August 4, 2005
Dear Mr Lee:
Dennis Lee
2270 Place Road
Port Angeles, WA 98363
`^4r.,
$4,393 00 fo
ORTANGELES
Public Works Utilities Department
SUBJECT Electrical power to Lots A B, Block 408
Lots A and B can be served from I Street with the addition of a pedestal and secondary cable
per the estimate provided m August 2003 However, smce you will be developmg the next
four lots to the east, it would be prudent to mstall primary electncal facihties which can be
extended m the future.
Our. City Policy requires electrical utihties to be mstalled m alleys for standard Lot/Block plats
and smce this alley will be eventually opened as it is developed, the electncal facilities will be
installed accordingly Please refer to attached drawmg.
d cost for installation of underground electrical facihties to Lots A and B is
labor and material provided by the City This estimate, based on the
n you provided, is good for 180 days. After 180 days or if there are any design
changes, the estimate will be reviewed and revised accordingly
New lme extensions are required to be underground unless the cost of underground is more
than twice the cost of overhead. The estimated cost for overhead installation is $3,037 00
which is more than one half of the underground cost, therefore, underground pnmary power is
the required installation.
Phone 360 -417 -4805 Fax' 360- 417 -4542
Website. www cityofpa us Enlail publicworks@cityofpa.us
321 East Fifth Street P 0 Box 1150 Port Angeles WA 98362 -0217
Page 2. D. Lee
The City will be responsible for the following items:
1 Providing and installing the underground user on the existing pole at the 14/15
alley on I Street.
2. Providing and mstallmg conduit, vault and cable.
3 Providing and mstalhng the padmount transformer and two (2) pedestals.
4 Removing the existing pole mount transformer and connectmg the two existing
services to a pedestal. Note: a riser cannot be installed on the same pole as a
transformer)
You will be responsible for the followmg:
1 Surveymg and staking of the alley adjacent to Lot B
2. Brmgmg alley and area for the padmount transformer to final grade.
3 All season, all hour alley to and including the transformer location per Public
Works specifications.
4 Providing the trench 47 inches deep from the final grade, 24 inches wide
rmmmuni, approximately 100 feet in length. The trench must meet
requirements of WAC Chapter 296 -155N, Excavation, Trenching, and
Shoring All excavated material shall be placed no closer than two (2) feet
from the edge of the excavation and any excavation over four (4) feet in depth
will require shormg.
5 Excavation for the 44 mch by 32 mch by 36 inch concrete vault with 6 inches
of gravel leveled in the bottom of the excavation.
6. Coordination with Qwest Communications, Wave Broadband, and Capacity
Provisioning, Inc. for the installation of their facilities. They may share the
trench with the electrical facilities.
7 Installation and future maintenance of the underground service wires m conduit
from the pedestal to the meter bases. The connection fee is $713 00 per meter
8 Permit to dig in the alley right -of -way
9 Grantmg an easement on Lot B for the location of the transformer and the
secondary service to Lot A. Please sign, notarize and return the attached
easement form.
10 Payment of the estimated amount of $4,393 00 Payment slip attached.
11 The completion of the above items, receipt of payment and an authonzmg
signature below will allow the City to schedule the mstallation. Construction
may begm m five to six weeks after completion of the above items. This time
is required by Engmeermg to complete the work order and for Operations to
schedule construction.
If the cost of construction exceeds the paid estimate, there will be no further billing. If the
cost is less than the estimate, the difference will be refunded.
page 3, D. Lee
When future customers take service from the new facilities, if withm seven years of
construction, the current owners will be reimbursed a proportionate amount of the original
cost of construction.
If you have any questions or concerns, please feel free to contact me at 360 417 -4708 or e-
mail: mnclaina.citvofDa_us.
Sincerely yours,
Gad McLain
Electrical Engineering Specialist
Authorizing Signature Date
cc: James Harper Electrical Engineering Manager
Permitting
File
ORT NGELES Y1(
W A S H I N G T O N U S A
PUBLIC WORKS UTILITIES DEPARTMENT
Mr Jim Taft
584 Maletti Hill
Port.Angeles, WA 98362
FAX 417 -2638
SUBJECT Extension of electrical primary power to Lots 13 through 20 Block 408
Habitat for Humanity
The estimated cost for labor and matenal supphed by the City to install underground
electrical primary facihties to serve eight lots is $14,199 09 This estimate is good for 180
days.
Our City pohcy for line extensions requires new installations to be underground unless the
cost of underground is more than twice the cost of overhead. The estimated cost for overhead
facihties is $8,073.34 which is more than one half the underground cost, therefore,
underground power is the required mstallation.
A new Connection Fee Policy has been established and became effective January 1, 2005 (see
attached letter) The connection fee of $713 00 for each house /meter connected to
underground facilities will be collected with the purchase of each electrical permit.
The City will be responsible for the following items:
1 Replacmg the existmg polemount transformer with a padmount transformer to allow
room for mstallation of the nser on the pole.
2 Providing and mstallmg conduit, vaults, cable, and related equipment.
3 Providing and mstallmg the padmount transformers and pedestals
321 EAST FIFTH STREET P 0 BOX 1 150 PORT ANGELES WA 98362 -0217
PHONE 360 -417 4805 FAX 360-417 4542 TTY 360 -417 4645
E MAIL publicworks @cityofpa us
page 2 Taft
The contractor will be responsible for the following:
1 Surveying and staking of the north property corners along the alley
2. Brmging the alley and north lot comers to final grade for the installation of the
electncal facihties.
3 All season, all weather alley
4 Providing the trench 47 inches deep from final grade, 24 mches wide minimum,
approxnnately 450 feet m length. The trench must meet the requirements of WAC
Chapter 296 -155N, Excavation, Trenching, and Shoring All excavated material shall
be placed no closer than two (2) feet from the edge of the excavation and any
excavation over four (4) feet m depth will require shoring. Four alley crossings
30mches from final grade.
5 Excavation for three 44 mch by 32 mch by 36 mch concrete vaults with 6 inches of
gravel leveled m the bottom of the excavation.
6 Coordmation with Qwest Commumcation, Wave Broadband, and Capacity
Provisioning, Inc. for the mstallation of their facihties They may share the trench with
the electncal facihties.
7 Installation and future maintenance of the underground service wires in conduit from
the pedestals to the meter bases for each house.
8 Pemnt to dig in the alley right -of -way
9 Grantmg easements for the location of the transformers and pedestals. Please sign,
notanze, and return the enclosed easement forms to our office.
10 An authonzmg signature m the space provided below and payment of the estimated
amount of $14,199 09
If the cost of construction exceeds the payed estimate, there will be no further billing If the
cost is less than the estimate, the difference will be refunded.
The completion of the above items, receipt of payment and an authonzmg signature below
will allow the City to schedule the work. Construction may begm m five to six weeks after
completion of the above items This time is required by Engineering to complete the work
order and for Operations to schedule construction.
page 3 Taft
When future customers take service from the new facilities, the current owners will be
reimbursed a proportionate amount of the ongmal cost of construction if the connection is
made within seven (7) years of installation.
If you have any questions or concerns, please do not hesitate to contact me at 360 -417 -4708
or e-mail: emclam(citvofua.us.
Smcerely yours,
Gail McLain
Electrical Engmeermg Specialist
Authorizing Signature Date
cc: James Harper, Electrical Engineering Manager
Roger Vess, permitting
File