4.9 2.4 88.9 1.5 0.7 4 6.5 3.3 114.3 2.0 1.0 139.7 8.0 41 2.4 1.3 5 8.2 4 1 141.3 2.5 1.3 165.1.m. 9.5 4.8 2.9 14 6 9.9 5.0 168.3 3.0 1.5 8 13.1 6.6 219.1 4.0 2.0 Figures 5015, 510S and 5195 L Figure 501S Friction Resistance 501S 510S 519S (Expressed as Equivalent Straight Pipe) Elbow .I Tee Size 90° 45° IBranch Run Inches Feet Feet Feet Feet mm Meters Meters Meters 1 I Meters 8.0 3.2 2.5 1.0 9.8 3.9 3.0 1.2 10.3 4 1 3.1 1.2 12.2 4.9 3.7 1.5 16.3 6.5 5.0 2.0 20.0 8.0 6.1 2.4 20.5 8.2 6.3 2.5 23.8 9.5 7.2 I 2.9 24.8 i 9.9 7.6 3.0 32.8 13.1 10.0 I 4.0 Figure 510 Clot i -Ctot Figure 510S* I Figure 501S 45° Elbow Nominal C to E Appx Wt. Size Inches Lbs. mm Kg. 2° I 21'2 76.1mm 3' 4' 1 139.7.., 5' 6 8 c toE i 1 Figure 519 3.75 95.3 4.25 108.0 5.00 1270 5.50 139.7 6.50 165.1 7 75 196.9 2.00 50.8 2.25 57.2 2.25 57.2 2.50 63.5 3.00 76.2 325 82.6 3.25 82.6 3.50 88.9 3.50 88.9 4.25 108.0 Figure 510DE 90° Drain Elbow A B Appx. Wt. Inches Inches Lbs. mm mm Kg. 2.00 I 50.8 2.34 59.4 2.85 72.4 3.38 85.9 3.92 99.6 4.95 125.7 2.75 69.9 2.75 69.9 2.75 69.9 2.75 69.9 2.75 69.9 2.75 69.9 --CtoE -I 4 i CtoE Figure 519S" 1.8 0.8 2.2 1.0 2.2 10 3.5 16 5.2 2.4 77 3.5 8.5 3.9 12.0 5.4 12.0 5.4 23.0 10.4 Ct 1 C to E Figure 510DE 2.7 1.2 3.7 17 7.0 3.2 13.0 5.9 13.4 6.1 26.3 11.9 Figure 510S I Figure 519S I 90° Elbow Tee C to E Appx. Wt. C to E Appx. Wt. Inches Lbs. Inches Lbs. mm Kg. mm Kg. 2.75 1.5 2.75 2.1 69.9 0.7 69.9 I 1.0 3.00 2.2 •3.00 3.0 76.2 1.0 76.2 1 4 3.00 2.3 3.00 3.1 76.2 1.0 76.2 14 3.38 3.0 3.38 4 1 85.9 1.3 85.9 1.9 4.00 5.6 4.00 7 7 101.6 2.6 101.6 3.5 4.88 8.6 4.88 12.0 124.0 3.9 124 0 5.4 4.88 8.8 4.88 12.0 124 0 3.9 124.0 5.4 5.50 11.00 5.50 15.0 139.7 5.0 139.7 6.8 5.50 11.2 5.50 15.2 139.7 5.1 139.7 6.9 6.88 23.4 6.88 31.2 174.8 10.6 174.8 14.2 Note: Figure 5105 and 519S fittings are special short radius fittings with sma lot center to end dimensions than standard grooved fittings. Depending on the size and coupling used there may be interferences at the bolt pads which requires repositioning of the coupling orientation. The use of flange adapters is not recommended with Figures 51DS and 5195 fittings. Contact Tyco Fire Products for details. Page 4 of 6 TFP1810 f to E---{ Figure 250 Cast h- E to E-1 Fgure 350 Fabricated Sizes 3' to 6" to E--{ Figure 350 Fabricated Sizes 8" to 12' Nominal Size Inches *2 x 1'/4 *2 x 1' /z *2' /z x 2 *76.1mmX1Y *76 1 mm X 2 3x1Y4 3x1' /z *3 x 2 *3 x 2Yz *3 x 76.1 mm 4x114 x11 4x2 4 x 2" 4x76.1mm 4x3 Figures 250 and 350 Figures 250 and 350 Concentric Reducer Groove x Groove E to E Inches mm 2.50 63.5 2.50 63.5 2.50 63.5 "2:50 63.5 2.50 63.5 2.50 63.5 2.50 63.5 2.50 63.5 3.00 76.2 3.00 76.2 3.00 76.2 3.00 76.2 3.00 76.2 3.00 76.2 3.00 76.2 3.00 76.2 Appx. Wt. Nominal E to E Appx. Wt. Lbs. Size Inches Lbs. Kg. Inches mm Kg. 1.0 1 39 7mm x 3 3.50 4.2 0.5 I 88.9 1.9 1.3 *139 7mm x 4 3.50 4 4 0,6 88.9 2.0 1.2 5 3.50 4.6 0.5 88.9 2.1 1 .5 3.50 4 6" (17 5x2 88.9 2.1 1.6 5 x 21/2 3.50 4.5 0.8 I I 88,9 2.0 1.3 3.50 4 4 05 5x3 88.9 2.0 1.3 3.50 4.5 0.6 *5x4 88.9 2.0 0.6 I "165.1x 3 101.6 2.5 07 I *165.1mmx 1016 2 0.9, I '165.1rmx 100 2. 5 2.2 4.00 6.0 1.0 *6 x 2 101.6 2.7 2.3 4.00 6.0 6 x 2Yz 1.0 I 101 6 2.7 2.3 4.00 6.0 1 I *6 x 76.1 mm 101 6 2.7 2.3 4.00 6.0 1.0 I 6x3 1016 2.7 3.2 4 00 5.9 1.5 *6x4 101.6 2.7 2.6 *6 x 139.7mm 100 6 2.9 Note: Sizes marked with an asterisk are only available in Figure 250 Cast Sizes vithout an asterisk are only available in Figure 350 Fabricated. ADA CAP® Patented Nominal E to E Appx. Wt. Size Inches *6X5 8x2 8x2',2 8x3 8x4 8x5 8x6 10x4 10x5 10x6 10x8 12 x 4 12 x 6 12 x 8 12 x 10 Inches Lbs. mm 4.00 101.6 5.00 127.0 5.00 127 0 5:00 127.0 5.00 127.0 5.00 127.0 5.00 127.0 6.00 152.4 6.00 152.4 6.00 152.4 6.00 152:4 7.00 177.8 7.00 177,8 7.00 177.8 7.00 177.8 Kg. 5 2.6 12.2 5.5 12.1 5.5 12.0 5.5 11.9 5.4 11.3 5.1 10.8 4.9 21.9 10.0 21.6 9.8 21 1 9.6 19.5 8.9 28.0 12.7 30.0 13.6 28.0 12.7 33.0 15.0 Pipe I Nominal Dimensions I I O.D. I Takeout I Center to End I Net Size Outlet A B C D Wt. Inches NPr Inches Inches Inches Inches Lbs. Inches mm mm mm mm 1.89 1/2 I 31.8 I 44.5 48.0 I 0 0. I 1 1' /z 3/4 1.900 1.25 1 75 1.89 0 77 C 48.3 31.8 44.5 48.0 0.3 B 1.37 2.00 2.02 0.88 1 34.8 50.8 51.3 0.4 I 1/2 1.25 175 1.89 0.92 31.8 44.5 48.0 I 0.4 2 3!4 2.375 1.25 175 1.89 0.92 60.3 31.8 44.5 48.0 0.4 I 1 1.37 I 2.00 2.02 1.06 34.8 50.8 51.3 0.5 1/2 I 147 37.3 1.97 1.89 1.28 50.0 48.0 0.6 2' /2 3/ 2.875 1 47 1.97 1.89 1.28 73.0 I 37.3 50.0 48.0 5.6 I 1 I 1.37 I 2.00 2.02. 1.50 34.8 50.8 51.3 0.7 ISO-7 threaded outlets are available upon request. Page 5 of 6 TFP1810 E to E EtoE--0-1 Figure 393 Figure 391 Figure 313 Figures 391, 392, 393, 312 and 313 Figure Figure 312 C to E CtoE -1 CtoE J Figure 327 I Figure 341 EtoE_H I C to E to E Nominal Size 1 1 2' 2 3' 4' 5' 6' 8' 10" 12" Figures 327 and 341 Nominal Size 2' 2 3" 4' 5" 6" 8' 10' 12" Figures 391 392 and 393 Adapter Nipples E to E Appx. Wt. Inches Lbs. mm Kg. I 4.00 0.8 101.6 0.4 4.00 0.9 1016 0.4 4 00 1.2 101.6 0.5 4.00 1.9 101.6 0.9 4.00 2.5 1016 11 I 6.00 5.5 152.4 2.5 6.00 7 4 152.4 3.4 I 6.00 9.5 152.4 4.3 6.00 14.2 152.4 6.4 8.00 27 0 203.2 1 12.2 8.00 203.2 33.0 15.0 Figure 312 Figure 313 22 Elbow 11 Elbow C to E Appx, Wt. C to E Inches Lbs. Inches mm Kg. mm 1 75 0.4 1.38 44.5 0.2 35.1 1 75 0.5 1.38 44.5 0.2 35.1 1:88 0:6 1.38 47.8 0.3 35.1 2.00 0 7 1.50 50.8 0.3 38.1 2.25 1 4 1.50 57.2 0.6 38.1 2.63 2.4 1 75 66.8 1 1 44 5 2.88 4 1 2.00 73.2 1.9 50.8 3.13 5.6 2.00 79.5 2.5 50.8 3.88 11 1 2.00 98 6 5.0 50.8 4.38 14 0 2.13 11.3 6.4 54 1 4.88 22.0 2.25 124.0 10.0 57.2 Figure 327 Figure 341 Cross 150 lbs. Flange Adapter. C to E Appx. Wt. E to E Appx. Wt. nches Lbs. Inches Lbs. mm kg. mm kq. 2.75 2.0 4.00 2.8 69.6 I 0.9 101.6 1.3 I 2.75 I 2.2 4.00 3.2 I 69.9 2.0 101.6 1.5 3.25 2.7 4 0 5.2 82.6 1.2 101.6 2.4 3.75 5.0 4.00 8.0 95.3 2.3 101.6 3.6 4.25 7 1 4 00 10.2 108.0 3.2 101.6 4.6 5.00 11.9 6.00 17.2 127.0 5.4 152.4 7.8 5.50 17 1 6.00 21 4 139.7 7.8 152.4 9.7 6.50 27.5 6.00 26.0 165.1 12.5 152.4 11.8 7 75 47.0 6.00 38.4 196.9 21.3 152.4 174 9.00 68.0 8.00 65.0 228.6 30.8 203.2 29.5 10.00 107 0 8.00 91.0 254.0 48.5 203.2 41.3 Appx. Wt. Lbs. Kg. 0.4 0.2 0.5 0.2 06 0.3 11 0.5 1.2 0.5 2.2 10 3.3 1.5 4.6 2.1 8.7 3.9 91 4.1 16.7 7.6 Page 6 of 6 TFP1810 I- Ctoc-H I 1 L_ I C to E 1 f 1 Figure 321 Figure 321 Nominal Size Inches 1/x 1'x 1Y 2x2x11 2;/2x21x1' /a 2%zx2Y2x1'h 2 x2 3x3x1'i2 3x3x2 3x3x2'h 4x4x11 4x4x1'h 4x4x2 4x4x21 4x4x3 5x5x2 5x5x2Y2 5x5 x3 5x5x4 6x6x2 6x6x2'/2 6x6x3 C to E Appx. Wt. Inches Lbs. mm Kg. 3.25 2.0 82.6 0.9 3.25 2.7 82.6 1.2 3.75 4.2 95.3 1.9 3.75 4.2 95.3 1.9 3.75 4.3 95.3 2.0 4.25 5.3 108.0 2.4 4.25 5.5 108.0 2.5 4.25 5.8 108.0 2.6 5.00 9.8 127.0 4.4 5.00 9.9 127.0 4.5 5.00 10.1 127.0 I 4.6 5.00 10.3 127.0 47 5. 10.5 1 27.0 4.8 5.50 14.5 139.7 6.6 5.50 14.8 139.7 6.7 5.50 15.2 139.7 6.9 5.50 15.8 139.7 7.2 6.50 26.5 165.1 11 9 6.50 26.5 165.1 12.0 6.50 26.5 165.1 12.0 Figure 321 Reducing Tee Nominal Size Inches 6x6x4 6x6x5 8x8x2 8x8x3 8x8x4 8x8x5 8x8x6 10x10x2 10x10x3 10x10x4 10x10x5 10x10x6 10x10x8 12 x 12 x 3 12 x 12 x 4 12 x 12 x 5 12x12x6 12x12x8 12x12x10 General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure that pressure ratings and performance data is not exceeded. Always read and understand the installation instructions (IH -1000) Never remove any piping component or correct or modify any piping deficiencies without first depressurizing draining the system: Material•and gasket selection should be'verified to be compatible the specific application. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 C to E Appx. Wt. Inches Lbs. mm 6.50 165.1 6.50 165 1 7 75 196.9 7 75 196.9 7 75 196.9 7 75 196.9 7 75 196.9 9.00 228.6 9.00 228.6 9.00 228.6 9.00 228.6 9.00 228.6 9.00 228.6 10.00 254.0 10.00 254.0 10.00 254.0 10.00 254.0 1 10.00 254.0 10.00 254.0 Kg. 26.6 I 12.1 27.0 12.2 36.2 16,4 36:5 16.6 36.6 16.6 36.8 16.7 37.0 16.8 571 25.9 57 4 26.0 57.6 26.1 57.8 26.2 58.0 26.3 58.4 26.5 80.2 36.4 80.5 36.5 80.7 36.6 80.9 36.7 91 4 41.5 91.8 41.6 Certified Company Printed U.S.A: vasmn�Z� 4 t. Fig 200 "Trimline" Adjustable Band Hanger Size Range 1/2' thru 8' pipe Material Carbon Steel, Mil. Galvanized to G90 specifications Function For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features (1/2' thru 2 Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion Captured design keeps adjusting nut from separating with hanger Hanger is easily installed around pipe. (2'/2 thru 8' Spring tension on nut holds it securely in hanger before installation Adjusting nut is easily removed Approvals Underwriters Laboratories listed (1/2' thru 8 in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and. Factory Mutual Engineering Approved (3/4 thru 8 Conforms to Federal Specifications WW-H -171 E, Type 10 and Manufacturers Standardization Society SP -69 Type 10 Maximum Temperature 650 °F Finish Mil. Galvanized. For Stainless Steel materi- als, order TOLCOTm Fig 200WON. Order By Figure number and pipe size 1/2 3/8 8mm or 10mm 3/4 3/8 8mm or 10mm 1 3/8 8mm or 10mm 1 /4 3/8 8mm or 10mm 1 3/8 8mm or 10mm 2 3/8 8mm or 10mm 21/2 3/8 10mm 3 3/8 10mm 3 3/8 10mm 4 3/8 10mm 5 1/2 12mm 6 1/2 12mm 8 1/2 12mm it t°al2li I PE 1W2. 71-A0 %1C1-4 PEPS Dimensions Weights Pipe Rod Size Size Inch Metric 31/2 21/2 400 11 31/2 2 400 11 3 21/2 400 12 3 21/2 400 13 3 2'/8 400 14 41/2 3 400 15 5 4'/8 600 27 51/2 4 600 29 7'/8 5'/4 600 34 7 5 1000 35 9 6 1250 66 101/2 6 1250 73 13 8 1250 136 Main Office /Manufacturing Facility 1375 Sampson As.. Corona, CA 9287° Ph: 909 737.5599 Fax: 909 737.0330 Customer Service 800.786.5266 www.tolco.com Max. Rec. Approx. A B Load Lbs. Length Fig 98 Rod Stiffener Size Range Secures 3/8' thru 7/8' hanger rod Material Carbon Steel Function Secures channel to hanger rod for vertical seismic bracing. Finish Electro Galvanized Note Available in HDG finish or Stainless Steel materials. Order By Figure number Fig 99 All Thread Rod Cut to Length Size Range Secures 3/8" thru 7/8' rod in 1 increments Material Carbon Steel Maximum Temperature 750 °F Finish Plain Note Available in Electro Galvanized and HDG finish or Stainless Steel materials Order By Figure number rod diameter rod length and finish Fig 100 All Thread Rod Full Lengths Size Range Secures 3/8' thru 7/8' rod in 10' lengths Material Carbon Steel Maximum Temperature 750 °F Finish Plain Note Available in Electro Galvanized and HDG finish or Stainless Steel materials. Order By Figure number rod diameter and finish Dimensions Weights Max Rec. Load Lbs. Rod For Service Temps Approx. Size 650 °F 750 °F Wt. /100 1/4 240 215 12 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 1 /4 8000 7140 360 1 11630 10370 510 Main Office/Manufacturing Facility 1375 SampsonAv_ Corona, CA 92879 Ph: 9 737.5599 Fax: 909 737.0330 Customer Service 800.786.5266 www.tolco.com Dimensions Weights Rod Max. Rec. Load Lbs. Size For Service Temps 650 °F 750 °F 3/8 6 0 540 1/2 1130 1010 5/8 1810 1610 3/4 2710 2420 7/8 3770 3360 wocrif A -12 CHANNEL Metal thickness is 12 Ga. 105 m.--15 A -12 Revision 8/30/02 Elements of Section Channel Area of AXIS X -X I AXIS Y -Y Catalog Weight Section I(in 4 S(in. R(in) I(in. S(in. R(in) Number lbs. /ft. Sq. A -12 1.89 583 I 18 .203 581 .257 316 680 A -12A 3.78 1 166 I 920 566 910 514 632 680 I Moment of inertia S Section modulus R Radius of gyration, Beam and Column Loads Data Channel Beam Span Uniform Load Deflection Uniform Load (lbs.) Maximum Catalog or Unbraced at St ess of at Stress of When Maximum Allowable Load Number Column Height 25,000'SI (lbs.) 25,000 PSI (in.) Deflection 2;," of Column (lbs.) A -12 18' 2213 031 2213 11300 24 1680 055 1680 9700 30' 1340 086 1340 8850 36' 1125 125 1125 8600 42' 950 168 950 7550 48' 855 .225 757 6720 60' 690 356 484 5800 72' 555 594 336 4970 84 490 693 247 4250 96' 4 .915 189 3500 120' 335 1 382 121 2100 A -12A 18" 6530 018 6530 24340 24 4895 033 4895 21800 30' 3800 050 3800 21500 36' 31100 070 3100 21000 42' 2700 097 2700 20600 48' 23 124 2300 19900 60' 1930 .203 1930 17950 72' 1580 .284 1560 15940 84 1360 393 1210 14750 96' 12b0 438 926 12650 120' 953 680 593 8000 Beam loads: Loads listed are uniformly distributed, for loads concentrated at center of span multiply uniform load at table by 5 and multiply the deflection by .8. When deflection is not a factor use stress of 25 000 PSI When deflec tion is a factor use deflection of r 240 Column loads. Loads listed are for unbraced heights as listed Modulus of elasticity 29 000 000 PSI Slotted or punched channel reduce load rating 10% Main OfficelManufachaing Facility 1375 Sampson Ace, Corona, CA 92870 Ph: 909.737.5599 Fax: 909.737.0330 Distribution Center 8790 Fruitridge Road Sacramento, CA 95826 Ph: 916.388.7800 Fax: 916.388.1401 Manufacturing Facility 4851 Homestead Road, Bldg. 118 Houston, TX 77028 Ph: 723.672.0058 Fax: 713.672.0074 www.tolco.com kft;WA/V.101CD:"COM a bran G i 4/Avyi Fig 65 and Fig 66 Reversible C -Type Beam Clamps 3/4" and 1 Throat Openings Size Range (Fig. 65 and Fig. 66) 3/8' 1/2' and 5/8' rod Material Carbon Steel with hardened cup point set screw and jam nut Function Recommended for hanging from steel beam where flange thickness does not exceed 3/4 (Fig 65) or 1 (Fig. 66). Features All steel construction eliminates structural deficiencies associated with casting type beam clamps. May be used on top or bot- tom flange of the beam. (Beveled lip allows hanging from top flange where clearance is limited) May be installed with set screw in up or down position Offset design permits unlimited rod adjustment by allowing the rod to be threaded completely through the clamp. Open design permits inspection of thread engagement. Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) Factory Mutual Engineering approved Conforms to Federal Specification WW -H -171 E, Type 23 and Manufacturers Standardization Society SP -69 Type 19 Exceeds requirements of the National Fire Protection Association (NFPA), Pamphlet 13 318' rod will support 1/2' thru 4 pipe, 1/2' rod will support 1/2' thru 8' pipe. Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish Plain Note Available in Electro- Galvanized and HDG finish. Order By Figure number rod size and finish Fig. 65 Patent #4 570 885 Rod Size A B C D E F 3/8 1 3/4 1 7/16 1 610 28 1/2 1 3/4 1 9/16 1 1130 55 5/8 1 3/4 1 9/16 1 1130 55 Max. loads for clamp with set screw in up or down position. Rod Size A B C D E F Max. Rec. Approx. Load Lbs.* Wt. /1 3/8 1 1 1 7/16 1 610 28 1/2 1 1 1 9/16 1 1130 55 5/8 1 1 1 9/16 1 1130 55 Max. loads for clamp with set screw in up or down position. Fig. 65 Dimensions Weights Fig 66 Dimensions Weights Max. Rec. Approx. Load Lbs.* Wt. /100 B D Component of State of California OSHPD Approved Seismic Restraints System OFFICE/MANUFACTURING FACILITY 1375 SAMPSON AVE. CORONA, CA 92879 PH: 951 737.5599 FAX. 951.737.0330 CUSTOMER SERVICE 800.786.5266 www.tolco.com B D .1 4 At Nut Driver 1/4' 8018957 4016 SWG 100 Use#14SWNutDriver 19 00. AN9 k f or SidevAnde:ig and 112' Rod Sam mys Part #8114910 Item #101 3/8' 8020957 18 SWG 10 ,'47. ,11 3/8' 8022925 26 SWG 25-380 1:40.54, 3/8' 8050957 39 SWD 10 1/4-14 X 1 25 7.50 125 ,D;$5t4))0,412'..,14`,.-.',' Y9'381., ::;.'1:;;#2 3/8' 8052957 41 SWD 20 1/4-14 X2 25 8.13 125 faiY.,i,5i.:".7tV.::::r47: 3/8' 8054957 46 SWDR 1 1/2' 1/4-20 X 1-1/2 25 9.06 125 3itt'21.11: ';13b8 re. itt ..!slixt1libal cimv.::. ge5W 3/8' 8056957 44 SWDR 516 5/16-18 X 1-1/4 25 10.31 125 k.?-fia .t:if NEW! NEVI!! NEINI_IIEW1 NEVE NEVI11);, 3 t r I escrptionsv Uninstalle Y-4.00"11 8139957 4702 SH-GST 20 1/4 x 2 25 9.38 125 vobrkatoilowitmwt4gx ,i277,0 A.-:::, i-vgarAT:J:gi •a! 8141957 4704 SH-GST 1/4 x 3 25 10.94 125 LZ„,'A;=,17;:*.ali147 2 5‘ 8137957 4700 SH-DSTR 1 1/4-20 x 1 25 9.38 125 W:4;;W°4415*7:4S151 Threaded Rod Directly Patent Pending Bang from Thin Gauge Metal Deck Installed ,04 §15t0:1 wsto-Ali 2:AmLx 1/4 X 1 25 9.38 125 4°X42YX;-'1,46254„ QP I 1/4 X 1 25 -04 X4t' 3/8 X 2-172 25 22-20 8150922 500 ,t3r53922.1' 7.50 125 "3 12.81 125 I}Mi et gjj 78.Wkin 11:ZATIXT1 WO: %,-,15 Most Items Available in Stainless Steel Use' willf318 "rr U.S Patent No 6,443,680 8151910 501 1/4-20x 1 1/8 XP 20 Sammy X-Press 20 25 Sammy X-Press It Installation Tool (Kit includes: Sleeve, Bit Receiver Hex Wrench, and 25/64" Drill Bit) XPIT as onerete 17 deflection from vertical Accommodates up to 3-1/2 x 12 pitch roof Also available in stainless steel Use #14 Nut Driver (black) 1.64-• od teel 10.3 125 02 ---1-- ood JTEP:Pmik:r 114" 8003957 22 1/4 8001957 20 31 1/4" 8005925 24 jri GST 750 8 1 ST Watir G.§1" 200 1/4 x 2 GST 600 1/4 x 6 3/8' 8006957 10 GST 75 1/4 x 3/4 .4C:46 ILIP,R1W f 1:'' l*liA51 *S5. 3/8' 8008957 12 GST 20 1/4 x 2 a87 *,3; 800992W "1:,:', ',GST25;g02,:i. lk I ---t 3/8' 8010957 30 GST 30 1/4 x 3 3 78:* It'i801 ',GSir;',1-32.: =4 'it 3/8" 8012925 14 GST 60 1/4 x 6 4 25 5.93 125 l'arw 'ti 25 8.13 125 25 11.25 125 25 5.63 125 Za%„1,:i1W.:7i; 25 7.50 125 25 8.75 125 25 11.25 125 1/2' 8013925 8 GST 2 1/4 X 2 25 8.75 125 I' Al?rt:', W1 5.k, _7; TWAT 45- WIWilR2` 2 V... Pr 1/2" 8015925 15 GST 3 1/4 X 3 25 13.13 125 120 4 1/2' 8017925 17 GST 6 1/4 X 6 25 13.69 125 1/4' 8024957 50 DSTR 100 1/4-20 X 1 25 7.81 125 1:047:IV8t1254 -441.ITL:TAPItqz "NI ,:=4'41#;43#5c>::50,; :2 .14-122.%: 4 1/4' 8026957 52 DST 150 1/4-14 X 1-1/2 25 6.88 125 4Y1r.: a topre:,;:sN' 7 l ''''ff 5 e'-' 5"748,qt421 aii 1/4' 8028957 54 DST 250 1/4-12 X 2-1/2 25 8.44 125 77 '''r!802.,9ei if:1s t 4,pp, ,„75.00,- ly:lopyg i '9108 8- lii. 1/4' 8030957 56 TEK 500 12-24 X 1 1/2 25 6.B8 125 Nut Driver ..2? 3/8' 8037957 29 DSTR 1-112" 12-24 X 1-1/2 25 7 75 125 Use ti4 Nut Driver .4.3.1:08g5vit.:zC't..„0,4„ -s,ip,q 40:4-,putiy... :4 A 1g8,17:! forSammYs and 3/8' 8039957 31 DSTR 516 5/16-18 X 1-1/4 25 7 06 125 Swivel Head =m4,,,,-.173:::-, .1:. dc§FliRxi: it '414.:::“1 F-5 4 4 3/8' 8041957 33 DST 15 1/4-14 X 1-1/2 25 6.56 125 8j 295 0 :f5)4:47 ATFOXIADE:lt."' giVAQ*1 zkifi:":1-. 3/8' 8043957 35 DST 25 1/4-14 X 2 1/2 25 7 81 125 ;12Wi.:7.aia?PZ,'743:::"1z.f;:lff14$:4 A 6. 3/8' 8045957 37 DST 516 5/16-18 X 1 1/4 25 7.50 125 1/2' 8031925 601 DST 2.0 1/4-14 X 2 ‘;:a15.1 1/2" 8033925 422 DSTR 1.0 1/4-20 X 1 25 6.25 125 tfi 11.7:1 1/2' 8035925 443 DST 5.16 5/16-18 X 1-1/4 25 8.44 125 onerete 25 8.44 125 ,T4v41,63, WX:444-e, zsm e., Part 8113910 Item 100 Fig 907 4 -Way Longitudinal Sway Brace Attachment Size Range 1 x 1 1 x 1 1.. and 1V x 1 /h bracing pipe Material Carbon Steel, hardened cone (or cup) point engaging screw Function For bracing pipe against sway and seismic disturbances, Functions as as longitudinal brace connection when attached to a lateral brace pipe. Bracing connection must be_positioned as close as physically possible to the braced pipe (No more than 3' away) Must be used only with TOLCO bracing components. When used in conjunction with TOLCO Fig. 1000 this combination bracing restricts piping movement in tension and compression both laterally and longitudinally. Features Universal swivel design allows the Fig. 907 to achieve any angle of attachment required Pipe end requires no threads simply slide bracing pipes through fittings and tighten each set screw until lock washer is fully compressed, or extends 20 ft. -lbs. Application Note Length of bracing pipe per NFPA 13, Table 6-4 5.8 (L/R =200); 1 schedule 40 pipe maximum TO' 11/4 schedule 40 pipe maximum 9'0' Alternative pipe materials are currently under review Please consult factory Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD) For additional load spacing and placement information relating to OSHPD projects please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish Plain Note Available in Electra- Galvanized and HDG finish. Order By Figure number bracing pipe sizes and finish. Important Note The Fig. 907 is precision manufactured to perform its function as a critical component of a complete bracing assembly. To ensure performance. the UL Listing requires that the Fia. 907 must be used only with other TOLCO bracing products. The Fla. 907 is not intended for use with the Fla. 1001 Sway Brace Attachment. NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS. Tolco Fia. 930 TOlco Fig. 907 Dimensions Weigh is Max. Design .Approx. Pipe Size A B Laed .Lbs. t Wt:il•f0 1 x 1 .4 /4 4 655` 103 I X1. 5' /,e 4 655* 1'07 1 X -i'/s 5 5 655* 109 Load will accbrrirnpdate tip 4' •pipe ai:rniArf uni spacingg- ,r 1 x l Tolto Fig_ .960 OFFICE/MANUFACTURING-FACILITY 137.5 SAMPSON AVE, CORONA, CA'S2873 -PH: i''L?32 .S5 °O- .F.A)s..95173i; 0330. CtiSTIINIER SERVICE '804.786.5256 wweotoico com Component of State of California OSHPD Approved Seismic Restraints System t no t Fig 1000 "Fast Clamp" Sway Brace Attachment Size Range Pipe size to be braced 1 thru 6' Schedule 10 thru 40 Pipe size used for bracing 1 and 11/4 Schedule 40 IPS. Additionally (UL) approved for use to brace Schedule 7 sprinkler pipe up to 4 (maximum horizontal design load 655 lbs.) Torque requirement 6 8 ft. lbs. Material Carbon Steel Function For bracing pipe against sway and seismic disturbance. The pipe attachment component of a sway brace system. Fig 1000 is used in conjunction with a TOLCOT" Fig 900 Series Fitting and joined together with bracing pipe per NFPA 13* or TOLCO OSHPD Approved Seismic Manual forming a complete sway brace assembly Features Can be used to brace Schedules 7 thru 40 IPS. Field adjustable making critical pre engineering of bracing pipe unnecessary. Unique design requires no threading of bracing pipe. Can be used as 4 -way riser brace. Can be used as longitudinal brace with Fig. 907 All steel construction eliminates structural deficiencies associated with casting type sway brace fittings. Comes assembled and individually packaged with illustrated installation instructions sizes are clearly marked. Steel leaf spring insert provided to assure installer and inspector necessary minimum torque has been achieved. Application Note Position Fast Clamp and tighten two hex nuts until leaf spring flattens. A minimum of 1 pipe extension beyond the Fig. 1000 is recommended. Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). Finish Plain Note Available in Electro Galvanized and HDG finish or Stainless Steel materials. Order By Order first by pipe size to be braced, followed by pipe size used. for bracing figure number and finish. important Note —The Fig. 1000 is precision 'manufactured t� perform its function as a critical component of a complete Prating assembly. To ensure performance. the UL Listiria reouires that the Fin:. 1000 must be used only with other TOLCO bracino products. Maximum Design Load 1 thru 4 pipe size 2015 lbs. 6' size 1265 lbs. 'Main Ofice7Manutactu ring 1375Sampsen:AVe. fnronaSA 52879 'PYr :909337.5599- Far 909737:0330 Customer "Service. 300.7865269. wwK.tvlce.com Component of State of California OSHPD Approved Seismic Restraints System 1/V.1tVVa! CD LD evisinn 2/02/20D Fig 909 No- Thread Swivel Sway Brace Attachment Size Range 1 bracing pipe For brace pipe sizes larger than 1 use TOLCO Fig 980 Material Carbon Steel, hardened cone point engaging screw Function The structural component of a sway and seismic bracing system Features This product's design incorporates a concentric attach- ment opening which is critical to the performance of structural seismic connections. NFPA 13 (1999 Edition) Table 6-4 5 9 indicates clearly that fastener table load values are based only on concentric loading No threading of the bracing pipe is required. Open design allows for easy inspection of pipe engagement. All steel construction eliminates deficiencies associated with malleable type attachments Fastener can be mounted to all surface angles Application Note The Fig. 909 is used in conjunction with the TOLCO Fig. 1000 Fig. 1001 or Fig 4 (A) pipe clamp and joined together with bracing pipe. Install per NFPA 13 and /or TOLCO State of California OSHPD Approved Seismic Restraint Manual. The required type, number and size of fasteners used for the structure attachment fitting shall be in accordance with NFPA13 and/or OSHPD Installation Extend bracing pipe through opening Tighten cone point engaging screw until head bottoms out or minimum torque 23 ft. /lbs. Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD) For additional load spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Finish Plain Note Available in Electro- Galvanized and HDG finish. Order By Figure number pipe size and finish Important Note The Fig. 909 is precision manufactured to perform its function as a critical component of a complete bracing assembly Sway brace assemblies are intended to be installed in accordance with NFPA13 and the manufacturer's installation instructions. To ensure performance. the UL Listing reauires that the Fin. 909 must be used only with other TOLCO bracina products NATIONAL AND INTERNATIONAL PATENT APPLICATION IN PROCESS. ®c Component of State of California OSHPD Approved Seismic Restraints System n Dimensions Weights Max. Design. Max. Design Load Approx. A B Pipe Size H Load Lbs. Lbs. w/Washer Wt. /100 1 6 1 /8 17/32 2015 2765 91 Available with hole sizes to accommodate up to 3/4° fastener. Consult Factory. OFFICE/MANUFACTURING FACILITY 1375 SAMPSON AVE. CORONA, CA 92879 PH: 951.737.5599 FAX: 951 737.0330 CUSTOMER SERVICE 800.786.5266 www.tolco.com Fig 800 Adjustable Sway Brace Attachment to Steel Size Range 4 thru 18' beam width Material Carbon Steel Function Seismic brace attachment to steel Features This product's design incorporates a concentric attach- ment point which is critical to the performance of structural seismic connections. NFPA 13 indicates the importance of concentric loading of connections and fasteners. Permits secure connection to steel where drilling and /or welding of brace connection could present struc tural issues. Comes completely assembled ready for installation. The Fig 800 must be used with one of the TOLCOTm Fig 900 series brace fittings (ordered separately) Installation Instructions Tighten set bolts against flange until bolt head breaks off. Tighten hex head bolts into clamp body until lock washers are fully flat. Application Note Allows bracing in either lateral or longitudinal direction Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD) Finish Plain Note Available in Electro- Galvanized and HDG finish. Order By Figure number type number and size number Important Structural Note TOLCO Steel Fig. 65/66 components were used during structural test ing and are required to achieve the listed results. Malleable iron com- ponents must never be substituted because of their serious potential for fracture and failure. Dimensions Weights *Max. Design Loads /Lbs. Flange Thickness Along Size Max. (In.) Beam 1 3/4 1265 2 1 1265 Dimensions Weights *Max. Design Fits Beam Along Size Range (ln.) Beam 1 4 6 1265 2 6 8 1265 3 8 10 1265 4 10 12 1265 5 12 14 1265 6 14 16 1265 7 16 18 1265 Across Beam 2015 2015 Loads /Lbs. Across Beam 2015 2015 2015 2015 2015 2015 2015 7 f Main Office/Manufacturing Facility 1375 Sampson Ave. Corona, CA 92879 Ph: 909.737.5599 Fax: 909.737.0330 Customer Service 800.786.5266 www.tolco.com Component of State of California OSHPD Approved Seismic Restraints System SHOWN WITH FIG. 980 BRACE FITTING TO PIPE BRACE (ACROSS BEAM) SHOWN WITH FIG. 980 BRACE FITTING TO PIPE BRACE (ALONG BEAM) wwvvtolco com R e rlslon 5/24/20D1 Fig 4A Pipe Clamp for Sway Bracing Size Range 4 thru 8' pipe For sizes smaller than 4 use TOLCOTM Fig 4 Material Carbon Steel Function For bracing pipe against sway and seismic disturbance. Approvals Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) 4 thru 8' Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD) For additional load spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines. Installation Instructions Install Fig 4A Pipe Clamp on pipe to be braced Attach Sway -Brace Fitting to 1/2' Clamp bolt (Sway -Brace Fitting to be on out side ears of clamp) Tighten securely. (min torque requirement 50 ft. lbs.) Sway Brace Assemblies are intended to be installed in accordance with NFPA 13 and the Manufacturers Installation Instructions. Finish Plain Note Available in Electro- Galvanized and HDG finish or Stainless Steel materials. Order By Figure number, pipe size and finish Fig 4A Longitudinal Brace Fig 4A Brace ®C® Component of State of California OSHPD Approved Seismic Restraints System Dimensions Weights Pipe Max. Horizontal Approx. Sizes A B C D Bolt Size Design Load Wt. /100 4 8 9/16 3 3 11 /18 1/2 2015 221 5 9 9/16 3' /e 4 1/2 2015 253 6 11 5/8 5 5 1/2 2015 513 8 13V4 3/4 6 11 /,8 6 1/2 2015 601 OFFICE/MANUFACTURING FACILITY 1375 SAMPSON AVE. CORONA, CA 92879 PH: 951.737.5599 FAX. 951.737.0330 CUSTOMER SERVICE 800.786.5266 www.to%acom